Honeywell RP7517 Catalog Page

Pneumatic Transducers
RP7517 Electronic-Pneumatic Transducer
Electronic-Pneumatic Transducers are used in electronic­pneumatic control systems to convert a proportional electric output signal from a controller into a direct-acting, proportional pneumatic signal.
• Screw mounting or snap rail (models with cover).
• Dual barb fittings.
• High accuracy.
Application: Electric to pneumatic Transducer Action: Direct Acting Airflow Usage: 0.025 scfm (117mL/s) Connections: Dual barb-fittings for 1/4 in. or 5/32 in. O.D. plastic tubing Current: 16 mA Maximum Operating Temperature: 131 F (55 C) Maximum Operating Pressure: 30 psi (205 kPa) Pressure Ranges: 0 to 18 psi (0 to 125 kPa) Nominal High End: 16 psi with 18 psi main pressure at 12 Vdc (110
kPa with 125 kPa main pressure at 12 Vdc)
Nominal Low End: 0.5 psi at 0 Vdc (3.5 kPa at 0 Vdc) Output Pressure Range: 3 to 15 psi (21 to 103 kPa) Humidity Ratings: 5 to 95% RH Capacity: 0.45 scfm (211 mL/s)
Dimensions, Approximate
Product Number Electrical Connections
RP7517A1009 30 in. (762 mm) lead wire 2 7/16 in. wide x
RP7517A1017 screw terminals for 14 to 22
gage wire
3 5/8 in. high x 2 in. deep
2 7/16 in. wide x 3 3/8 in. high x 1 7/8 in. deep
RP7517B1016 30 in. (762 mm) lead wire 2 7/16 in. wide x
3 5/8 in. high x 2 in. deep
RP7517B1024 screw terminals for 14 to 22
gage wire
2 7/16 in. wide x 3 3/8 in. high x 1 7/8 in. deep
62 mm wide x 92 mm high x 52 mm deep
62 mm wide x 86 mm high x 48 mm deep
62 mm wide x 92 mm high x 52 mm deep
62 mm wide x 86 mm high x 48 mm deep
RP7517 Typical Piping/Wiring
SUPPLY AIR
EXCEL PANEL
M
I/O
B
C
O
P
A
U
R D
RP7517B
Input Signal Voltage Includes(inch) (mm)
2 to 10 Vdc Powered by
2 to 10 Vdc Powered by
2 to 10 Vdc at
0.1 mA max
2 to 10 Vdc at
0.1 mA max
Control signal
Control signal
24 Vac external transformer
24 Vac external transformer
HEATING COIL
DUCT TEMP SENSOR
N.O.
VALVE
M5431
With cover, without internal power supply (2-wire)
Without cover, without internal power supply for panel mounting (2 wire)
With cover, external transformer required, 24 Vac, 50/60 Hz, (3 wire)
Without cover, external transformer required, 24 Vac, 50/60 Hz, (3 wire)
660 customer.honeywell.com 70-6910