Temperature Controllers
T4054 Return Air Controller
Type: Filled element
Application: Provides control in heating systems
Dimensions, Approximate: 7 5/8 in. high x 2 5/8 in. wide x 2 in. deep (194 mm high x 67 mm wide x 51 mm deep)
Accuracy: ±6 F (±3.3 C)
Sensor Element: Fast response capillary
Color: Gray
Contact Ratings (120 Vac): 16.0 AFL, 96.0 ALR
Contact Ratings (240 Vac): 8.0 AFL, 48.0 ALR
Voltage: 120 Vac or 240 Vac
Provides SPDT heavy-duty, line-voltage temperature control in ventilation, heating or cooling systems.
•Use in a variety of farm, industrial or commercial applications
•Wall or duct mount in any position
•Fast response, tin-plated element not affected by adverse environment
•Rugged case
•Mounts on flat surface with three screws
•T6064 provides fast response with hydraulic temperature sensing elements mounted on the unit
Frequency: 50 Hz; 60 Hz
Maximum Operating Temperature: 125 F (52 C) Differential Temperature: 3.5 F (1.9 C)
Contact Ratings (120 Vac): 16.0 AFL, 80.0 ALR Contact Ratings (120 Vac): 8.0 AFL, 48.0 ALR
Approvals
Canadian Standards Association: CSA Listed: Report -1 Underwriters Laboratories, Inc: Listed: E4436, vol. 5, sec. 12,
Guide XAPX
|
|
|
|
|
|
|
|
Setpoint Temperature Range |
|
Output |
Number of |
|
|
|
|
|
|
|
||
Product Number |
(F) |
(C) |
Output |
Type |
Sensor Inputs |
Comments |
|
|
|
|
|
|
|
T4054A1000/U |
36 F to 100 F |
2 C to 38 C |
1 SPST |
relay |
1 |
Make R to B on temperature fall |
|
|
|
|
|
|
|
T4054B1016/U |
36 F to 100 F |
2 C to 38 C |
1 SPST |
relay |
1 |
Make R to W on temperature rise |
|
|
|
|
|
|
|
344 |
customer.honeywell.com |
70-6910 |