The T4360/T6360 range of thermostats
are designed to provide automatic
ON/OFF control for gas valves,
circulation pumps, relays and zone
valves in all heating, cooling, or
heating/cooling installations where
single or changeover switching up to
10 A (resistive load) or 3 A (inductive
load) is required.
In addition a 16 A (resistive load)
variant is available for direct switching
of high current carrying loads.
Nine models of the thermostat are
available, in a wide range of feature
combinations.
FEATURES
• Dual diaphragm sensing element ensures close
temperature control for all loads and applications
• Attractive modern styling makes this thermostat ideal
for locating in the living space
• Available with or without heat anticipation to suit the
application
• The T6360 has changeover contacts for use in
cooling or heating/cooling applications
• Versions with switches for positive-off selection, or
summer/ winter (heat/cool) changeover operation
• Mounts directly onto wall or conduit box
• Improved eas
conductor clamps to ensure wiring is retained
securely
-to-wire terminals with built-in
• Double insulated. No earth wire required for
operation. Earth "parking" terminal available on
selected models
• Optional extras available are:
– range stops F42006646-001
– tamperproof cover F42007110-001 (opaque) or
F42007110-002 (transparent)
– additional wallplate for special mounting
requirements F42007789-001
EN0R8281 R3 2003
T4360/T6360 LINE VOLTAGE ROOM THERMOSTATS
SPECIFICATIONS
MODEL
HEAT
ANTICIPATOR
CHANGEOVER
CONTACTS
INDICATOR
LAMP
SUMMER/
WINTER
SWITCH
ON/OFF
SWITCH
16 AMP
RATING
FROST
PROTECT
FUNCTION
TAMPER-
PROOF COVER
NIGHT
SETBACK
HEATER
SPECIAL
ANTICIPATOR
T4360A
T4360B
T4360C ∗
T4360D
∗
∗
∗
∗
T4360E
T4360F
T6360A
T6360B
T6360C
∗
∗
∗
∗
∗ Versions available with or without this feature
For thermal actuator control
Switch type : T4360 S.P.S.T. (Heating)
T6360 S.P.D.T. (Heating/Cooling)
Electrical ratings : 230Vac, +/-10%, 50…60Hz
T6360A,B,C 10(3) A Terminal 3 (Heat),
6(2) A Terminal 4 (Cool)
T4360A,C,E 10(3) A Terminal 3
(Heating)
T4360B 16 A Terminal 3 (Heating)
T4360D 6(2) A Terminal 2 (Heating
or Cooling)
T4360F 2(2) A Terminal 3 (Heating)
Manual switches on T4360C,D and
T6360C rated 10(3) A
o
Temperature
setting range
: 10 to 30
(0 to 20
C
o
C - T4360A only)
Terminals : Terminals sized to accept up to 2 x
single or multi-stranded wires from
1.0 mm
16 A version will accept one 4.0 mm
2
to 2.5 mm2.
2
wire per terminal.
Lamp terminals suitable for only one
wire per terminal up to 2.5 mm
2
max.
Each terminal has a conductor clamp
for securing the wiring conductor and is
suitable for both blade and cross-head
screwdrivers.
Earth "parking" terminal to comply with
IEC guidelines.
o
Performance : Maximum differential 1.0
heat ramps of 3
o
C per hour, with
anticipator connected.
Typical differential 0.5
C at 20oC at
o
C.
Switch life : Greater than 100,000 operations (all
loads) for main switch.
10,000 operations for auxiliary on/off or
heat/cool switches.
Environmental
requirements
: Operating temperature range 0 to 40
Shipping and storage range -20 to 50
Humidity range 0 to 90% R.H. (noncondensing)
Approvals : CE mark, complying with standards
EN60730-1 (1995), EN55014-1 (1997),
EN55014-2 (1996).
Product must be wired as shown for CE
compliance.
o
C
o
C
DIMENSIONS