• Honeywell Standard Installation
Adapter (J-box adapter)
• Honeywell Decorative Cover Plate –
Small; size 449/64 in x 449/64 in x
11/32 in (121 mm x 121 mm x 9 mm)
• Screws and anchors
• 2 AA Batteries
• Installation Instructions and User
Guide
Optional Cover Plate installation
NOTE: If Optional Cover Plate is not
required, see “UWP Mounting System
installation” on next page.
Use the Optional Cover Plate when:
• Mounting the thermostat to an
electrical junction box
• Or when you need to cover paint gap
from old thermostat.
1. Separate the Junction Box Adapter
from the Cover Plate. See Figure 1.
2. Mount the Junction Box Adapter to
the wall or an electrical box using any
of the eight screw holes. Insert and
tighten mounting screws supplied with
Cover Plate Kit. Do not overtighten. See
Figure 2. Make sure the Adapter Plate
is level.
3. Attach the UWP by hanging it on the
top hook of the Junction Box Adapter
and then snapping the bottom of the
UWP in place. See Figure 3.
4. Snap the Cover Plate onto the Junction
Box Adapter. See Figure 4.
1
2
Use 2x
supplied
screws #6
5/8”
4
3
UWP Mounting System installation
6
5. Before starting, turn the power off
at the breaker box or switch. Open
package to find the UWP. See Figure 5.
6. Position the UWP on wall. Level and
mark hole positions. See Figure 6.
Drill holes at marked positions, and
then lightly tap supplied wall anchors
into the wall using a hammer.
‒ Drill 7/32” holes for drywall.
7. Pull the door open and insert the wires
through wiring hole of the UWP. See
Figure 7.
8. Place the UWP over the wall anchors.
Insert and tighten mounting screws
supplied with the UWP. Do not
overtighten. Tighten until the UWP
no longer moves. Close the door. See
Figure 8.
5
7
8
Use 3x supplied
screws #8 11/2”
Power options
L/A
S
S
Y
Y
G
C
U
U
Insert R and C wires into
designated terminals for primary
AC power (C terminal is optional
if batteries are installed, but it is
recommended). Remove wires by
depressing the terminal tabs.
A
O/B
AUX
W2
E
W
K
R
Rc
Insert AA batteries for primary or backup
power.
2
Setting Slider Tabs
Set R Slider Tab.
• Use built-in jumper (R Slider Tab)
to differentiate between one or two
transformer systems.
• If there is only one R wire, and it is
connected to the R, Rc, or RH terminal, set
the slider to the up position (1 wire).
• If there is one wire connected to the R
terminal and one wire connected to the Rc
terminal, set the slider to the down position
(2 wires).
NOTE: Slider Tabs for U terminals should be
left in place for T6 Pro models.
Wiring terminal designations
UWP Mounting System
R/Rc slider tab
Universal input for
S
wired indoor or outdoor
sensors
S
Compressor contactor
Y
(stage 1)
Compressor contactor
Y2
(stage 2)
Fan RelayWHeat relay (stage 1)
G
24VAC common. For 2
transformer systems,
C
use common wire from
cooling transformer.
U
Unused
U
L/A
- A
O/BChangeover valve
AUX W2
EEmergency Heat relay
K
R
Rc
Heat Pump fault input (most
common case)
Auxiliary heat relay
Heat relay (stage 2)
Connect to K on Wire Saver
Module**
24VAC power from heating
transformer*
24VAC power from cooling
transformer*
Note: Not all
terminals may be
used, depending
on the system
type that is being
wired. The most
commonly used
terminals are
shaded.
* Terminal can be jumped using Slider Tab. See “Setting Slider Tabs” above.
** The THP9045A1023 Wire Saver Module is used on heat/cool systems when you
only have four wires at the thermostat, and you need a fifth wire for a common wire.
Use the K terminal in place of the Y and G terminals on conventional or heat pump
systems to provide control of the fan and the compressor through a single wire—the
unused wire then becomes your common wire. See THP9045 instructions for more
information.
3
Wiring conventional systems: forced air and hydronics
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C System (1 transformer)
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
W Heat relay
G Fan relay
Heat-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat relay
Heat-only System (Series 20) [5]
R Series 20 valve terminal “R” [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Series 20 valve terminal “W”
C 24VAC common [3]
W Series 20 valve terminal “B”
Heat-only System
(power open zone valve) [5]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
W Valve
C 24VAC common [3]
1H/1C System (2 transformers)
R Power (heating transformer) [1]
Rc Power (cooling transformer) [1]
Y Compressor contactor
C 24VAC common [3, 4]
W Heat relay
G Fan relay
Heat-only System with Fan
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
C 24VAC common [3]
W Heat relay
G Fan relay
Cool-only System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
G Fan relay
2H/2C System (1 transformer) [6]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
W Heat relay (stage 1)
G Fan relay
W2 Heat relay (stage 2)
Y2 Compressor contactor (stage 2)
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not required.
[1]
Power supply. Provide disconnect means and overload
protection as required.
Move RSlider Tab on UWP to the R setting. For more
[2]
information, see “Setting Slider Tabs” on page 3
Optional 24VAC common connection.
[3]
[4] Common connection must come from cooling transformer.
[5] In ISU set Heat system type to Radiant Heat. Set number of
cool stages to 0.
In Installer Setup, set system type to 2Heat/2Cool
[6]
Conventional.
4
Wiring heat pump systems
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C Heat Pump System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
2H/1C Heat Pump System [8]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
L Heat pump fault input
2H/2C Heat Pump System [9]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common[3]
O/B Changeover valve[7]
G Fan relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
3H/2C Heat Pump System
(TH6320U only) [10]
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
Y2 Compressor contactor (stage 2)
L Heat pump fault input
Dual Fuel System
R Power [1]
Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay
Aux Auxiliary heat
E Emergency heat relay
Y2 Compressor contactor (stage 2 - if needed)
L Heat pump fault input
S Outdoor sensor
S Outdoor sensor
NOTES
Wire specifications: Use 18 to 22-gauge thermostat wire. Shielded cable is not required.
[1]
Power supply. Provide disconnect means and overload
protection as required.
Move RSlider Tab on UWP to the R setting. For more
[2]
information, see “Setting Slider Tabs” on page 3
Optional 24VAC common connection.
[3]
[6] In Installer Setup, set system type to 2Heat/2Cool
Conventional.
[7]
In Installer Setup, set changeover valve to O (for cool
changeover) or B (for heat changeover).
In ISU set Heat system type to Heat pump. 1 compressor
[8]
and 1 stage of backup heat.
In ISU set Heat system type to Heat pump. 2 compressors
[9]
and 0 stage of backup heat.
In ISU set Heat system type to Heat pump. 2 compressors
[10]
and 1 stage of backup heat.
5
Thermostat mounting
1. Push excess wire back into the wall
opening.
2. Close the UWP door. It should remain
closed without bulging.
3. Align the UWP with the thermostat, and
push gently until the thermostat snaps in
place.
4. Turn the power on at the breaker box or
switch.
System operation settings
1 Press the Mode button to cycle to the next
available System mode.
2 Cycle through the modes until the required
System mode is displayed and leave it to
activate.
NOTE: Available System modes vary by model
and system settings.
System modes:
‒ Auto‒ Heat‒ Cool‒ Em Heat‒ Off
Fan operation settings
1 Press the Fan button to cycle to the next
available Fan mode.
2 Cycle through the modes until the required
Fan mode is displayed and leave it to
activate.
NOTE: Available Fan modes vary with system
settings.
Fan modes:
‒ Auto: Fan runs only when the heating or
cooling system is on.
‒ On: Fan is always on.‒ Circ: Fan runs randomly about 33% of
the time.
6
Installer setup (ISU)
1 Press and hold CENTER and buttons for
approximately 3 seconds to enter advanced
menu.
2 Press Select to enter ISU.
3 Press Select to cycle through menu setup
options.
4 Press or to change values or select
from available options.
5 Press Select and confirm your settings or
press Back to ignore changes and return
to ISU menu screen to continue editing
another setup option.
6 To finish setup process and save your
setting, press Home and return to Home
screen.
NOTE: A complete list of all setup (ISU)
parameters and options starts below and
continues through page 10.
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISUIS U NameISU Op tions (fac tory defau lt in bold)
120Scheduling Options0 = NonProgrammable
125Temperature Indication Scale
130Outdoor Sensor
(TH 6320 / TH6220 only)
200Heati ng System Type
205Heating Equipment TypeConventional Forced Air Heat:
218Reversing Valve O/B
220Cool Stages / Compressor Stages
200= Conv / 200 =HP
(TH 6320 / TH6220 only*)
2 = 52 Progra mmable
3 = 511 Programmable
4 = 7Day Progr ammable
0 = Fahrenheit
1 = Cel sius
0 = None
1 = Wired O utdoor Sen sor
1 = Conventional Forced Air Heat
2 = Heat Pu mp
3 = Radian t Heat
5 = None (Co ol Only)
1 = Standa rd Efficie ncy Gas For ced Air
2 = High Efficiency Gas Forced Air
3 = Oil For ced Air
4 = Elec tric Force d Air
5 = Hot Wate r Fan Coil
Heat Pum p:
7 = Air to Air Heat Pump
8 = Geot hermal Heat P ump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
0 = O (O/B in Cool)
1 = B (O/B in He at)
0, 1, 2*
7
Advanced setup options (ISU)
# ISUIS U NameISU Op tions (fac tory defau lt in bold)
221Heat Sta ges / Backu p Heat Stage sHeat Stag es: 1, 2
230Fan Co ntrol in Heat1 = Equipment Controls Fan
253Aux /E terminal c ontrol (T H6320
only)
255Back up Heat Sourc e
(Heat P ump Only)
256Emerg ency Heat S ource (TH 6320
only)
260Ex ternal Fos sil Fuel Kit
(TH 6320 / TH6220 only)
270Ba ckup Heat Fan 1 = Equipment Controls Fan
271Emergency Heat Fan 1 = Equipment Controls Fan
300System Changeover
303Auto Changeover Differential 0 °F to 5 °F
340Backup Heat Droop
350Upsta ge Timer for B ackup Heat
355Compre ssor Lock out / Balanc e Point
356Outdoo r Lockout Ba ckup Heat
365Compre ssor Cyc le Rate (Stage 1 )1 - 6
366Compre ssor Cyc le Rate (Stage 1 )1 - 6
370He ating Cycl e Rate (Stage 1) 1 - 12
371He ating Cycle R ate (Stage 2) 1 - 12
Backu p Heat Stage s: 0, 1
2 = Thermostat Controls Fan
0 = Drive both Aux & E together
1 = Aux and E in dependent
1 = Electric Forced Air
2 = Gas/ Oil Forced A ir (or Fossil Fo rced Air)
1 = Electric Forced Air
2 = Gas/ Oil Forced A ir (or Fossil Fo rced Air)
0 = Thermostat Controls Backup Heat
1 = Ex ternal Fos sil Fuel Kit C ontrols B ackup Heat
2 = Thermostat Controls Fan
Note: S etting onl y active wi th TH6320 in Heat P ump mode.
2 = Thermostat Controls Fan
Note: S etting onl y active wi th TH6320 in Heat P ump mode.
0 = Manual
1 = Automatic
0.0 °C to 2.5 ° C
Note: Differential is NOT deadband. Differential means how far past the setpoint
before switching to the mode selected. Deadband setup is not an option.
Honeywell uses an advanced algorithm that fixes deadband at 0 °F. This is more
advanced than previous thermostats.
# ISUIS U NameISU Op tions (fac tory defau lt in bold)
375He ating Cycle R ate Auxili ary Heat1 - 12
378H eating Cycl e Rate Emerge ncy Heat
(TH 6320 only)
387Compre ssor Protection0 = Off
425Adaptive Intelligent Recovery0 = No
430Minimum Cool Setpoin t50 °F to 99 ° F (50 °F)
431Maxim um Heat Setp oint40 °F to 90 ° F (90 °F)
435Keypad Lockout
500Is Indoor Temperature Sensor WIRED
to your s ystem? (T H6320 / TH6220
only)
515Indoor Sensor type
(TH 6320 / TH6220 only)
520Whi ch Sensor s will be used f or
TEMPERATURE Control ? (Multiple
Sens ors are Aver aged) (TH 6320 /
TH6220 only)
702Numb er of Air Filt ers0 - 2
711Air Filter 1 Replacement Reminder
712Air Filter 2 Replacement Reminder
140 0Backlighting
1401Backlight brightness 1 - 5
1410Clock Format12 / 24
1415Daylight Saving T ime0 = O ff
1420Temperature Display Offset3 to 3F (0)
1 - 12
1 - 5 minutes
1 = Yes
Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling
equipment will turn on earlier, ensuring the indoor temperature will match the
setpoint at the scheduled time.
10.0 °C to 37.0 °C (10.0 °C)
4.5 °C to 32 .0 °C (32.2 °C)
0 = None
1 = Part ial
2 = Full
0 = No
1 = Yes
0 = 10k
1 = 20k
1 = Ther mostat Onl y
2 = Wired O nly
3 = Average
0 = Off
1 = 10 Run Time D ays
2 = 20 Run Tim e Days
3 = 30 Run Ti me Days
4 = 45 Run Tim e Days
5 = 60 Run Ti me Days
6 = 90 Run Ti me Days
7 = 120 Run Tim e Days
8 = 150 Run Tim e Days
9 = 30 Cale ndar Days
0 = Off
1 = 10 Run Time D ays
2 = 20 Run Tim e Days
3 = 30 Run Ti me Days
4 = 45 Run Tim e Days
5 = 60 Run Ti me Days
6= 90 Run T ime Days
7 = 120 Run Tim e Days
8 = 150 Run Tim e Days
9 = 30 Cale ndar Days
0 = On Demand
1 = Continuous
Note: Common wire needed for continuous.
Note: Only displayed if continuous backlight selected.
1 = On
1.5 to 1.5C (0)
10 = 45 Calen dar Days
11 = 60 Cal endar Days
12 = 75 Calen dar Days
13 = 3 Calen dar Months
14 = 4 Calenda r Months
15 = 5 Calen dar Months
16 = 6 Calen dar Months
17 = 9 Calenda r Months
18 = 12 Calen dar Months
19 = 15 Calen dar Months
10 = 45 Calen dar Days
11 = 60 Cal endar Days
12 = 75 Calen dar Days
13 = 3 Calen dar Months
14 = 4 Calenda r Months
15 = 5 Calen dar Months
16 = 6 Calen dar Months
17 = 9 Calenda r Months
18 = 12 Calen dar Months
19 = 15 Calen dar Months
9
Installer system test
To perform a System Test:
1 Press and hold CENTER and buttons for
approximately 3 seconds to enter advanced
menu.
2 Use to go to TEST. Press Select to enter
System Test.
3 Use to change between Heat, Cool, Fan, Em
Heat, or Ver (thermostat version information).
Press Select.
4 Press to turn stages on one at a time, and
press to turn them off.
5 Use the Home button to exit the System Test.
System testSystem status
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
All Off
0
Heat Stage 1 on
Heat
Cool
Em Heat
Fan
1
Heat Stage 2 also on
2
Heat Stage 3 also on
3
All Off
0
Cool Stage 1 on
1
Cool Stage 2 also on
2
All Off
0
Em Heat on
1
Fan Off
0
Fan On
1
10
Specifications
Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
Working Ambient Temperature
32 °F to 120 °F (0 C° to 48.9 °C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.9 °C)
Shipping Temperature
20 °F to 120 °F (28.9 °C to 48.9 °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x W x D)
41/16” H x 41/16” W x 15/32” D
103.5 mm H x 103.5 mm W x 29 mm D
Electrical Ratings
TerminalVoltage
(50/60Hz)
W Heating2030 Vac0.021.0 A
(Powerpile)750 mV DC100 mA DC
W2 (Aux) Heating2030 Vac0.021.0 A
E Emergency Heat2030 Vac0.020.5 A
Y Compressor Stage 12030 Vac0.021.0 A
Y2 Compressor Stage 22030 Vac0.021.0 A
G Fan2030 Vac0.020.5 A
O/B Changeover2030 Vac0.020.5 A
L/A Input2030 Vac0.020.5 A
Running
Current
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.