The ROME (Relay Option Module Enclosure, red) and ROME-B (black) is shipped with one ANN-BUS Relay Module
already installed. The ROME Series provides mounting space for one additional Relay Module or one addressable MultiModule.
Relay Module
The Relay Module provides 10 programmable Form-C relays when used with a compatible FACP (Fire Alarm Control
Panel). This document is provided as a quick reference. For more detailed programming information, refer to the appropriate FACP installation manual.
Relay Module Specifications
Operating Voltage24 VDC
Max. Current @
24 VDC
Operating Temperature
Max. Wiring Distance from FACP
(with 12 AWG wire)
Relay Contact Ratings
Indoor Use in Dry Location Only
Alarm75 mA
Standby15 mA
32° to 120° F
(0° to 49° C)
1,250 ft. (380 m)
2 amps @ 30 VDC
(resistive)
0.5 amps @ 30 VAC
(resistive)
Relay Designations and Terminals
The relay numbers and terminal designations are illustrated in the following illustration.
R9 R10
R7 R8
NO
NC
C
Relay Module
R5 R6
R3 R4
R1 R2
NO
NC
C
Relay Module
Normally Open,
Normally Closed
and Common
terminals for each
relay follow the
same pattern as
illustrated above.
Page 2
Wiring the Relay Module to an FACP
Refer to the following table and illustration for wiring connections.
1.All connections/sources are to be power-limited and
supervised.
2.12 - 18 AWG (0.75 - 3.25 mm
2
) wire for 24 VDC circuit is
acceptable. Refer to the appropriate FACP manual.
3.Power wire distance limitation is set by 1.2 volt maximum line
drop from source to end of circuit.
4.Maximum distance from FACP to last ANN-BUS device must
not exceed 1,250 feet (380 m). Refer to Wiring Distance
Table in appropriate FACP manual for wire gauge and
distance limitations.
B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
- (GND)
}Connect to FACP ANN-BUS and/or next device
}Connect to FACP or next device
Relay Terminals (TB1) FACP ANN-BUS Terminals
Terminal 1 (B)B (ANN-BUS)
Terminal 2 (A)A (ANN-BUS)
Terminal 3 (+)(+)
Terminal 4 (-)(-)
Relay Module
Setting Relay Module DIP Switches
Each ANN-BUS device requires a unique address. Relay Module DIP switch SW1 is used to set the address for the module. A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. ANN-BUS device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid
address. The following illustrates the DIP switch settings for each address (ID Number):
2ROME Series Installation Document — P/N 53530:B 9/14/2009
Page 3
Mounting an Optional Second Relay Module in the ROME Series
ANN-MBRLY Mounting Bracket Installation
An optional second Relay Module can be mounted inside the ROME Series using the ANN-MBRLY mounting bracket.
Two holes must be drilled in the enclosure to secure the ANN-MBRLY as described in the following steps:
1.Place the ANN-MBRLY mounting bracket flat against the inside back wall of the ROME Series, while positioning
two oblong holes over the mounting studs as shown in the following illustration.
2.Make a mark on the ROME Series back wall using the two holes that will be used to secure the ANN-MBRLY as a
guide.
3.Remove the ANN-MBRLY from the ROME Series and drill two 3/32” (dia. 0.093”) holes in the locations marked in
step 2. Note that these holes will be used to secure the ANN-MBRLY using the two supplied self-tapping screws.
4.Place the ANN-MBRLY mounting bracket oblong holes in position over the mounting studs and install the two
supplied nuts, but do not tighten at this time.
5.Install the two supplied self-tapping screws in the locations indicated and secure the ANN-MBRLY to the ROME
Series using the holes drilled in step 3.
6.Tighten the two nuts installed in step 4.
self-tapping screw
mounting stud
oblong mounting hole
(with nut)
self-tapping screw
drill 3/32” (dia. 0.093”)
hole in ROME Series for
self-tapping screw
ANN-MBRLY
Mounting Bracket
drill 3/32” (dia. 0.093”)
hole in ROME Series for
self-tapping screw
oblong mounting hole
mounting stud
(with nut)
ROME Series
ROME Series Installation Document — P/N 53530:B 9/14/20093
Page 4
Relay Module Installation on ANN-MBRLY Mounting Bracket
1.Hold the Relay Module with the relays positioned to the left and install the Relay Module on the ANN-MBRLY
mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket.
2.Secure the Relay Module to the ANN-MBRLY mounting bracket with the four supplied screws.
3.Set the SW1 DIP switches and connect the wiring as described in the previous sections.
mounting hole
mounting hole
Optional
Relay
Module
mounting hole
ROME Series
mounting hole
4ROME Series Installation Document — P/N 53530:B 9/14/2009
Page 5
Mounting an Addressable Multi-Module in the ROME Series
MULTIMOD-BRKT Mounting Bracket Installation
An addressable Multi-Module communicates with the FACP via the SLC loop. A Multi-Module can be installed inside
the ROME Series enclosure using the MULTIMOD-BRKT module mounting bracket. Install the MULTIMOD-BRKT as
described below.
1.Place the MULTIMOD-BRKT mounting bracket flat against the inside back wall of the ROME Series, while
positioning two oblong holes over the mounting studs as shown in the following illustration.
2.Make a mark on the ROME Series back wall using the two holes that will be used to secure the MULTIMOD-BRKT
as a guide.
3.Remove the MULTIMOD-BRKT from the ROME Series and drill two 3/32” (dia. 0.093”) holes in the locations
marked in step 2. Note that these holes will be used to secure the MULTIMOD-BRKT using the two supplied selftapping screws.
4.Place the MULTIMOD-BRKT mounting bracket oblong holes in position over the mounting studs and install the two
supplied nuts, but do not tighten at this time.
5.Install the two supplied self-tapping screws in the locations indicated and secure the MULTIMOD-BRKT to the
ROME Series using the holes drilled in step 3.
6.Tighten the two nuts installed in step 4.
self-tapping screw
self-tapping screw
mounting stud
(with nut)
drill 3/32” (dia. 0.093”)
hole in ROME Series for
self-tapping screw
MULTIMOD-BRKT
Mounting Bracket
drill 3/32” (dia. 0.093”)
hole in ROME Series for
self-tapping screw
mounting stud
(with nut)
oblong mounting hole
oblong mounting hole
ROME Series
ROME Series Installation Document — P/N 53530:B 9/14/20095
Page 6
7.Install the supplied module insulating pad on the MULTIMOD-BRKT bracket by aligning the four outer holes with
the four standoffs on the bracket and pressing the pad onto the standoffs and flat against the bracket as illustrated
below.
standoffstandoff
standoff
standoff
8.Install the addressable Multi-Module on the MULTIMOD-BRKT mounting bracket by positioning the four module
mounting holes over the four standoffs on the mounting bracket.
9.Secure the addressable Multi-Module to the MULTIMOD-BRKT bracket with the four supplied mounting screws as
illustrated below.
mounting screw
mounting screw
mounting screw
mounting screw