Honeywell ROME-B, ROME Product Installation Document

ROME Series
Relay Option Module Enclosure
Product Installation Document
PN 53530:B 9/14/2009 09-327
The ROME (Relay Option Module Enclosure, red) and ROME-B (black) is shipped with one ANN-BUS Relay Module already installed. The ROME Series provides mounting space for one additional Relay Module or one addressable Multi­Module.

Relay Module

Relay Module Specifications

Operating Voltage 24 VDC
Max. Current @ 24 VDC
Operating Temperature
Max. Wiring Distance from FACP (with 12 AWG wire)
Relay Contact Ratings
Indoor Use in Dry Location Only
Alarm 75 mA
Standby 15 mA
32° to 120° F (0° to 49° C)
1,250 ft. (380 m)
2 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Relay Designations and Terminals
The relay numbers and terminal designations are illustrated in the following illustration.
R9 R10
R7 R8
NO NC C
Relay Module
R5 R6
R3 R4
R1 R2
NO NC C
Relay Module
Normally Open, Normally Closed and Common terminals for each relay follow the same pattern as illustrated above.

Wiring the Relay Module to an FACP

Refer to the following table and illustration for wiring connections.
1. All connections/sources are to be power-limited and supervised.
2. 12 - 18 AWG (0.75 - 3.25 mm
2
) wire for 24 VDC circuit is
acceptable. Refer to the appropriate FACP manual.
3. Power wire distance limitation is set by 1.2 volt maximum line drop from source to end of circuit.
4. Maximum distance from FACP to last ANN-BUS device must not exceed 1,250 feet (380 m). Refer to Wiring Distance Table in appropriate FACP manual for wire gauge and distance limitations.
B (ANN-BUS) A (ANN-BUS) + (24 VDC)
- (GND)
}Connect to FACP ANN-BUS and/or next device
}Connect to FACP or next device
Relay Terminals (TB1) FACP ANN-BUS Terminals
Terminal 1 (B) B (ANN-BUS)
Terminal 2 (A) A (ANN-BUS)
Terminal 3 (+) (+)
Terminal 4 (-) (-)
Relay Module

Setting Relay Module DIP Switches

Each ANN-BUS device requires a unique address. Relay Module DIP switch SW1 is used to set the address for the mod­ule. A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. ANN-BUS device addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid address. The following illustrates the DIP switch settings for each address (ID Number):
2 ROME Series Installation Document — P/N 53530:B 9/14/2009