Honeywell T6120B, T6120A SPECIFICATION DATA AND MOUNTING INSTRUCTIONS

T6120A,B
SINGLE- AND DUAL-STAGE
INDUSTRIAL ROOM THERMOSTATS
SPECIFICATION DATA AND MOUNTING INSTRUCTIONS
GENERAL
The T6120A and B Single- and Dual-Stage Industrial Room Thermostats are designed for measuring, monitoring, and controlling temperatures in heating and cooling systems. These thermostats are suitable for the following areas of applications:
· commercial buildings,
· storage rooms,
· garages,
· machine rooms,
· factories,
· greenhouses, and
· agricultural installations.
FEATURES
· Liquid-filled stainless steel or copper (T6120A1005, only) bulb.
· Rugged design.
· Easy installation and wiring connection.
· Dust-tight microswitches with switching contacts for
heating and cooling.
MODELS
T6120A1005 T6120A1013 T6120A1021 T6120A1039 T6120B1003
no. of stages 1 2 switch contact 1 SPDT 2 SPDT hysteresis 1 K (fixed) 2...15 K (adjustable) 1 K (fixed) 1 K (fixed) switching differential
between stages adjustment range 0...60 °C -30...+30 °C working temperature -10...+65 °C -35...+65 °C storage temperature -20...+70 °C current 10 (1.5) A 15 (8) A voltage 250 Vac 24...250 Vac housing ABS, re-inforced sensor material 1.4301 copper weight 360 g 530 g protection standard IP54 IP65 W x H x L (mm) 108 x 70 x 72
Copyright © 2004 Honeywell Inc.
All Rights Reserved EN0B-0317GE51 0304
n.a. 2...10 K (adjustable)
T6120A,B SINGLE- AND DUAL-STAGE INDUSTRIAL ROOM THERMOSTATS
T6120A1005
Function and Wiring
To control a heating unit, connect terminals 2 and 3 of the thermostat to the heating unit. When the temperature rises, the contact will open (see Fig. 1).
To control a cooling unit, connect terminals 1 and 2 of the thermostat to the cooling unit. When the temperature drops, the contact will open (see Fig. 1).
2 3 1
T
Fig. 1. T6120A1005 wiring
Dimensions
T6120A1013/A1021/A1039
Function and Wiring
To control a heating unit, connect the red terminal ("COMMON") and the blue terminal ("NORM OPEN") of the thermostat to the heating unit. When the temperature rises, the contact will open (see Fig. 3).
To control a cooling unit, connect the red terminal ("COMMON") and white terminal ("NORM CLOSED") of the thermostat to the cooling unit. When the temperature drops, the contact will open (see Fig. 3).
whitebluered
T
Fig. 3. Wiring T6120A1013/1021/1039 and T6120B1003
PG 13.5
90
108
Fig. 2. Dimensions T6120A1005 (in mm)
Adjusting the Hysteresis (T6120A1013/A1021, only)
In the case of the T6120A1013/A1021 Single-Stage
105
5270
72
Thermostats, it is possible to adjust the hysteresis to a value of between 2 K (factory setting) and 15 K. This can be done as follows:
Pull off the adjustment knob, unscrew the two fastening screws, and remove the housing cover. The hysteresis adjustment dial is now visible (see Fig. 4). The dial settings are numbered from "2" (corresponding to the min. setting of 2 K) to "15" (corresponding to the max. setting of 15 K).
dial
increasing hysteresis
(max.: 15 K)
Fig. 4. Adjusting the hysteresis (T6120A1013/A1021,
only)
decreasing
hysteresis (min.: 2 K)
EN0B-0317GE51 R0304 2