Honeywell T6371, T6370 PRODUCT SPECIFICATION SHEET

XE70 SERIES T6370/T6371
water pipe of the fan-coil.
FEATURES
Slide switches allow manual control of system
FAN-COIL THERMOSTATS
FAN ONLY CONTROL
PRODUCT SPECIFICATION SHEET
The T6370 and T6371 are designed to control the fan only in fan-coil or ventilation applications.
In all cases the thermostat cycles the fan to provide control at the desired setpoint temperature.
Versions are available with a manual 3-speed fan switch, and with a system on-off switch.
Heat/cool changeover operation is also possible on some versions. This function can be accomplished by a manually operated heat/cool switch on the front of the thermostat. A version for 2-pipe fan-coil units allows automatic heat/cool changeover by connection of a pipe thermostat on the supply
Dual diaphragm sensing element ensures close
temperature control for all loads and applications
Attractive modern styling makes this thermostat
ideal for locating in the occupied space, particularly in offices or hotels
All versions have heat anticipator, which improves
temperature control in both heating and cooling operation
Thermostat mounts directly onto a wall or conduit
box
operation and fan speed
Auto heat/cool changeover possible (on one version)
by using pipe thermostat
Optional extras available are :
- range stops F42006646-001
- tamperproof cover F42008489-001 (opaque),
F42008489-002 (transparent)
EN0R8402 R4 1998
T6370/T6371 FAN -COIL THERMOSTATS FAN ONLY CONTROL
SPECIFICATIONS
:
DIMENSIONS
Model Switches Features
ON/OFF 3-speed Fan/ Heat/Cool Heat/Cool Heat/Off/ Heat/Fan/ Fixed Auto
Fan Auto/Cont Cool Cool Deadband Change-
(SPST) (SPTT) (SPDT) (SPDT) (DPDT) (DPTT) (DPTT) (Aquastat)
T6370A1010 T6371A1019 T6371B1017 T6371C1015
4 4
4 4 4
4 4 4
over
Setpoint range: 10...30oC. By means of a large setpoint
dial Supply voltage : 230 V~, 50...60 Hz Thermostat
switch Performance : Typical differential 1 oC (heating &
Electrical ratings : 4(2) A, 230 V~
Operational life : Greater than 100,000 cycles (all loads)
Mounting : Mounts directly onto wall or wall-box
: S.P.D.T.
cooling) at 20 oC at 50% load with
anticipator connected
Typical loads are fans
for thermostat contacts at 230 V~
Greater than 6,000 operations for all
manually operated switches
(mounting screws supplied)
Wiring
Enclosure : Plastic 2-piece housing Dimensions : 85 x 130 x 40 mm (w x h x d). Protection class : IP30 Environmental
requirements
Approvals : CE mark, complying with standards
Up to 8 screw-in terminals per unit,
capable of accepting wires up to 1.5
2
mm
:
Operating temperature range 0 to 40oC Shipping and storage temperature range
-20 to 50oC Humidity range 0 to 90% rh, non­condensing
EN60730-1 (1995), EN55014-1 (1997), EN55014-2 (1996). Product must be wired as shown for CE compliance.
EN0R8402 R4 1998 2