Honeywell T6 Pro Installation Instructions

T6 Pro
Programmable Thermostat
Installation Instructions
Package Includes:
• T6 Pro Thermostat
• UWP Mounting System
• Honeywell Standard Installation Adapter (J-box adapter)
• Honeywell Decorative Cover Plate – Small; size 449/64 in x 449/64 in x 11/32 in (121 mm x 121 mm x 9 mm)
• 2 AA Batteries
• Installation Instructions and User Guide
Optional Cover Plate installation
NOTE: If Optional Cover Plate is not
required, see “UWP Mounting System installation” on next page.
Use the Optional Cover Plate when:
• Mounting the thermostat to an electrical junction box
• Or when you need to cover paint gap from old thermostat.
1. Separate the Junction Box Adapter from the Cover Plate. See Figure 1.
2. Mount the Junction Box Adapter to the wall or an electrical box using any of the eight screw holes. Insert and tighten mounting screws supplied with Cover Plate Kit. Do not overtighten. See Figure 2. Make sure the Adapter Plate is level.
3. Attach the UWP by hanging it on the top hook of the Junction Box Adapter and then snapping the bottom of the UWP in place. See Figure 3.
4. Snap the Cover Plate onto the Junction Box Adapter. See Figure 4.
1
2
Use 2x
supplied
screws #6
5/8”
4
3
UWP Mounting System installation
6
5. Before starting, turn the power off at the breaker box or switch. Open package to find the UWP. See Figure 5.
6. Position the UWP on wall. Level and mark hole positions. See Figure 6.
Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.
‒ Drill 7/32” holes for drywall.
7. Pull the door open and insert the wires through wiring hole of the UWP. See Figure 7.
8. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP no longer moves. Close the door. See Figure 8.
5
7
8
Use 3x supplied
screws #8 11/2”
Power options
L/A
S
S
Y
Y
G
C
U
U
Insert R and C wires into designated terminals for primary AC power (C terminal is optional if batteries are installed, but it is recommended). Remove wires by depressing the terminal tabs.
A
O/B
AUX
W2
E
W
K
R
Rc
Insert AA batteries for primary or backup power.
2
Setting Slider Tabs
Set R Slider Tab.
• Use built-in jumper (R Slider Tab)
to differentiate between one or two transformer systems.
• If there is only one R wire, and it is
connected to the R, Rc, or RH terminal, set the slider to the up position (1 wire).
• If there is one wire connected to the R
terminal and one wire connected to the Rc terminal, set the slider to the down position
(2 wires).
NOTE: Slider Tabs for U terminals should be
left in place for T6 Pro models.
Wiring terminal designations
UWP Mounting System
R/Rc slider tab
Universal input for
S
wired indoor or outdoor sensors
S
Compressor contactor
Y
(stage 1)
Compressor contactor
Y2
(stage 2)
Fan Relay W Heat relay (stage 1)
G
24VAC common. For 2 transformer systems,
C
use common wire from cooling transformer.
U
Unused
U
L/A
- A
O/B Changeover valve
AUX ­W2
E Emergency Heat relay
K
R
Rc
Heat Pump fault input (most common case)
Auxiliary heat relay Heat relay (stage 2)
Connect to K on Wire Saver Module**
24VAC power from heating transformer*
24VAC power from cooling transformer*
Note: Not all
terminals may be
used, depending
on the system
type that is being
wired. The most
commonly used
terminals are
shaded.
* Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above. ** The THP9045A1023 Wire Saver Module is used on heat/cool systems when you
only have four wires at the thermostat, and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more information.
3
Wiring conventional systems: forced air and hydronics
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C System (1 transformer) R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24VAC common [3] W Heat relay G Fan relay
Heat-only System R Power [1]
Rc [R+Rc joined by Slider Tab] [2] C 24VAC common [3] W Heat relay
Heat-only System (Series 20) [5] R Series 20 valve terminal “R” [1]
Rc [R+Rc joined by Slider Tab] [2] Y Series 20 valve terminal “W” C 24VAC common [3] W Series 20 valve terminal “B”
Heat-only System (power open zone valve) [5]
R Power [1] Rc [R+Rc joined by Slider Tab] [2] W Valve C 24VAC common [3]
1H/1C System (2 transformers) R Power (heating transformer) [1]
Rc Power (cooling transformer) [1] Y Compressor contactor C 24VAC common [3, 4] W Heat relay G Fan relay
Heat-only System with Fan R Power [1]
Rc [R+Rc joined by Slider Tab] [2] C 24VAC common [3] W Heat relay G Fan relay
Cool-only System R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24VAC common [3] G Fan relay
2H/2C System (1 transformer) [6] R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor (stage 1) C 24VAC common [3] W Heat relay (stage 1) G Fan relay W2 Heat relay (stage 2) Y2 Compressor contactor (stage 2)
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not required.
[1]
Power supply. Provide disconnect means and overload
protection as required.
Move RSlider Tab on UWP to the R setting. For more
[2]
information, see “Setting Slider Tabs” on page 3
Optional 24VAC common connection.
[3]
[4] Common connection must come from cooling transformer. [5] In ISU set Heat system type to Radiant Heat. Set number of
cool stages to 0.
In Installer Setup, set system type to 2Heat/2Cool
[6]
Conventional.
4
Wiring heat pump systems
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C Heat Pump System R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24VAC common [3] O/B Changeover valve [7] G Fan relay
2H/1C Heat Pump System [8] R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux Auxiliary heat E Emergency heat relay L Heat pump fault input
2H/2C Heat Pump System [9] R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor (stage 1) C 24VAC common [3] O/B Changeover valve [7] G Fan relay Y2 Compressor contactor (stage 2) L Heat pump fault input
3H/2C Heat Pump System (TH6320U only) [10]
R Power [1] Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor (stage 1) C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux Auxiliary heat E Emergency heat relay Y2 Compressor contactor (stage 2) L Heat pump fault input
Dual Fuel System R Power [1]
Rc [R+Rc joined by Slider Tab] [2] Y Compressor contactor (stage 1) C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux Auxiliary heat E Emergency heat relay Y2 Compressor contactor (stage 2 - if needed) L Heat pump fault input S Outdoor sensor S Outdoor sensor
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not required.
[1]
Power supply. Provide disconnect means and overload
protection as required.
Move RSlider Tab on UWP to the R setting. For more
[2]
information, see “Setting Slider Tabs” on page 3
Optional 24VAC common connection.
[3] [6] In Installer Setup, set system type to 2Heat/2Cool
Conventional.
[7]
In Installer Setup, set changeover valve to O (for cool
changeover) or B (for heat changeover).
In ISU set Heat system type to Heat pump. 1 compressor
[8]
and 1 stage of backup heat.
In ISU set Heat system type to Heat pump. 2 compressors
[9]
and 0 stage of backup heat.
In ISU set Heat system type to Heat pump. 2 compressors
[10]
and 1 stage of backup heat.
5
Thermostat mounting
1. Push excess wire back into the wall opening.
2. Close the UWP door. It should remain closed without bulging.
3. Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
4. Turn the power on at the breaker box or switch.
System operation settings
1 Press the Mode button to cycle to the next
available System mode.
2 Cycle through the modes until the required
System mode is displayed and leave it to activate.
NOTE: Available System modes vary by model and system settings.
System modes:
Auto Heat Cool Em Heat Off
Fan operation settings
1 Press the Fan button to cycle to the next
available Fan mode.
2 Cycle through the modes until the required
Fan mode is displayed and leave it to activate.
NOTE: Available Fan modes vary with system settings.
Fan modes:
Auto: Fan runs only when the heating or
cooling system is on.
On: Fan is always on. Circ: Fan runs randomly about 33% of
the time.
6
Installer setup (ISU)
1 Press and hold CENTER and buttons for
approximately 3 seconds to enter advanced menu.
2 Press Select to enter ISU. 3 Press Select to cycle through menu setup
options.
4 Press or to change values or select
from available options.
5 Press Select and confirm your settings or
press Back to ignore changes and return to ISU menu screen to continue editing another setup option.
6 To finish setup process and save your
setting, press Home and return to Home screen.
NOTE: A complete list of all setup (ISU) parameters and options starts below and continues through page 10.
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISU IS U Name ISU Op tions (fac tory defau lt in bold)
120 Scheduling Options 0 = NonProgrammable
125 Temperature Indication Scale
130 Outdoor Sensor
(TH 6320 / TH6220 only)
200 Heati ng System Type
205 Heating Equipment Type Conventional Forced Air Heat:
218 Reversing Valve O/B
220 Cool Stages / Compressor Stages
200= Conv / 200 =HP (TH 6320 / TH6220 only*)
2 = 52 Progra mmable
3 = 511 Programmable
4 = 7Day Progr ammable
0 = Fahrenheit
1 = Cel sius
0 = None
1 = Wired O utdoor Sen sor
1 = Conventional Forced Air Heat
2 = Heat Pu mp 3 = Radian t Heat 5 = None (Co ol Only)
1 = Standa rd Efficie ncy Gas For ced Air
2 = High Efficiency Gas Forced Air
3 = Oil For ced Air 4 = Elec tric Force d Air 5 = Hot Wate r Fan Coil
Heat Pum p:
7 = Air to Air Heat Pump
8 = Geot hermal Heat P ump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
0 = O (O/B in Cool)
1 = B (O/B in He at)
0, 1, 2*
7
Advanced setup options (ISU)
# ISU IS U Name ISU Op tions (fac tory defau lt in bold)
221 Heat Sta ges / Backu p Heat Stage s Heat Stag es: 1, 2
230 Fan Co ntrol in Heat 1 = Equipment Controls Fan
253 Aux /E terminal c ontrol (T H6320
only)
255 Back up Heat Sourc e
(Heat P ump Only)
256 Emerg ency Heat S ource (TH 6320
only)
260 Ex ternal Fos sil Fuel Kit
(TH 6320 / TH6220 only)
270 Ba ckup Heat Fan 1 = Equipment Controls Fan
271 Emergency Heat Fan 1 = Equipment Controls Fan
300 System Changeover
303 Auto Changeover Differential 0 °F to 5 °F
340 Backup Heat Droop
350 Upsta ge Timer for B ackup Heat
355 Compre ssor Lock out / Balanc e Point
356 Outdoo r Lockout Ba ckup Heat
365 Compre ssor Cyc le Rate (Stage 1 ) 1 - 6
366 Compre ssor Cyc le Rate (Stage 1 ) 1 - 6
370 He ating Cycl e Rate (Stage 1) 1 - 12
371 He ating Cycle R ate (Stage 2) 1 - 12
Backu p Heat Stage s: 0, 1
2 = Thermostat Controls Fan
0 = Drive both Aux & E together
1 = Aux and E in dependent
1 = Electric Forced Air
2 = Gas/ Oil Forced A ir (or Fossil Fo rced Air)
1 = Electric Forced Air
2 = Gas/ Oil Forced A ir (or Fossil Fo rced Air)
0 = Thermostat Controls Backup Heat
1 = Ex ternal Fos sil Fuel Kit C ontrols B ackup Heat
2 = Thermostat Controls Fan
Note: S etting onl y active wi th TH6320 in Heat P ump mode.
2 = Thermostat Controls Fan
Note: S etting onl y active wi th TH6320 in Heat P ump mode.
0 = Manual
1 = Automatic
0.0 °C to 2.5 ° C
Note: Differential is NOT deadband. Differential means how far past the setpoint before switching to the mode selected. Deadband setup is not an option. Honeywell uses an advanced algorithm that fixes deadband at 0 °F. This is more advanced than previous thermostats.
0 = Comfort
2 = 2 °F 3 = 3 °F 4 = 4 °F 5 = 5 °F 6 = 6 °F 7 = 7 °F 8 = 8 °F
0 = Off
1 = 30 minute s 2 = 45 minute s 3 = 60 minut es 4 = 75 minute s 5 = 90 minut es 6 = 2 hours 7 = 3 hours 8 = 4 hours 10 = 5 hours
-- = Of f
5 °F to 60 ° F (in 5 °F increme nts) 15.0 °C to 15.5 ° C (in 2.5 °C or 3.0 ° C increment s)
Note: Us e a wired senso r to set compres sor lockout / b alance point o n TH6320 / TH6220 .
-- = Of f
5 °F to 65 °F ( in 5 °F increme nts) 15.0 °C to 18.5 ° C (in 2.5 °C or 3.0 ° C increment s)
9 = 9 °F 10 = 10 °F 11 = 11 °F 12 = 12 °F 13 = 13 °F 14 = 14 °F 15 = 15 °F
8
Advanced setup options (ISU)
# ISU IS U Name ISU Op tions (fac tory defau lt in bold)
375 He ating Cycle R ate Auxili ary Heat 1 - 12
378 H eating Cycl e Rate Emerge ncy Heat
(TH 6320 only)
387 Compre ssor Protection 0 = Off
425 Adaptive Intelligent Recovery 0 = No
430 Minimum Cool Setpoin t 50 °F to 99 ° F (50 °F)
431 Maxim um Heat Setp oint 40 °F to 90 ° F (90 °F)
435 Keypad Lockout
500 Is Indoor Temperature Sensor WIRED
to your s ystem? (T H6320 / TH6220 only)
515 Indoor Sensor type
(TH 6320 / TH6220 only)
520 Whi ch Sensor s will be used f or
TEMPERATURE Control ? (Multiple Sens ors are Aver aged) (TH 6320 / TH6220 only)
702 Numb er of Air Filt ers 0 - 2
711 Air Filter 1 Replacement Reminder
712 Air Filter 2 Replacement Reminder
140 0 Backlighting
1401 Backlight brightness 1 - 5
1410 Clock Format 12 / 24
1415 Daylight Saving T ime 0 = O ff
1420 Temperature Display Offset 3 to 3F (0)
1 - 12
1 - 5 minutes
1 = Yes
Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.
10.0 °C to 37.0 °C (10.0 °C)
4.5 °C to 32 .0 °C (32.2 °C)
0 = None
1 = Part ial 2 = Full
0 = No
1 = Yes
0 = 10k
1 = 20k
1 = Ther mostat Onl y 2 = Wired O nly
3 = Average
0 = Off
1 = 10 Run Time D ays 2 = 20 Run Tim e Days 3 = 30 Run Ti me Days 4 = 45 Run Tim e Days 5 = 60 Run Ti me Days 6 = 90 Run Ti me Days 7 = 120 Run Tim e Days 8 = 150 Run Tim e Days 9 = 30 Cale ndar Days
0 = Off
1 = 10 Run Time D ays 2 = 20 Run Tim e Days 3 = 30 Run Ti me Days 4 = 45 Run Tim e Days 5 = 60 Run Ti me Days 6= 90 Run T ime Days 7 = 120 Run Tim e Days 8 = 150 Run Tim e Days 9 = 30 Cale ndar Days
0 = On Demand
1 = Continuous
Note: Common wire needed for continuous.
Note: Only displayed if continuous backlight selected.
1 = On
1.5 to 1.5C (0)
10 = 45 Calen dar Days 11 = 60 Cal endar Days 12 = 75 Calen dar Days 13 = 3 Calen dar Months 14 = 4 Calenda r Months 15 = 5 Calen dar Months 16 = 6 Calen dar Months 17 = 9 Calenda r Months 18 = 12 Calen dar Months 19 = 15 Calen dar Months
10 = 45 Calen dar Days 11 = 60 Cal endar Days 12 = 75 Calen dar Days 13 = 3 Calen dar Months 14 = 4 Calenda r Months 15 = 5 Calen dar Months 16 = 6 Calen dar Months 17 = 9 Calenda r Months 18 = 12 Calen dar Months 19 = 15 Calen dar Months
9
Installer system test
To perform a System Test: 1 Press and hold CENTER and buttons for
approximately 3 seconds to enter advanced menu.
2 Use to go to TEST. Press Select to enter
System Test.
3 Use to change between Heat, Cool, Fan, Em
Heat, or Ver (thermostat version information). Press Select.
4 Press to turn stages on one at a time, and
press to turn them off.
5 Use the Home button to exit the System Test.
System test System status
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
All Off
0
Heat Stage 1 on
Heat
Cool
Em Heat
Fan
1
Heat Stage 2 also on
2
Heat Stage 3 also on
3
All Off
0
Cool Stage 1 on
1
Cool Stage 2 also on
2
All Off
0
Em Heat on
1
Fan Off
0
Fan On
1
10
Specifications
Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C) Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
Working Ambient Temperature
32 °F to 120 °F (0 C° to 48.9 °C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.9 °C)
Shipping Temperature
20 °F to 120 °F (28.9 °C to 48.9 °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x W x D)
41/16” H x 41/16” W x 15/32” D
103.5 mm H x 103.5 mm W x 29 mm D
Electrical Ratings
Terminal Voltage
(50/60Hz)
W Heating 2030 Vac 0.021.0 A
(Powerpile) 750 mV DC 100 mA DC
W2 (Aux) Heating 2030 Vac 0.021.0 A E Emergency Heat 2030 Vac 0.020.5 A Y Compressor Stage 1 2030 Vac 0.021.0 A Y2 Compressor Stage 2 2030 Vac 0.021.0 A G Fan 2030 Vac 0.020.5 A O/B Changeover 2030 Vac 0.020.5 A L/A Input 2030 Vac 0.020.5 A
Running Current
11
Loading...
+ 25 hidden pages