• Attractive modern styling ideal for offices or hotels.
• Digital display of ambient temperature, with user
activated temperature display.
• Digital display shows mode icons when cooling or
heating relays operate, or when energy savings mode
is active.
• Push button setpoint adjustment.
• Switches allow manual control of system operation
and fan speed.
• Energy savings mode - external energy savings input
from time switch, occupancy sensors or hotel cardkey
overrides comfort setpoint with setback heating or
cooling setpoint.
• Energy savings input configurable, normally open or
normally closed.
• Proportional plus integral (P+I) control algorithm for
precision temperature regulation.
• Mounts directly onto wall or standard junction box or
vertical junction box with optional adapter plate.
• Installer setup mode allows changes of operating
APPLICATION
T6570 Series Digital Fan-Coil thermostats provide line voltage
on/off control for fans, valves, compressors or auxiliary
electric heaters in fan-coil and small air-conditioner
applications.
T8570 Series provides low voltage control of these functions.
Models are available for control of single stage air-conditioner
and various fan-coil units
–2-pipe.
– 2-pipe with manual heat/cool changeover.
– 4-pipe with manual heat/cool changeover.
– 4-pipe with automatic heat/cool changeover.
All models are suitable for multiple applications. Changes in
output wiring and external links between wiring terminals can
configure the thermostat for the appropriate application.
The fan can also be controlled from the thermostat. In some
cases it is wired to run continuously and can be switched off
with the On/Off switch. Other models can be installed with fan
running continuously or cycling with the thermostat.
Compressors and auxiliary electric heaters can be controlled
using a relay or contactor controlled by the thermostat.
parameters.
• Selectable °C or °F display.
• Adjustable deadband (some models) for heat and cool
control.
• Selectable energy savings setup cooling and setback
heating setpoints.
• Adjustable maximum heating and minimum cooling
setpoint limits.
• Adjustable minimum relay off-times (heating or
cooling) for compressor short-cycle protection.
• EEPROM permanently retains user settings during
power loss (no batteries required).
• Capability to display temperature sensor failure for
Setpoint Range: 10°C to 30°C (50°F to 90°F). Enclosure: (cover, base, and wallplate) Plastic.
Supply Voltages: 24 (NEMA - rated transformer), 120, 230, Control Performance: On/Off control with P+I algorithm
277 Vac (±10%), 50/60 Hz. (depending on model select ed) gives typical control to 0.75°C (1.5°F) at 22°C (72°F) and
0.5 A. 50% duty cycle.
Ambient Ratings:Junction Box Mounting: Direct mounting on single gang
Temperature: NEMA 2" x 4" surface mount electrical box, or on 4" x 4"
Operating Range: 5°C to 45°C (41°F to 113°F). box with optional 272878 adapter plate.
Shipping and Storage Range: -20°C to 55°C (-4°F to
131°F). Wiring: 11 terminals; screw-in terminals capable of accepting
Humidity Range: 5 to 95% RH, non-condensing at 26°C up to 2 x 18 AWG, 1 x 14 AWG, or 1.5 mm2 wires. Some
(79°F). terminals pre-fitted with color-coded flyleads.
Thermostat Output: 1spdt or 2 spst relay outputs (depending
on model).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Equivalent to NEMA 1/8 horsepower rating; allowable load
must be determined by adding nameplate full load and locked
rotor rating of all loads.
Minimum Operational Life (at maximum load): Thermostat
contacts (at 120 Vac): 100,000 cycles
Manual Switches: 10,000 operations.
4-3/16 (122)
3-11/16
(94)
Energy Savings Input: 24 Vdc dry contact, maximum resis-
tance of 1000 ohms. Note 'Caution', page 3.
Protection Class: IP30.
Approvals: CSA Certified C/US LR158158 for Canada and
the U.S.A. Meets CE requirements.
Accessories: Adapter plate for mounting on single- or double-
gang NEMA-standard vertical switch box:
272878 - line voltage models, 24V 2000 series
272881 - 24 V models, 1000 series
T8109 - remote temperature sensor for
T8575D W6380 - fan switching center for T8574/T8575
products
1-7/16 (37)
1-1/2
(38)
3-5/16 (84)
2-3/8 (60)
Fig. 1. Nominal dimensions in inches (mm)
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
M12081A
IMPORTANT
T6570 Series are line voltage powered devices.
All wiring must comply with national and local electrical codes, ordinances and regulations.
Provide disconnect means and overload protection as required.
T8570 Series thermostats must be powered by an
Approved 24 Vac, Class 2 transformer (such as a
W6380 Relay Control Center).
Location
The T6570, T8570 series thermostats are the temperature
control element in a fan-coil or air-conditioning system. They
must be located about 1.5m (5 ft.) above the floor in a position
with good air circulation to sense room temperature.
The optional T8109 sensor can be used to sense temperature
in return air ductwork, instead of at the thermostat
IMPORTANT
Do not mount device where it can be affected by:
1. Drafts or dead spots behind doors or in corners.
2. Hot or cold air from ducts.
3. Radiant heat from the sun or appliances.
4. Unheated (uncooled) areas such as an outside wall
behind the thermostat.
5. Concealed pipes or chimneys.
3 95C-10897–6
T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS
Mounting
Any T6570, T8570 series thermostat can be mounted directly
on the wall on a 65x65mm junction box, or a 2"x4" horizontal
junction box. An optional adapter plate is available for
mounting on a 4"x4" or vertical junction box. (See Fig. 2)
Mounting screws are supplied for alternatives.
1. Feed leadwires through wiring access hole of wallplate
and adaptor plate (if used).
2. Attach supply wires using wire nuts (not provided), or
screw terminals, as appropriate.
3. Locate wallplate in the horizontal mounting position. See
Fig. 2 if using the vertical junction box adapter plate.
4. Push leadwires into electrical junction box and attach
wallplate to box using machine screws provided in the
appropriate mounting holes.
5. Attach thermostat to wallplate:
a. Locate the two center side holes on the back of the
thermostat.
b. Align the holes with the two wallplate side tabs.
c. Press down firmly to snap thermostat into place.
3. Use both hands to pull the thermostat straight away from
the wallplate.
1
2
3
M15396
Fig. 3. Removing the thermostat
Thoroughly check wiring to the wallplate before finally
mounting the thermostat on the wall.
OPERATION
40007507-001
M17505
Fig. 2. Mounting the vertical junction box adapter plate
M17505 Optional adapter plate.
Removing the thermostat
CAUTION
Equipment Damage Hazard.
Improper removal can damage the thermostat.
Carefully follow the thermostat removal directions.
If it is necessary to remove the thermostat from the wallplate
(see Fig. 3):
1. Use a screwdriver to pry thermostat left side away from
the base.
2. Use the screwdriver to pry thermostat's right side away
from the wallplate.
Control
PROPORTIONAL + INTEGRAL (P+I) CONTROL
Like a mechanical thermostat, the T6570, T8570 Series have
On/Off control output. However, this output is regulated by a
P+I algorithm, enabling the thermostat to control closer to
setpoint than conventional thermostats. This results in
performance where the space temperature is maintained within
0.75°C (1.5°F) of the setpoint regardless of fan speed.
P+I action minimizes the difference between the temperature
setpoint and the effective control point by adjusting the output
on-time until the control point matches the setpoint. The ontime is based on a fixed cycle rate of 4 cycles/hour for cooling
(8 cycles/hour for heating), and the proportional band is 1.6°C
(2.9°F).
NOTE: Integral action corrects the temperature control errors
of proportional-only control, but it is slower to react to
large temperature or setpoint changes.
These thermostats also feature optional built-in time
delays for equipment protection which can inhibit
rapid response to large setpoint changes if active.
SINGLE-STAGE COOLING OR HEATING CONTROL (SEE FIG. 4)
In cooling mode the user setpoint will be positioned at the
bottom of the Proportional Band, so the setpoint will effectively
be the temperature where the cooling switches off. In heating
mode the user setpoint will be positioned at the top of the
Proportional Band, and this will be the temperature where the
heating switches off.
NOTE: This also applies to models with manual heat/cool
changeover.
95C-10897–6 4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.