Line Volt Thermostats
40
50
60
70
80
90
40 50 60 70 80 90
COOL HEAT COM
F
M6130A
2-13/16 (70)
4-17/32
(114)
1-1/8
(22)
1-13/16
(48)
15/16
(24)
1-3/4
(45)
1-1/8
(37)
17/32
(14)
3-9/32
(83)
1-15/32
(35)
9/16
(14)
T451; T651 Light and Medium Duty Line Voltage Thermostat
Light and Medium Duty Line Voltage Thermostats control line
voltage valves, motors, contractors, electric heat, elements, duct
furnaces, and fan coil units in heating/cooling systems.
• Automatic cooling and heating anticipation
• Mount on standard vertical or horizontal outlet box
Dimensions in inches (millimeters) Application: T451-Heating; T651-Heating and cooling
Dimensions, Approximate: 4 1/2 in. high x 2 15/16 in. wide x 1 1/2 in. deep
(switches and wiring terminals protrude into outlet box 3/4 in.) (115 mm high x
75 mm wide x 39 mm deep (switches and wiring terminals protrude into
outlet box 19 mm))
Electrical Ratings:
22 A @ 120 - 240 Vac Resistive
19 A @ 277 Vac Resistive
9.8 FLA / 58.8 ALR @ 120 Vac
5.6 FLA / 33.6 ALR @ 208 Vac
4.9 FLA / 29.4 ALR @240 Vac
4.2 FLA / 25.2 ALR @277 Vac
Electrical Connections: Flylead
Volt ag e: 120 Vac - 227 Vac
Frequency: 50 Hz; 60 Hz
Sensor Element: Vapor filled dual diaphragm
Color: Champagne gold face-plate with beige cover
Approvals
Canadian Standards Association: CSA Certified, File No. LR1322
Underwriters Laboratories, Inc: Listed: File No. E4436, Guide No. XAPX
Accessories:
TG511A1000-Medium Universal Thermostat Guard with clear cover and
base, and opaque wallplate Fits T822, T834, T8034, T841, T874 with
Q674, WR1F46, and others
TG511D1004-Medium Universal Thermostat Guard with Beige painted
steel cover, opaque ring base and wallplate Fits T822, T834, T8034,
T841, T874 with Q674, and others
Setting
Temperature
Range
Product Number
T451A3005/U 44 F to
86 F
T451B3004/U 50 F to
• T651A3018/U 44 F to
86 F
86 F
T651A3026/U —7 C to
* TRADELINE models • SUPER TRADELINE models
Differential
Tem pe rature
Switch
Position
Switching Action Includes(F) (C) (F) (C) System
— 2 F — — SPST- breaks on
temperature rise
— 2 F — — SPST- breaks on
— 2 F — heating and
cooling
temperature rise; with
positive off
SPDT - breaks heating
and makes cooling on
temperature rise
— 1 C heating and
28 C
cooling
SPDT - breaks heating
and makes cooling on
temperature rise
Vertical scaleplate with thermometer, range stops
and locking cover screws, wall plate,
high accuracy Dual Diaphragm sensor
Vertical scaleplate with thermometer and
high accuracy Dual Diaphragm sensor
Vertical scaleplate with thermometer,
horizontal scaleplate with no thermometer,
range stops and locking screws, wall plate,
and high accuracy Dual Diaphragm sensor
Vertical scaleplate with thermometer, range stops
and locking screws, wall plate, high accuracy
Dual Diaphragm sensor
494 customer.honeywell.com 70-6910