Honeywell T4360 PRODUCT SPECIFICATION SHEET

y
T4360/T6360
LINE VOLTAGE
ROOM THERMOSTATS
PRODUCT SPECIFICATION SHEET
The T4360/T6360 range of thermostats are designed to provide automatic ON/OFF control for gas valves, circulation pumps, relays and zone valves in all heating, cooling, or heating/cooling installations where single or changeover switching up to 10 A (resistive load) or 3 A (inductive load) is required.
In addition a 16 A (resistive load) variant is available for direct switching of high current carrying loads.
Nine models of the thermostat are available, in a wide range of feature combinations.
FEATURES
Dual diaphragm sensing element ensures close
temperature control for all loads and applications
Attractive modern styling makes this thermostat ideal
for locating in the living space
Available with or without heat anticipation to suit the
application
The T6360 has changeover contacts for use in
cooling or heating/cooling applications
Versions with switches for positive-off selection, or
summer/ winter (heat/cool) changeover operation
Mounts directly onto wall or conduit box
Improved eas
conductor clamps to ensure wiring is retained securely
-to-wire terminals with built-in
Double insulated. No earth wire required for
operation. Earth "parking" terminal available on selected models
Optional extras available are:
range stops F42006646-001 tamperproof cover F42007110-001 (opaque) or
F42007110-002 (transparent)
– additional wallplate for special mounting
requirements F42007789-001
EN0R8281 R3 2003
T4360/T6360 LINE VOLTAGE ROOM THERMOSTATS
SPECIFICATIONS
MODEL
HEAT
ANTICIPATOR
CHANGEOVER
CONTACTS
INDICATOR
LAMP
SUMMER/
WINTER SWITCH
ON/OFF SWITCH
16 AMP RATING
FROST
PROTECT
FUNCTION
TAMPER-
PROOF COVER
NIGHT
SETBACK
HEATER
SPECIAL
ANTICIPATOR
T4360A  
T4360B  
T4360C
T4360D
T4360E  
T4360F
T6360A
T6360B  
T6360C
Versions available with or without this feature
For thermal actuator control
Switch type : T4360 S.P.S.T. (Heating)
T6360 S.P.D.T. (Heating/Cooling)
Electrical ratings : 230Vac, +/-10%, 50…60Hz
T6360A,B,C 10(3) A Terminal 3 (Heat),
6(2) A Terminal 4 (Cool)
T4360A,C,E 10(3) A Terminal 3
(Heating) T4360B 16 A Terminal 3 (Heating) T4360D 6(2) A Terminal 2 (Heating
or Cooling) T4360F 2(2) A Terminal 3 (Heating) Manual switches on T4360C,D and
T6360C rated 10(3) A
o
Temperature setting range
: 10 to 30
(0 to 20
C
o
C - T4360A only)
Terminals : Terminals sized to accept up to 2 x
single or multi-stranded wires from
1.0 mm
16 A version will accept one 4.0 mm
2
to 2.5 mm2.
2
wire per terminal.
Lamp terminals suitable for only one
wire per terminal up to 2.5 mm
2
max.
Each terminal has a conductor clamp
for securing the wiring conductor and is suitable for both blade and cross-head screwdrivers. Earth "parking" terminal to comply with IEC guidelines.
o
Performance : Maximum differential 1.0
heat ramps of 3
o
C per hour, with anticipator connected. Typical differential 0.5
C at 20oC at
o
C.
Switch life : Greater than 100,000 operations (all
loads) for main switch. 10,000 operations for auxiliary on/off or heat/cool switches.
Environmental requirements
: Operating temperature range 0 to 40
Shipping and storage range -20 to 50 Humidity range 0 to 90% R.H. (non­condensing)
Approvals : CE mark, complying with standards
EN60730-1 (1995), EN55014-1 (1997), EN55014-2 (1996). Product must be wired as shown for CE compliance.
o
C
o
C
DIMENSIONS
EN0R8281 R3 2003 2
T
INSTALLATION
IMPORTAN
1. The installer must be a trained service engineer
2. Disconnect the power supply before beginning installation
Location
A T4360/T6360 room thermostat is the temperature control element in your heating system and must be located in a position with good air circulation at average temperature - on an inside wall about 1.5 m above the floor.
Do not position the thermostat in draughts, near hot or cold air from water pipes or radiant heat from the sun or appliances.
T4360/T6360 LINE VOLTAGE ROOM THERMOSTATS
Mounting the thermostat
The T4360/T6360 can be mounted directly on the wall or on a conduit box (see Fig. 2). Mounting screws are provided for both alternatives.
An additional wall-plate is available for special mounting requirements.
Wiring the thermostat
The standard wiring access is via a hole in the base of the thermostat, near the top edge. There are also 4 breakouts on the cover (2 on top and 2 on the sides) for surface wiring requirements.
Wall box mounting Fixing holes spaced to suit BS4662
screws supplied
Fig.2 Mounting the Thermostat
OPERATION
Sensing Element
The thermostat sensing element comprises two circular, flexible metal plates welded together at the rims encapsulating a small quantity of gas (0.125g) in liquid form, whose pressure changes greatly in response to small variations in temperature. In effect, this dual diaphragm forms a 'bellows' which expands/contracts in sympathy with the ambient temperature changes - this movement serving to operate a snap acting switch rated to control the heating or cooling circuit.
Heat Anticipator
It is recommended that a thermostat with heat anticipator is used for systems with a high heating ramp rate. This will overcome the overshoot and undershoot problems often found in this type of installation.
Indicator Lamp
A 'potential-free' indicator lamp is available on some models. This can be wired as required to indicate when power has been switched to the (heating or cooling) load (see Wiring).
To wire the lamp as 'boiler lockout' indicator, follow boiler manufacturers wiring instructions.
Surface mounting Use wall box fixing holes or alternatives shown
screws supplied
Auxiliary Switches
The on/off switch provides a means of manually isolating the mains input to the thermostat, to provide a positive off feature.
The summer/winter switch provides the user with a means of manually switching between a heating output (activated on temperature fall) to a cooling output (activated on temperature rise).
Frost Protect Thermostat
The frost protect thermostat prevents water pipes from freezing in exposed locations. It should be positioned close to where the pipework is most exposed to external chilling and connected to override all existing time and temperature controls. The frost protect thermostat is provided with an indicator mark at the 5 tamperproof cover.
o
C point, and is supplied with a
Disposal of Thermostat
The thermostat contains no user serviceable parts. Please ensure product disposal is in a safe and environmentally friendly manner, in compliance with local regulations. Do not dispose of in a fire.
EN0R8281 R3 2003 3
T4360/T6360 LINE VOLTAGE ROOM THERMOSTATS
A
A
A
WIRING
LAMP
ON/OFF SWITCH
LAMP
ON/OFF SWITCH
HEATING LOAD
NTICIPATOR
HEATING LOAD
HEATING LOAD
NTICIPATOR
NIGHT SETBACK RESISTOR
TIMER
ON/OFF SWITCH
HEATING LOAD
NTICIPATOR
ANTICIPATOR
THERMAL ACTUATOR
NIGHT SETBACK RESISTOR
TIMER
HEATING LOAD
HEATING LOAD
HEATING/ COOLING LOAD
HEAT/COOL SWITCH
LAMP
LAMP
COOLING LOAD
ON/OFF
ANTICIPATOR
HEATING LOAD
LAMP
COOLING LOAD
SWITCH
HEATING LOAD
Honeywell Control Systems Limited
http://europe.hbc.honeywell.com
Newhouse Industrial Estate Motherwell ML1 5SB United Kingdom
EN0R8281 R3 2003
LAMP
COOLING LOAD