Honeywell T6590A1000, T6590B1000 PRODUCT DATA

APPLICATIONS
The T6590 range of digital thermostats is designed to control the valves, fan and auxiliary electric heater within fan-coil systems.
Modern, attractive styling and comprehensive feature set makes the T6590 suitable for a wide range of applications.
There are a total of 8 application configurations supported, and these are:
Application Description
0 2 pipe system, heating only
1 2 pipe system, cooling only
2 2 pipe system, 1 stage heat or 1 stage cool
3 2 pipe system, 1 stage heat or 1 stage cool,
auto changeover
4 4 pipe system 1 stage heat and 1 stage cool
5 4 pipe system 1 stage heat and 1 stage cool
auto changeover
6 2 pipe system, 1 stage heat or 1 stage cool
with auxiliary electric heater
7 4 pipe system, mixed manual and auto
The different applications can be selected from the installer setup mode and by altering the external wiring connections
T6590 Series
FAN-COIL CONTROLLER
PRODUCT DATA
FEATURES
Large, easy to read LCD display with backlight
Heat / Cool or standby mode displayed on LCD
Lockable keypad
Room setpoint adjustable via simple-to-use up/down
buttons
Fan speed ON/Off, low/med/high or auto
Auto mode, fan speed is proportional to distance of room
temperature from setpoint
Manual or automatic heat / cool changeover
Control of auxiliary electric heater
Inbuilt or remote sensor (NTC20K) options available
Simultaneous display of room temperature and user
setpoint
Push button adjustment of setpoint
Switches allow manual control of system operation
and fan speed
Special energy savings mode activated by external
input from Energy Management System (EMS) – a window contact or hotel card-key - overrides the temperature setting to installer defined heating and cooling temperatures
Energy savings input (remote setback) can be
configured to be normally open (NO) circuit or normally closed (NC) circuit
All models have a proportional plus integral (P+I)
T6590 meets all relevant requirements for CE
approval
Installer setup mode allowing operating parameters
to be changed
Installer set up settings retained in the event of a
power loss
Central remote setback for both cooling and heating
operation
Freeze protection
Automatic setback to unoccupied mode with no key
operation
°C display
0°C to 2°C Temperature display offset available
Easy to use installer setup mode allows for simple
thermostat setup
Adjustable deadband for heat & cool sequence
control
Setpoint range 10°C to 32°C
Installer test mode for on-site wiring checks
Line voltage (230V~) models available
EN0H8579 R0 2009
T6590 FAN-COIL THERMOSTAT
SPECIFICATIONS
Setpoint range 10...32oC
Supply voltage
Control Performance
Electrical ratings
230 V~ (+10%, -15%), 50/60 Hz P+I algorithm applied to ON/OFF control gives typical control to ±1.0°C at 22°C at 50% duty cycle,
nominal control to ±1.0°C
Fan Motor: 230V~, 50…60Hz, 3.0A run, with inrush 6A Valve Actuators: 230V~, 50…60Hz, 1.0A run, with inrush 3.5A
Operational life
Mounting
Greater than 100,000 cycles (all loads) for thermostat contacts at 230 V~ Mounts directly onto wall or wall-box - a standard 65x65mm junction box (hole pitch 60mm). Mounting
screws supplied.
Wiring 11 screw-in terminals per unit, capable of accepting either 2 wires up to 1.5 mm
Energy Savings Input Voltage-free contact (rating 24Vdc), maximum contact resistance of 1000ohms
Enclosure Plastic 3-piece housing
Dimensions 97 x 148 x 29 mm (h x w x d)
Environmental requirements
Approvals
Operating temperature range 5 to 45ºC Shipping and storage temperature range -20 to 55ºC Humidity range 5 to 95% rh, non-condensing
CE mark, complying with standards EN60730-1 (2001), EN55014-1 (2007), EN55014-2 (1997). Product must be wired as shown for CE compliance.
T6590 APPLICATIONS
2
, or 1 x 2.5mm2
T6590A1000 – 2 Pipe Model
Application Description Changeover Fan speed
0 2 pipe system, heating only No
1 2 pipe system, cooling only No
2
3
6
2 pipe system, 1 stage heat or 1 stage cool 2 pipe system, 1 stage heat or 1 stage cool, auto changeover
2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heater
Manual
Seasonal Changeover
Manual with seasonal changeover
On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto
On/Off, 3 speed or Auto
T6590B1000 – 4 Pipe Model
Application Description Changeover Fan speed
0 2 pipe system, heating only No
1 2 pipe system, cooling only No
2
3
4
5
6
7
2 pipe system, 1 stage heat or 1 stage cool 2 pipe system, 1 stage heat or 1 stage cool, auto changeover
4 pipe system 1 stage heat and 1 stage cool
4 pipe system 1 stage heat and 1 stage cool auto changeover
2 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heater
4 pipe system, mixed manual and auto
Manual
Seasonal Changeover
Manual
Auto changeover
Manual with seasonal changeover
Manual / Auto changeover
On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto On/Off, 3 speed or Auto
On/Off, 3 speed or Auto
On/Off, 3 speed or Auto
On/Off, 3 speed or Auto
On/Off, 3 speed or Auto
Remote sensor
Y Y On Off
Y Y On Off
Y Y On Off
Y Y Y On Off
Y Y Y Y On Off
Remote sensor
Y Y On Off
Y Y On Off
Y Y On Off
Y Y Y On Off
Y Y On Off
Y Y On Off
Y Y Y Y On Off
Y Y On Off
Pipe sensor
Pipe sensor
Remote setback
Remote setback
Auxiliary Heater
Auxiliary Heater
Output type
Output type
EN0H8579 R0 2009
2
A
INSTALLATION
Location
The T6590 Series thermostat is the temperature control element in the fan-coil or air-conditioning system, and must be located about 1.2 to 1.5m above the floor (according to local building regulations) in a position with good air circulation at room temperature. Do not mount it where it could be affected by :-
- draughts or dead spots behind doors or in corners
- hot or cold air from ducts
- radiant heat from the sun or appliances
- unheated (uncooled) areas such as an outside wall behind the thermostat
- concealed pipes or chimneys
Mounting the thermostat
ny T6590 Series thermostat can be directly mounted on the wall or horizontally on either a 65x65mm standard junction box or a 2x4inch US junction box. Mounting screws are supplied for both alternatives.
IMPORTANT
The installer must be a trained service engineer Isolate the power supply before beginning installation
T6590 FAN-COIL THERMOSTAT
1. Locate the wall-plate in the mounting position, insert the mounting screws through the appropriate holes, and screw into position.
2. Complete the wiring.
3. Attach the thermostat to the wall-plate as follows:
4. Locate the 4 side slots on the wall plate into the appropriate slots on the back of the thermostat.
5. Press down firmly and snap the thermostat into place.
6. Tighten retaining screw in lower edge of thermostat.
Wiring the thermostat
The standard wiring access is via a hole in the centre of the thermostat wall-plate.
Removing the thermostat from the wall
If it becomes necessary to remove the thermostat from the wall-plate:
1. Isolate the power supply before removing the thermostat.
2. Loosen the retaining screw in the lower edge of the thermostat.
3. Pry the lower edge of the thermostat away from the wall­plate.
4. Use both hands to pull the thermostat straight away from the wall-plate.
5. NOTE - Incorrect removal of the thermostat from the wall-plate may damage the device.
EN0H8579 R0 2009
3
T6590 FAN-COIL THERMOSTAT
)
INSTALLER SETUP MODE (ISU
ISU Number and description
Units Range
- 0 = 2 Pipe system Heat Only
- 1 = 2 Pipe system Cool Only
- 2 = 2 Pipe system 1H1C manual changeover
T6590A1000 & T6590B1000
-
1 System Type
- 4 - 4 pipe system with manual changeover (not available on T6590A1000)
-
- 6 = 2 pipe system 1H1C with Auxiliary Heater. Manual changeover
- 7 = 4 pipe system, mixed manual and automatic changeover (not available on T6590A1000)
-
2 Valve output type
- 1 NC ON/OFF
-
3 Sensor Type
- 1 remote sensor (NTC20K)
-
4 Pipe sensor (Note: This item will be automatically populated based on ISU #2 selection).
5 Threshold for pipe sensor cooling
6 Threshold for pipe sensor heating
7 Fan control type
-
-
8 Dead band for four pipes ºC
9 Cycles Per Hour (CPH)
value for heating
10 Cycles Per Hour (CPH) value for cooling
11 Cycles Per Hour (CPH) value for Auxiliary Heater
-
-
-
-
ºC
ºC
-
-
-
-
3 = 2 Pipe system 1H1C auto changeover (default on T6590A1000)
5 = 4 Pipe system auto changeover (default on T6590B1000) (Not available on T6590A1000)
0 NO ON/OFF (Default)
0 Onboard Sensor (Default)
0 NO input (default mode is Heat)
1 NO input (default mode is Cool)
2 NC input (default mode is Heat)
3 NC input (default mode is Cool)
4 Analog input (Default)(NTC20K, T7414C1012
Range: 10-18 ºC (Default 15 ºC)
Range: 24-32 ºC (Default 27 ºC)
0 User can choose Cycle or Constant (Default) (3 speed: Low->Med->High->Auto-> Low)
1 CONSTANT ONLY (3 speed: Low->Med->High-> Low)
2 CYCLE ONLY Auto has fan ramping algorithm
1ºC, 2ºC (Default), 3ºC, 4ºC, 5ºC (not available on T6590A1000)
1 – 12CPH (Default 4)
1 – 6CPH (Default 3)
1-12 (Default 6)
N0H8579 R0 2009
ISU Number and description
12 Display
Temperature adjustment
13 Temperature Display mode
- 1 display Setpoint
Units Range
ºC -2ºC - +2ºC (Default 0ºC)
- 0 display Room Temperature
T6590 FAN-COIL THERMOSTAT
-
14 Heating setpoint Range Stops
15 Cooling setpoint Range Stops
16 Keypad Lockout
- 1 System button Locked out
- 2 Fan and System button Locked out
- 3 All buttons locked out
17 Remote setback
-
-
-
18 Remote setback heating setpoint
19 Remote setback cooling setpoint
20 Activity Sensing (No single key pressed after certain period which is configured in this parameter, the system will enter unoccupied mode)
- 1 4 Hour Sensing
ºC
ºC
-
-
ºC
ºC
-
2 display both (Default)
10-32ºC (default 32ºC)
10-32ºC (default 10ºC)
0 All keys available(default)
1: Hotel card NO, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc.
2: Hotel Card NC, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc.
3: Hotel Card enabled, NO, with 1 second software delay going from UnOcc to Occupied; 30 minute delay going from Occupied to UnOcc
4: Hotel Card enabled, NC, with 1 second software delay going from UnOcc to Occupied; 30 minute delay going from Occupied to UnOcc.
Range 10-21ºC (Default 18ºC)
Range 22-32ºC (Default 26ºC)
0 Disabled (Default)
- 2 12 Hour Sensing
-
21 Freeze Protection
-
22 Auto Fan Reset
-
-
23 Fan run-on time after auxiliary heater is switched off
-
-
S 0 – 600Sec (Default 60Sec)
3 24 Hour Sensing Comment: Anytime the thermostat is not touched (no single key pressed), the thermostat will automatically fall back into unoccupied setpoints. When any key is pressed, thermostat controls to occupied mode.
0 Disabled (Default)
1 Enabled – Stat Cycles On Heat when room temperature reaches 4ºC and disables Heat when room temperature reaches below 8ºC. This feature can not activate if the application is cool only
0 Inactive (Default)
1 Reset back to Auto after 2 hours (Not when constant fan is selected in ISU #7). The start time is calculated after the initial call for heat/cool.
2 Reset back to Auto after 4 hours (Not allowed when constant fan is selected in ISU #7). The start time is calculated after the initial call for heat/cool.
5
EN0H8579 R0 2009
T6590 FAN-COIL THERMOSTAT
DIMENSIONS
Remote sensor
Remote setback
WIRING DIAGRAMS
Remote sensor
Remote setback
Application 2: Two pipes heating or Cooling, manual changeover wiring diagram
Remote sensor
Remote setback
Pipe sensor
Application 3: Two pipes, one stage heating or cooling – Auto changeover wiring diagram
Application 0: Two Pipes, Heating-Only wiring Diagram
N
Remote sensor
Remote setback
Application 1: Two Pipes, Cooling-Only wiring diagram
N0H8579 R0 2009
Remote sensor
Remote setback
Application 4, 5 & 7: Four pipes (Heat + Cool) Manual / Auto changeover wiring diagram
WIRING DIAGRAMS (CONT)
T6590 FAN-COIL THERMOSTAT
Remote sensor
Remote setback
Pipe sensor
Application 6: Two pipe heating or cooling with Auxiliary electric heater wiring diagram
N
ORDERING SPECIFICATIONS
OS Number Description
T6590A1000
T6590B1000
FCU Controller two pipe,
230VAC
FCU Controller two or four
pipe, 230VAC
Honeywell Control Systems Limited http:/ /europe.hbc.honeywell.com Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0H8579 R0 2009
7
Loading...