The RP908A and B are force balance pneumatic
amplifiers, with adjustable proportional band, for use as
Controllers in HVAC systems,
The RP908 is no longer being manufactured. There is
an RP920 model available for all RP908A and B applications. Refer to Application Replacement Listing in the
REPAIR section.
APPLICATION
RP908A
RP908A &
B
PNEUMATIC CONTROLLERS
The RP908A, in conjunction with a remote sensor,
provides direct or limit control in air conditioning control systems, with or without remote control point
adjustment (CPA). It may be adjusted for either direct or
reverse acting operation. Refer to Figures 1 and 2 for
these applications.
5737-2
Fig. 1. Typical RP908A Primary Control of Normally
Open Valve.
PRIMARY
CONTROLLER
LIMIT
LOW
CONTROLLER
5759-2
Fig. 2. Typical RP908A Low Limit Control.
RP908B
The RP908B dual input Controller is applied to compensating systems by using an additional compensating
signal to change the control point of the Controller (Fig.
3). Temperature, humidity, pressure, or dewpoint may
be controlled by using the appropriate sensors,
Rev. 6-84
Form No
75-553 1
Commercial Bldp
MLFTAB:
Group
111
C. 6.
1
DISCHARGE
hl
Q
I
RP908B
I
I
I+
SENSOR 2
D.A.
J
5760-2
SUPPLY AIR PRESSURE: 18 psi (124
MAXIMUM SAFE AIR PRESSURE: 25 psi (172
kPa)
nominal.
kPa).
AMBIENT TEMPERATURE LIMITS: 40 to 120F (4 to
9OC).
PROPORTIONAL BAND:
2-1/2
to 40 percent of pri-
mary sensor span, field adjustable.
AUTHORITY: 10 to 200 percent of primary sensor span,
field adjustable.
REMOTE CPA:
-t
10 percent of sensor span.
OPERATION
RP908A
Fig. 3. Typical RP908B Application.
SPECIFICATIONS
MODELS: See Table
Table 1. RP908A and B Model Listing.
Single
Model
RP908A
1005 X
RP908A
1013 X
RP908A
1021 X
RP908A
1039 X
RP908A
1047
RP908A
1054 X
RP908A
1042
RP908B
1003
RP908B
1011
RP908B
1029
RP908B
1037
Input Limit
1
I
I
I
I
1.
Single
Input
IXI
I
I
11x1
I
Dual With
Input Cover
X
I I I
lxlxl
Ixlxlxl
I
1x1
X
X
X
X
With
CPA
X
X
Ixlx
With
Calibration
Knob
X
X
X
X
X
X
Ix
x
Ix
When used in a heating system with the Controller set
for direct action, a drop in temperature at the sensor
lowers the branchline pressure, opening the valve to
increase the flow of heating medium to the coil (Fig. 1). If
the CPA model is used, an increase in air pressure on the
CPA port raises the setpoint of the Controller and a
decrease lowers it.
Used as a low limit Controller, the
RP908B
reduces
branchline pressure from the primary Controller, opening a heating valve to maintain discharge temperature at
setpoint (Fig. 2).
RP908B
Operation is similar to RP908A. However,
an
increase
in outdoor temperature causes the compensating (outdoor) sensor to reset the control point of the Controller
to raise the branch line pressure (Fig. 3). The resulting
change in branch line is dependent on the authority setting on the Controller.
MAINTENANCE
EQUIPMENT REQUIRED
-
Plastilube 311057 for O-rings, screw threads, etc.
-
Molycote or similar commercial powdered lubri-
cant for pivots and plungers in units with CPA.
-
0 to 30 psi test gage (if gages have not been installed
in system).
GENERAL
The only preventive maintenance necessary is an
annual visual check for leaks, loose fittings, etc, and an
operational and calibration check.
75-553 1
OPERATIONAL CHECK
Check main air pressure for 18 psi (124 kPa) at Controller. For models with manual CPA adjustment, move
CPA switch up and down and observe the action of the
Controller. If the system’ does not have CPA, the sen-
sor(s) may be disconnected and the port plugged so that
pressure may be slowly built up, causing the Controller to
operate from one extreme position to the other. Bleeding
this pressure slowly causes the Controller to operate in
the opposite direction. The main lever should move
smoothly, and the branchline pressure should change
gradually in the proper direction.
2
CALIBRATION CHECK
RP908A
Change the
sensor temperature if the two do not already match. The
branchline pressure should be at its calibration pressure
of 8 + 1 psi (55
drawings. If recalibration is necessary, see CALIBRATION,
RP908B
Determine the existing calibration temperature from
the reset schedule on the job drawings. Draw a straight
line on graph as shown in Figure 4. Measure the temperature at the Port 2
sor temperature (Fig. 5). Measure temperature at Port 1
sensor location. This temperature must agree within two
100
(38)
setpoint
-t-
7
kPa)
sensor.
of the Controller to the existing
unless otherwise noted on job
Find corresponding Port 1 sen-
percent of the sensor range span and the branchline pressure must be within the operating range of the controlled
device. If recalibration is necessary, see CALIBRATION.
CHANGE FROM DIRECT TO REVERSE
ACTING
The change from direct to reverse acting is made by
following the three steps listed in Figure 6.
OUTDOOR AIR TEMPERATURE IN F(C)
20884
Fig. 4, Typical Discharge Air Reset Schedule.
21c
(99:
T
??
:
19c
z
(88
2
17c
2
(77:
;:
w 150
ii
(66)
?
[L
130
p
(54)
s
110
g
(43)
I
(Zi,
40 30
OUTDOOR AIR TEMPERATURE IN F (C)
(4)
(-1)
(770)
(-:“z,
(-:8) (::i)
Fig. 5. Typical Hot Water Reset Schedule for
Radiation Systems.
20885
1.
RENlOVE PIVOT
SCREWS (2)
A
DISCONNECT WHEN PROPORTIONAL BAND (PB) IS
LESS THAN 15 PERCENT, REGARDLESS OF ACTION.
3.
CbNNECT
TO NOTCHES (2)
RA SPRINGS (2)
4707-l
Fig, 6. Set-Up for Reverse-Acting Operation.
ADJUSTMENTS
PROPORTIONAL BAND
If the original setting shown on the job drawings must
be changed:
1. Loosen the Proportional Band Adjustment Knob
(Fig. 7) and slide the Proportional Band Indicator
to the desired setting.
NOTE: When a proportional band of more than
I5 percent is used, fasten the Bias Spring
to the Lever Assembly (Fig. 6). This spring
is left unconnected if proportional band is
15 percent or less.
I
2. The Controller must be recalib
proportional band is changed.
ra
.ted
whenever the
75-553 1
REMOTE CONTROL POINT
A pressure change from 3 to 13 psi (21 to 90
kPa)
in the
remote CPA port changes the control point proportionately by 20 percent of the sensor span.
1 (and Port 2 if RP908B is used). If the reset signal on an
RP908B is produced by the output of a room thermostat
or pressure control, a
Port 2. Otherwise, the scale range on the
30-psi
gage must be installed in
gage should
match the range of the sensor for Ports 1 and 2.
SETPOINT
The
setpoint
is raised by turning the
Setpoint
Knob
(Fig. 7) counterclockwise. This increases the force from
the
setpoint
spring on the lever assembly so that a greater
force from the sensor chamber is required to cause an
increase in branchline pressure.
The
setpoint
It has 10 marked divisions, each equaling
screw has a vernier for fine adjustment.
l/2
percent of
the sensor span (1 degree F per division for a 200-degree
sensor span, or 20 turns for the whole span).
SETPOINT
SCREW WITH 10 MARKED
DiVISIONS
CONTROLLER WITHOUT CPA
ADJUSTMENT
SETPOINT
KNOB
RP908A
There are two methods of calibrating the RP908A
when 18 psi (124
kPa)
main air is supplied to the Control-
ler and the internal restriction is not blocked.
CALIBRATION USING AN ADJUSTABLE
RESTRICTION
1,
Install the proper scaleplate on the Controller if not
already installed.
2.
Disconnect the Port 1 sensor and connect an adjustable restriction to Port 1.
Choose a
3.
setpoint
and adjust the restriction until the
gage in Port 1 shows this setpoint.
Turn the
4.
reads 8 psi (55
setpoint
knob until the branchline pressure
kPa).
This is standard calibration. On
some applications, the calibration branchline pressure
may be set at a different point that relates to the spring
range of the device being operated.
Move the scaleplate until the
5.
setpoint
indicator agrees
with the chosen setpoint, and tighten.
6.
Disconnect the adjustable restriction and reconnect
the sensor.
LPROPORTIONAL
CONTROLLER WITH CPA
BAND INDICATOR
.
20887
Fig. 7. RP908 Adjustment Locations.
CALIBRATION
GENERAL
Always calibrate with 18 psi (124
sure. On CPA models, set CPA to 8 psi (5.5
30-psi gage must be installed in the branchline port
during calibration and a temperature, humidity, or pressure gage matching the sensor should be installed in Port
kPa)
main air pres-
kPa).
A 0 to
CALIBRATION WITH GAGES
1. Install
30-psi
match Port
gages in Ports 1 and B. Port I gage must
B.
Install proper scaleplate on the Controller if not
already done.
Turn the
psi (55
setpoint
kPa)
knob until branchline pressure is 8
or other selected calibration pressure (see
Step 4 of CALIBRATION USING AN ADJUSTABLE RESTRICTION).
Move the scaleplate until the
setpoint
indicator is at
the reading shown on the Port 1 gage and tighten.
Adjust the
setpoint
to the desired control setting.
RP908B
The only method of calibrating the RP908B is to use
an adjustable restriction. If the settings are known, proceed to Step 1 of RP908B CALIBRATION PROCEDURE. If the settings ‘must be calculated, read the
following and calculate as shown. Authority Calculator
No. 813 may be used to simplify these calculations.
Although these examples are shown for a hot water reset
system, the formulae also apply to other systems-
75-553 I
4
Two separate parameters must be known in order to
properly calibrate a reset system, Reset Schedule and
Throttling Range. Proportional Band and Authority
may be calculated from these parameters
RESET SCHEDULE
The reset schedule is plotted by determining the outdoor air temperature at which designed maximum heating water temperature is needed and the outdoor air
temperature at which no heating is required.
THROTTLING RANGE (TR)
Throttling Range indicates the change in water temperature at the sensor to cause the valve to move from
fully open to fully closed (full heat to no heat). It is desirable to have a throttling range as narrow as possible for
efficient control and yet wide enough to produce stable
operation. A throttling range of
mended trial setting. If the system will not stabilize after
being in operation for a short period of time, the throttling range should be increased (this requires recalculation of the proportional band, authority, and
recalibration). An unstable system can be recognized by
frequent, repetitive changes in branchline pressure,
known as hunting or cycling.
a
10F (5C)
is a recom-
Where:
TR = Throttling Range
AT1= Change in Hot Water Temperature
AT2
= Change in Outdoor Air Temperature
EXAMPLE:
Determine settings for a system where hot water should
be controlled at 180F (82C) when outdoor air
temperature is -lOF
when outdoor air is
(5C). Hot Water Sensor
Sensor
-40/160F
AT2
ATI
TR =
PB = &
(-23C),
65F
(18C). Assume a TR of
40/24OF
(Span =
Reset Schedule
=
65-(-
10) = 75
=
180-90
=
10F
x100=5%
and reduced to
(Span =
2OOF).
go
9OF
200F);
(32C)
0-A.
IOF
When the throttling range has been selected, it must be
converted to a proportional band value that can be set on
the Controller.
PROPORTIONAL BAND (PB)
Proportional Band is similar to throttling range except
it is expressed in terms of percent of temperature change
rather than degrees. Proportional band can be determined by using the following formula:
TR
Sensor Span
EXAMPLE:
When a sensor having a 200-degree span is used and a
IO-degree TR has been selected:
PB =
200
AUTHORITY
Authority indicates the amount of effect that the change
in outdoor air temperature will have on the control point.
The formula must take into account
and Sensor 2. The complete formula is:
Authority
=
Span S,
Span SI
x 100 = PB%
10
-
x 100 = 5%
the
spans of Sensor
A~l+m xloQ
X
Al-2
1
Authority =
RP908B
I. Install the scaleplate matching the Port I sensor on the
2.
3.
4
5
CALIBRATION PROCEDURE
Controller if not already done.
Disconnect the sensors to Ports 1 and 2 and connect an
adjustable restriction to each port. If an external main
has been connected to the sensor line, install the
adjustable restriction on the sensor side of the tee.
Select the low end of the Sensor 1 schedule or
(32C). Adjust the No. 1 restriction until the Sensor 1
gage reads that temperature. Also set Sensor 2 at “low
end” of reset schedule, in this example
Set the authority and proportional band into the Con-
troller. Adjust the
gage reads 12 psi (83
closed” pressure if the valve has other than a standard
4 to 11 psi (28 to 76
.
Move the scaleplate until the desired
with the
ler is now in calibration.
REPLACEMENT PAGE FOR:
RP908A&B
Service Data
75-5531 6-84 II. C. 6.
setpoint
200
2oo
indicator and tighten. The Control-
Pneumatic Controllers
90;5IO
x
setpoint
kPa),
kPa) spring range.
x 100 = 133%
knob until the branchline
or until it reads the “valve
65F
(18C).
setpoint
8-88
90F
lines up
75-553 1
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.