Honeywell T6374, T6375 PRODUCT SPECIFICATION SHEET

XE70 SERIES T6374/T6375
wired to run continuously, and can be switched off with the
FEATURES
Slide switches allow manual control of system
FAN-COIL THERMOSTATS
4-PIPE FAN-COIL CONTROL
PRODUCT SPECIFICATION SHEET
The T6374 and T6375 are designed to control the valves, or the valves and the fan in 4-pipe fan-coil applications, with the possibility of also being used for control of split units and small air conditioners.
The thermostat operates the on/off valves to provide control at the desired setpoint temperature.
The fan can also be controlled from the thermostat. It is system ON/OFF switch.
Versions are available with a manual 3-SPEED FAN switch, and with a system ON/OFF switch.
Heat/cool changeover operation is also possible on some versions. This function can be accomplished by a manually operated HEAT/ COOL switch on the front of the thermostat, or in some versions, automatically by means of a fixed deadband built into the thermostat between the heating and cooling setpoints.
Dual diaphragm sensing element ensures close
temperature control for all loads and applications
Attractive modern styling makes this thermostat
ideal for locating in the occupied space, particularly in offices or hotels
Versions with heat anticipator, which improves
temperature control in both heating and cooling operation
Thermostat mounts directly onto a wall or conduit
box
operation and fan speed
Versions available with fixed deadband between
heating and cooling operation
Optional extras available are :
- range stops F42006646-001
- tamperproof cover F42008489-001 (opaque),
F42008489-002 (transparent)
EN0R8404 R4 1999
T6374/T6375 FAN-COIL THERMOSTATS 4-PIPE FAN-COIL CONTROL
SPECIFICATIONS
:
DIMENSIONS
Model Switches Features
ON/OFF 3-speed Fan/ Heat/Cool Heat/Cool Heat/Off/ Heat/Fan/ Fixed Auto
Fan Auto/Cont Cool Cool Deadband Change-
(SPST) (SPTT) (SPDT) (SPDT) (DPDT) (DPTT) (DPTT) (Aquastat)
T6374C1004 T6374C1012 T6375B1021 T6375B1013 T6375C1003 T6375D1001
4 4
4 4 4
4 4 4
4 4 4
4 4 4
4
over
Setpoint range: 10...30oC. By means of a large setpoint
dial
Supply voltage : 230 V~, 50...60 Hz Thermostat
switch
Performance : Typical differential 1
Electrical ratings : 4(2) A, 230 V~
: S.P.D.T.
o
C (heating & cooling) at 20oC at 50% load with anticipator connected
Typical loads are fans, zone valves and
relays
Operational life : Greater than 100,000 cycles (all loads)
for thermostat contacts at 230 V~ Greater than 6,000 operations for all manually operated switches
Mounting : Mounts directly onto wall or wall-box
(mounting screws supplied)
Wiring
Up to 9 screw-in terminals per unit,
capable of accepting wires up to 1.5
2
mm
Enclosure : Plastic 2-piece housing Dimensions : 85 x 130 x 40 mm (w x h x d). Protection class : IP30 Environmental
requirements
:
Operating temperature range 0 to 40oC Shipping and storage temperature range
-20 to 50oC
Humidity range 0 to 90% rh, non-
condensing
Approvals : CE mark, complying with standards
EN60730-1 (1995), EN55014-1 (1997), EN55014-2 (1996).
Product must be wired as shown for CE
compliance.
EN0R8404 R4 1999 2
T6374/T637 FAN-COIL THERMOSTATS 4-PIPE FAN-COIL CONTROL5
INSTALLATION
OPERATION
wall or on a conduit box (see diagram). Mounting screws are
APPLICATION
T6374C
T6374C
T6375B
T6375B
T6375C
T6375D
Application
manual
manual
Location
The XE70 Series thermostat is the temperature control element in the fan-coil or air-conditioning system, and must be located in a position with good air circulation, on an inside wall about 1.5 m above the floor to sense the average temperature. Do not position the thermostat in draughts, near hot or cold air sources or where it will be affected by radiant heat from the sun or other appliances.
Mounting the thermostat
Any XE70 Series thermostat can be directly mounted on the supplied for both alternatives.
Wiring the thermostat
The standard wiring access is via a hole in the base of the thermostat, near the top edge.
Sensing element
The thermostat sensing element comprises two circular, flexible metal plates welded together at the rims and encapsulating a gas/liquid combination whose pressure changes in response to variations in temperature. This dual­diaphragm expands and contracts with ambient temperature changes to operate a snap-acting switch which controls the heating or cooling circuit.
Heat anticipator
It is recommended that the heat anticipator is always connected for both heating and cooling operation.
1004 1012 1013 1021 1003 1001
Ventilation 2-pipe fan-coil 4-pipe fan-coil Heatpump Air-conditioner
[ [ [ [ [ [
[ [ [ [ [ [
IMPORTANT
1. The installer must be a trained service engineer
2. Disconnect the power supply before beginning installation
Switches
All switches are slide switches for ease of operation. The ON/OFF switch is a system on/off switch, as it removes
power from the thermostat. The FAN SPEED switch allows selection of 3 different fan
speeds, 1 (low), 2 (medium), and 3 (high) The DPDT HEAT/COOL switch allows selection of either
heating or cooling operation. There are 2 output terminals controlled by this switch.
The HEAT/FAN/COOL switch allows selection of either heating or cooling operation, but also has an additional selection position which disables all outputs except that of the fan. The fan can be controlled separately, by the system ON/OFF switch.
[
Heat or Cool Heat/cool [ [ [ [ [ [
Control Changeover (auto or manual) Capability Fan control (auto or cont) cont cont cont cont a or c
Fan speed control Valve control Compressor control
auto
auto
auto auto
[ [ [ [
[ [ [ [ [ [
EN0R8404 R4 19993
T6374/T6375 FAN-COIL THERMOSTATS 4-PIPE FAN-COIL CONTROL
WIRING
Honeywell Control Systems Limited http://europe.hbc.honeywell.com Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0R8404 R4 1999