XE70 SERIES |
|
T6376/T6377 |
|
|
THERMOSTATS |
|
HEATPUMPS & SMALL AIR CONDITIONERS |
|
|
|
|
|
|
PRODUCT SPECIFICATION SHEET |
|
|
The T6376 and T6377 are designed to control the valves, |
|
|
|
|
|
the fan and the compressor in split units, heatpumps and |
|
|
small air conditioners. |
|
|
The thermostat operates the compressor to provide either |
|
|
heating or cooling (as selected by the system switch) at |
|
|
the desired setpoint temperature. |
|
|
The fan can also be controlled from the thermostat. In some |
|
|
cases it is wired to run continuously, and can be switched off |
|
|
with the system ON/OFF switch, while with other models |
|
|
there is a switch which gives the choice of running the fan |
|
|
continuously, or cycling it with the thermostat. |
|
|
Versions are available with a manual 3-SPEED FAN switch, |
|
|
and with a system ON/OFF switch, or a HEAT/OFF/COOL |
|
|
switch |
|
|
Heat/cool changeover operation can be accomplished either |
|
|
by a manually operated HEAT/FAN/ COOL switch or a |
|
|
HEAT/OFF/ COOL switch on the front of the thermostat. |
|
|
|
FEATURES
∙Dual diaphragm sensing element ensures close temperature control for all loads and applications
∙Attractive modern styling makes this thermostat ideal for locating in the occupied space, particularly in offices or hotels
∙Versions with heat anticipator, which improves temperature control in both heating and cooling operation
∙Thermostat mounts directly onto a wall or conduit box
∙Slide switches allow manual control of system operation and fan speed
∙Optional extras:
-rangestops F42006646-001
-tamperproof cover F42008489-001 (opaque), F42008489-002 (transparent)
EN0R8405 R3 1998
T6376/T6377 THERMOSTATS HEATPUMPS & SMALL AIR CONDITIONERS
SPECIFICATIONS
Model |
|
|
|
Switches |
|
|
|
Features |
|
|
ON/OFF |
3-speed |
Fan/ |
Heat/Cool |
Heat/Cool |
Heat/Off/ |
Heat/Fan/ |
Fixed |
Auto |
|
|
Fan |
Auto/Cont |
|
|
Cool |
Cool |
Deadband |
Change- |
|
|
|
|
|
|
|
|
|
over |
|
(SPST) |
(SPTT) |
(SPDT) |
(SPDT) |
(DPDT) |
(DPTT) |
(DPTT) |
|
(Aquastat) |
|
|
|
|
|
|
|
|
|
|
T6376B1004 |
|
|
4 |
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
T6377B1003 |
4 |
4 |
|
|
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
T6377B1011 |
|
4 |
4 |
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
T6377B1045 |
|
4 |
4 |
|
|
4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Setpoint range : 10...30oC. By means of a large setpoint
|
|
dial |
Supply voltage |
: 230 V~, 50...60 Hz |
|
Thermostat |
: |
S.P.D.T. |
switch |
|
|
Performance |
: |
Typical differential 1 oC (heating & |
|
|
cooling) at 20oC at 50% load with |
|
|
anticipator connected |
Electrical ratings |
: 4(2) A, 230 V~ |
|
|
|
Typical loads are fans, zone valves, |
|
|
relays, compressors. Compressors of |
|
|
greater than 0.5 kW capacity should be |
|
|
switched via a contactor. |
Operational life : Greater than 100,000 cycles (all loads) for thermostat contacts at 230 V~ Greater than 6,000 operations for all manually operated switches
Mounting |
: |
Mounts directly onto wall or wall-box |
|
|
(mounting screws supplied) |
Wiring |
: |
Up to 9 screw-in terminals per unit, |
|
|
capable of accepting wires up to 1.5 |
|
|
mm2 |
Enclosure |
: |
Plastic 2-piece housing |
Dimensions |
: |
85 x 130 x 40 mm (w x h x d) |
Protection class |
: |
IP30 |
Environmental |
: |
Operating temperature range 0 to 40oC |
requirements |
|
Shipping and storage temperature range |
|
|
-20 to 50oC |
|
|
Humidity range 0 to 90% rh, non- |
|
|
condensing |
Approvals |
: |
CE mark, complying with standards |
|
|
EN60730-1 (1995), EN55014-1 (1997), |
|
|
EN55014-2 (1996). |
|
|
Product must be wired as shown for CE |
DIMENSIONS
|
|
|
|
|
|
|
|
|
EN0R8405 R3 1998 |