
T4360G, T6360D, T6360E
Line Voltage Thermostat
PRODUCT DATA
FEATURES
• Models available for heat only, cool only and
heat pump systems.
• Fan models for air circulation.
• Three-speed fan model to improve circulation
and temperature control.
• 16A model available for direct switching of
high current loads.
• Indicator lamp on all models.
APPLICATION
The T4360G thermostat with on/off switch
provides control of 240Vac heat only systems with
a maximum current of 16A.
The T6360D thermostat with on/off switch
provides control of 240Vac cool only systems.
The T6360E thermostats provide control of 240Vac
heat pump systems with or without fan control.
Contents
APPLICATION............................................................ 1
FEATURES.................................................................1
SPECIFICATIONS...................................................... 2
INSTALLATION .......................................................... 3
OPERATION...............................................................5
ACCESSORIES.......................................................... 5
WIRING DIAGRAMS .................................................. 6
® Registered Trademark
Copyright © 2005 Honeywell Inc. • All Rights Reserved
1 AU4360-00

T4360G, T6360D,E Line Voltage Thermostat
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit might not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Thermostat Model
T4360/T6360 Thermostats provide features listed in
Table1.
Table 1. Thermostat Features.
System
Model
T4360G1006 On-Off None Heat only
T6360D1008 On-Off None Cool only
T6360E1005 Heat-Off-
T6360E1013 Heat-Off-
T6360E1021 Heat-Off-
Selection
Cool
Cool
Cool
Fan
Selection Comments
None Heat pump
Cont-Auto Heat Pump
Lo-Med-Hi Heat Pump
Dimensions:
Electrical Rating (Nominal Range):
220-240Vac, 50/60 Hz
T4360G: 16A
T6360D: 10(3) A
T6360E: 10(3) A
Batteries:
No Batteries required.
Temperature:
Temperature Range: 10-30°C.
Operating Ambient Temperature: 0°C to 40°C.
Storage Temperature: -20°C to 50°C.
Humidity Ratings:
0-90% RH, non condensing.
AU4360-00 2

T4360G, T6360D,E Line Voltage Thermostat
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Location
Install the thermostat about 5 ft (1.5m) above the floor in an
area with good air circulation at average temperature. See Fig.
1.
Do not install the thermostat where it can be affected by:
— Drafts, or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
AU4360-00 3