Honeywell T641A, T641C, T641B Installation Instructions Manual

T641A,B,C
Floating Control Thermostats
Installation instructions for the trained service technician.
Application
The T641A,B,C Floating Control Thermostats provide spdt outputs to control floating actuators in applications such as variable air volume (VAV) terminal units.
—T641A: standard spdt floating control thermostat.
—T641B: incorporates momentary system override switch
to provide external relay connection to be energized for override in building management systems or other applications.
—T641C: provides manual heat/cool changeover switch.
Operation
FLOATING CONTROL
The control provided by the T641 is conventionally termed floating control. During floating control, a variation of two-position control, the thermostat provides a three output control, Advance motor, Reverse motor, and Hold.
On a change in temperature, the T641 drives the actuator to an intermediate position and then opens the circuit to the actuator. The actuator remains in this position until there is a temperature change at the T641. The actuator is said to float between the limits of the T641 to satisfy various load require­ments. See Fig. 1.
VAV SYSTEMS
VAV systems control the temperature within a space by varying the volume of supply air. Air is delivered to the space at a fixed temperature. The volume of supply air is controlled by the space thermostat modulating the supply air damper. When full heating and cooling flexibility is required in a zone, it is handled by perimeter heating, or reheat capability in the air terminal units. As individual zones shut down, the total air flow in the system is regulated by a central duct static pressure controller. The fan system is sized to handle an average peak load, not the sum of the individual peaks. As each zone peaks at a different time of day, extra air is borrowed from the off­peak zones. This transfer from low-load to high-load zones occurs only in true VAV systems.
Pressure dependent systems do not incorporate an indi­vidual zone air flow sensor and depend on a stable system pressure to maintain flow. These systems require slower motors such as the seven minute ML6161 models that are typically controlled by the T641 thermostats.
HEAT ANTICIPATION/COOL ANTICIPATION
Control of heating or cooling units with a thermostat does not allow for the temperature to remain exactly at the thermo­stat set point, but varies within a certain temperature range. Anticipation is added to the thermostat to reduce this range.
The anticipator is a small resistive heater in the thermo-
Fig. 1—T641 floating control.
R-Y ENERGIZED
DEADBAND
SET POINT
R-W ENERGIZED
FOR EXAMPLE, WITH SET POINT = 70°F R-Y SWITCH WILL ENERGIZE AT 71.5°F R-W SWITCH WILL ENERGIZE AT 68.5°F
71.5°F
SET POINT 70°F
68.5°F
stat which heats when the system is on or off. The heat produced by the anticipator raises the internal bimetal tem­perature slightly faster than the surrounding room tempera­ture. The thermostat anticipates the need to shut off the heating system sooner than it would if affected by room temperature only. The T641 has fixed or voltage anticipation.
R-Y ENERGIZED
3° DEADBAND
R-W ENERGIZED
M2283
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your applica­tion.
3. Installer must be a trained experienced service techni­cian.
4. After installation is complete, check out product op­eration as provided in these instructions.
1 62-0101
J. H. • 9-92 • © Honeywell Inc. 1992 • Form Number 62-0101
CAUTION
1. Disconnect power supply to prevent electrical shock or equipment damage.
2. To prevent interference with the thermostat link­age, keep wire length to a minimum and run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mounting screws, because damage to subbase threads can result.
4. Do not short across coil terminals on relay. This can burn out the thermostat heat anticipator.
IMPORTANT: An incorrectly leveled thermostat will cause
the temperature control to deviate from set point. It is not a calibration problem.
LOCATION
Install the thermostat about 5 ft. [1.5 m] above the floor in
an area with good air circulation at average temperature.
Do not install the thermostat where it may be affected
by—
— drafts, or dead spots behind doors and in corners. — hot or cold air from ducts. — radiant heat from sun or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas behind the thermostat,
such as an outside wall.
MOUNTING AND WIRING
IMPORTANT: The T641 is electrically compatible and
designed to operate with actuators that have seven minute timings for a full stroke of 90° (angular). Using with motors that have timings less than seven minutes (90° full stroke) will result in unstable temperature control.
The thermostat can be mounted on a horizontal outlet box or directly on the wall. Choose the method that best fits your installation.
In replacement applications, check the existing thermo­stat wires for cracked or frayed insulation. Replace any wires in poor condition. All wiring must comply with local codes and ordinances. The T641 utilizes a four-wire opera­tion, so an additional transformer common wire must be present for correct wiring and operation. See Fig. 2 for functional schematic of T641. Screw terminals are on the back of the thermostat. See Fig. 3.
The part no. 221618 Cover Plate is available when replac­ing a competitive device that has left marks on the wall. See Fig. 4.
1. Grasp the thermostat cover at the top and bottom with one hand. Pull outward on bottom edge of the cover until it snaps free of the thermostat base. Carefully remove and save the packing material surrounding the mercury switches. See Fig. 3.
2. Run wiring from the actuator (if necessary) to the location. If the wiring is plastered into the wall, make a hole next to the cable and loosen the wires so they can be pushed back into the wall later. Thread wires through hole in packing material saved in step 1. Connect the wires to the terminals on the back of the thermostat. See Figs. 5 and 6.
3. Push the excess wire back through the hole and plug any opening with packing material to prevent drafts that may affect thermostat performance.
4. Through the thermostat two middle mounting holes, use the screws provided to loosely secure the T641 to the wall or outlet box.
5. Level the thermostat exactly using a spirit level or plumb line. Tighten the two mounting screws at the middle of the device. See Fig. 3.
Fig. 2—Functional equivalent anticipator circuit of T641.
SOLID STATE RELAY
HEAT
FALL
RISE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ONLY T641B HAS SYSTEM OVERRIDE SWITCH.
2
COOL
HEAT ANTICIPATOR
COOL ANTICIPATOR
N.O.
SOLID STATE RELAY
N.C.
ON
SYSTEM OVERIDE
2
OFF
W
C
Y
2
X
R
DAMPER CONTROL
DRIVE CLOSED COIL
DRIVE OPEN COIL
SYSTEM OVERIDE RELAY
1
L1 (HOT)
L2
M6112
Loading...
+ 4 hidden pages