T4098A,B
Deluxe Electric Heat Thermostats
PRODUCT DATA
FEATURES
• Controls both fan-forced and baseboard electric
heaters.
• Temperature-responsive, vapor-filled dual diaphragm
sensing element provides 2°F (1°C) sensitivity with
minimum droop.
• Replaces virtually all standard wall-mounted line
voltage thermostats.
• Includes long-lasting Micro Switch™ mechanism.
• Color-coded leads allow easy installation.
• Protective cover door opens to provide access to
setpoint knob.
GENERAL
The T4098A,B Deluxe Electric Heat Thermostats provide high
performance line voltage direct control of resistance-rated
electric heating equipment.
• Attractive sloped faceplate allows easy viewing of
temperature.
• Classic styling.
CONTENTS
General ............................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 3
Settings and Adjustments ................................................... 4
Checkout ............................................................................. 6
Operation ............................................................................ 6
Copyright © 1996 Honeywell Inc. • • All Rights Reserved
T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS
SPECIFICATIONS
IMPORTANT
TRADELINE® Models
TRADELINE® models are selected and packaged to provide
ease of stocking and handling and also maximum
replacement value. See Table 1 for TRADELINE® model
specifications.
Number Switching
T4098A Spst;
T4098B Dpst;
The Specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed
specifications. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed. For exact
engineering specifications, contact your Honeywell
sales representative.
Table 1. Thermostat Specifications.
Temp.
Model
makes
single line
break on
temperature
fall.
makes
double line
break with
setting knob
in OFF
position.
Rating
F° (C°) Finish Includes
50° to 90°
(10° to 30°)
50° to 90°
(10° to 30°)
Classic
beige or
Premier
White™
Classic
beige or
Premier
White™
Cover
thermometer,
temperature
range stops,
and locking
cover.
Cover
thermometer,
temperature
range stops,
and locking
cover.
Electrical Ratings (Noninductive Resistive Loads):
22A at 120/208/240 Vac, 60 Hz.
19A at 277 Vac, 60 Hz.
Wiring Connections:
6 in. (150 mm) leads suitable for connecting to aluminum
wiring if approved special service CO/ALR connectors are
used.
Sensing Element:
Vapor-filled dual diaphragm.
Setpoint Adjustment:
Knurled knob on front of thermostat.
Differential:
2°F (1°C), nonadjustable.
Dimensions:
See Figs. 1 and 2.
Mounting:
Mount directly on vertical 2 x 4 in. outlet box, or on 4 x 4 in.
outlet box using ring adapter (ordered separately).
Approvals:
Underwriters Laboratories Listed: File No. E47434, Guide
No. XAPX.
Canadian Standards Association Listed: File No. LR1322.
Canadian Standards Association Performance Certified:
C273.4.
Accessories:
272804A Range Stop and Locking Screw Assembly. Includes
locking cover screws, Tinnerman clips, wrench, and range
stops—two plastic pins to insert inside cover for fieldselection of minimum and maximum temperature settings.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number or specify.
1. Model number.
2. Switching.
3. Type of finish.
If you have additional questions, need further information or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International sales and
service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0146—3
2
T4098A,B DELUXE ELECTRIC HEAT THERMOSTATS
FRONT VIEW
2-7/8 (73)
4-1/2
(115)
SIDE VIEW
2-5/8 (67)
1-3/4
(45)
1
(25)
Fig. 1. T4098 dimensions in in. (mm).
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do
control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of an old control containing mercury in a
sealed tube.
not
place your old
2-1/8
(54)
4-1/2
(115)
M5790
CAUTION
1. Disconnect power supply to prevent electrical
shock or equipment damage.
2. If connecting with aluminum conductors, use CO/
ALR solderless wire connectors to avoid fire
hazard.
3. Do not remove thermostat cover until wiring is
complete to avoid damaging the sensing element.
Location
Install a vertical outlet box that is used to mount the
thermostat about 5 ft (1.5m) above the floor in an area with
good air circulation at room temperature.
Do not install the thermostat where it may be affected by:
—drafts or dead spots behind doors, in corners or under
cabinets.
— hot air from convectors.
—radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
Wiring and Mounting
CAUTION
1. Handle the thermostat with care to avoid
damaging the sensing element or control.
2. Use a separate limit control in the heating
appliance.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow these
instructions could damage the product or cause a
hazardous condition.
2. Check the ratings on the product to make sure the
product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
HIGH VOLTAGE CONTROL.
ELECTRICAL SHOCK HAZARD.
Follow local codes and ordinances when installing this
thermostat. Improper handling can cause serious
injury or death.
L2
1
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
USE SPECIAL SERVICE CO/ALR SOLDERLESS CONNECTORS
WHEN CONNECTING ALUMINUM CONDUCTORS OR A FIRE
HAZARD MAY RESULT.
3
BREAKS AND REMAKES BELOW -31°F(-35°C); NORMALLY
THERMALLY ACTIVATED. BREAKS ON A TEMPERATURE RISE;
MAKES ON A TEMPERATURE FALL.
USE A SEPARATE LIMIT CONTROL IN THE HEATING APPLIANCE.
4
T4098A
3
L1
T1
2
4
ELECTRIC
HEATER
Fig. 2. Typical wiring connections for T4098A.
M5813B
3
68-0146—3