Honeywell T4M User Manual

T4M Thermostat
Programmable Modulating Thermostat
OpenTherm Boiler
EN
Quick Start Installation Guide
Compatible with OpenTherm appliances only. Not compatible with 230V boilers, zone valve applications or 230V electric heating.
Installation in 3 steps...
Wire the
1
Thermostat
T
T
T
T
S S
Must be installed by a competent person.
To ensure your safety make sure the mains power
is switched OFF before accessing wiring.
Power Up
2
and Test
Configure
3
the System
OpenTherm
Communication
32318058001 B
Thermostat
A B C
T T S S
Polarity free
OT OT
OpenTherm Boiler
To prevent a short circuit from a loose wire -
When using multi-core cables: Only remove enough outer insulation to allow secure fixing of the cores into the terminal block.
When using single core cables: Secure them together with a cable tie as close as possible to the terminal block.
1
Wire the Thermostat
Find a suitable wall location away from draughts, direct sunlight or other heat sources, and where cables can be run from the boiler to the thermostat.
A) Separate the wallplate from
the thermostat, and using a screwdriver open the wallplate terminal cover to connect wires.
max 6mm
1.2-1.5m
B) Connect wires according
to wiring diagrams and clip the cover closed.
A B C
T
T S
S
2
Power Up and Test
Power Up the Heating System and do a quick functional test on the thermostat to check that it switches the boiler.
Press the button to increase the temperature to maximum and check the boiler switches on – The heat demand icon on the
thermostat should be on.
Now press the button to decrease the temperature to minimum and check the boiler switches off – The heat demand icon on the
thermostat should also go off.
min 0.25mm² max 1.5mm²
3
Configure the System
Specific settings for the thermostat and heating system can be configured in the advanced menu.
Press and hold
and then buttons together until the display changes (approx. 3 seconds).
A) Press
and buttons to navigate
through the parameter list
C) Press
button to save the change
(or press to cancel the change)
B) Press
and buttons to
change a parameter
D) Press
button to exit advanced
menu and save any changes
Parameter
Number
Parameter
Setting
Parameters
o
N
10:BL
12:DS
13:TO 15:SD 16:FS
Description Settings (default in bold)
Language 1 = EN, 2 = NL, 3 = DE, 4 = FR, 5 = ES
1:LA
Lower Temperature Limit 5 - 21 (°C)
4:LL
Upper Temperature Limit 21 - 35 (°C)
5:UL
Schedule options 1 = 7 day (different schedule each day of the week)
6:SO
Number of periods per day 4 or 6
7:NP
Wired Remote Sensor 0 = No Remote Sensor, 1 = Wired Remote Sensor
8:SS
Fail Safe mode 0 = Boiler off, 1 = Boiler 20% on / 80% off
9:LC
Backlight 0 = Off, 1 = On (only on demand)
Clock Format 0 = 24 hr, 1 = AM/PM
11:CL
Daylight Saving time change 0 = Off, 1 = Auto
Temperature Display Offset +/1. 5°C
Restore Schedule Defaults 0, 1 = reset
Restore Factory Settings 0, 1 = reset
2 = 5 + 2 day (weekday + weekend schedule)
3 = 1 day (same schedule every day)
OpenTherm Data ID's
NoDescription Settings (default in bold)
Low load control 0 = Off, 1 = On
O T1
Control setpoint 5 - 99°C
OT2
Supply water temperature 5 - 99°C
OT3
Return water temperature 5 - 99°C
OT4
Max. supply water temperature 5 - 99°C
OT5
Hot water temperature 5 - 99°C
OT6
Hot water setpoint 5 - 99°C
OT7
Actual power 0 - 99%
OT8
Water pressure 0.0 - 9.9
OT9
OTC control 0 = Off, 1 = On
O T1 0
OTC curve 4 - 40 (16)
O T11
Room compensation 0 = Off, 1 = On
O T1 2
Conforms to protection requirements of the following directives:
EMC: 2014/30/EU and LVD: 2014/35/EU
ErP: Class VI (+4%), (EU) 811/2013
WEEE Directive 2012/19/EC - Waste Electrical and Electronic Equipment directive
At the end of the product life dispose of the packaging and product in a corresponding recycling centre. Do not dispose of the unit with the usual domestic refuse. Do not burn the product.
Troubleshooting
What’s happening? What it could mean... How to fix it...
Thermostat display is blank
Display =
Thermostat shows heat demand but boiler doesn't respond
Honeywell Control Systems Ltd.
Skimped Hill Lane, Bracknell, Berkshire RG12 1EB
www.honeywelluk.com
No power to heating system
Faulty wiring connection Check wiring at thermostat
Faulty temperature sensor
Boiler (water) already at temperature
Faulty wiring connection Check wiring at thermostat
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, ACSE&ES, Z.A., La Pièce 16, 1180 Rolle, Switzerland by its Authorised Representative Honeywell Inc.
© 2016 Honeywell International Inc. | Printed in UK
Check heating system is powered
and boiler terminals
Replace thermostat or check wiring to remote temperature sensor if fitted
Normal behaviour - wait for water temperature to drop
and boiler terminals