XE70 SERIES T6370/T6371
water pipe of the fan-coil.
Slide switches allow manual control of system
FAN-COIL THERMOSTATS
FAN ONLY CONTROL
PRODUCT SPECIFICATION SHEET
The T6370 and T6371 are designed to control the fan only in
fan-coil or ventilation applications.
In all cases the thermostat cycles the fan to provide control
at the desired setpoint temperature.
Versions are available with a manual 3-speed fan switch,
and with a system on-off switch.
Heat/cool changeover operation is also possible on some
versions. This function can be accomplished by a manually
operated heat/cool switch on the front of the thermostat. A
version for 2-pipe fan-coil units allows automatic heat/cool
changeover by connection of a pipe thermostat on the supply
• Dual diaphragm sensing element ensures close
temperature control for all loads and applications
• Attractive modern styling makes this thermostat
ideal for locating in the occupied space, particularly
in offices or hotels
• All versions have heat anticipator, which improves
temperature control in both heating and cooling
operation
• Thermostat mounts directly onto a wall or conduit
box
operation and fan speed
• Auto heat/cool changeover possible (on one version)
by using pipe thermostat
• Optional extras available are :
- range stops F42006646-001
- tamperproof cover F42008489-001 (opaque),
F42008489-002 (transparent)
EN0R8402 R4 1998
T6370/T6371 FAN -COIL THERMOSTATS FAN ONLY CONTROL
Model Switches Features
ON/OFF 3-speed Fan/ Heat/Cool Heat/Cool Heat/Off/ Heat/Fan/ Fixed Auto
Fan Auto/Cont Cool Cool Deadband Change-
(SPST) (SPTT) (SPDT) (SPDT) (DPDT) (DPTT) (DPTT) (Aquastat)
T6370A1010
T6371A1019
T6371B1017
T6371C1015
4 4
4 4 4
4 4 4
over
Setpoint range: 10...30oC. By means of a large setpoint
dial
Supply voltage : 230 V~, 50...60 Hz
Thermostat
switch
Performance : Typical differential 1 oC (heating &
Electrical ratings : 4(2) A, 230 V~
Operational life : Greater than 100,000 cycles (all loads)
Mounting : Mounts directly onto wall or wall-box
: S.P.D.T.
cooling) at 20 oC at 50% load with
anticipator connected
Typical loads are fans
for thermostat contacts at 230 V~
Greater than 6,000 operations for all
manually operated switches
(mounting screws supplied)
Wiring
Enclosure : Plastic 2-piece housing
Dimensions : 85 x 130 x 40 mm (w x h x d).
Protection class : IP30
Environmental
requirements
Approvals : CE mark, complying with standards
Up to 8 screw-in terminals per unit,
capable of accepting wires up to 1.5
2
mm
:
Operating temperature range 0 to 40oC
Shipping and storage temperature range
-20 to 50oC
Humidity range 0 to 90% rh, noncondensing
EN60730-1 (1995), EN55014-1 (1997),
EN55014-2 (1996).
Product must be wired as shown for CE
compliance.
EN0R8402 R4 1998 2