Honeywell M7685 Catalog Page

Modutrol IV Motors
Fail
Torque/Force
Product Number
M7294A1010/U
M7294Q1007/U
M7294Q1015/U
Safe Mode
Non-
300 lb-in. 34 Nm 24V 60-120 Spring Return
Non-
300 lb-in. 34 Nm 120V 60-120 Spring Return
Non-
300 lb-in. 34 Nm 24V 60/107 Screw Spring Return
M7685 Modutrol IV™ Series 2 Motor
Vo lt ag e
Nominal Timing (sec)
sec
sec
Electrical Connec­tions
Quick­connect terminals
Screw terminals
terminals
Control Signal
Modulating, 2-10 Vdc
Modulating, 4-20 mA
Modulating, 4-20 mA
Internal Auxiliary Switch
0 160
2 90
2 90
Factory Stroke Setting Stroke Includes Comments
degrees
degrees
degrees
Adjustable; 90 to 160 degrees, Asymmetrical
Adjustable; 90 to 160 degrees, Symmetrical
Adjustable; 90 to 160 degrees, Symmetrical
None
Transformer and Screw Terminal Adapter
Screw Terminal Adapter
Adjustable zero and span for split range applications
Adjustable zero and span for split range applications
Internal Transformerlb-in., lb Nm, N
50004263­002
None
Proportional, spring-return motors for use with Honeywell W7080 panel 14-17 Vdc output; with minimum position adjustment.
• Integral spring return returns motor to normal position in the event of power failure
• Integral junction box provides NEMA 3 weather protection
• Quick-connect terminals are standard
• Adapter bracket for matching shaft height of older motors is available
• Motors have field adjustable stroke (90 deg. to 160 deg.)
• Integral auxiliary switches are available factory mounted, or can be field added
• Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications
• All models have dual shafts (slotted and tapped on both ends)
• All models have auxiliary switch cams
• Fixed torque throughout the entire voltage range
Application Type: Electric Dimensions, Approximate: 6 7/16 in. high x 5 1/2 in. wide x 8 3/4 in.
deep (164 mm high x 140 mm wide x 222 mm deep)
Fail Safe Mode: Spring Return Control Signal: Modulating, 14-17 Vdc Feedback: No Frequency: 50 Hz; 60 Hz External Auxiliary Switches Available: Ye s Auxiliary Switch Ratings AFL - 120 Vac: 7.2A Auxiliary Switch Ratings ALR - 120 Vac: 43.2A Auxiliary Switch Ratings AFL - 240 Vac: 3.6A Auxiliary Switch Ratings ALR - 240 Vac: 21.6A Electrical Connections: Quick-connect terminals Mounting: Foot-mounted Motor Shafts: Dual-ended shaft Shaft Shape: square Shaft Dimensions: 0.375 in. (10 mm) Shaft Rotation (upon control signal increase): Clockwise (as viewed
Deadweight Load on Shaft (Either End): 200 lbs. Deadweight Load (Combined on both Shafts): 300 lbs. Ambient Temperature Range: -40 F to +150 F (-40 C to +60 C) Weight: 8.5 lb Approvals Underwriters Laboratories, Inc: Listed: File No. E4436, Guide No.
XAPX for USA and Canada
Accessories:
4074ERU-Weatherproofing kit. Protects motor from driving rain when
mounted in any position
220736A-Internal Auxiliary Switch Assembly - 1 Switch 220736B-Internal Auxiliary Switch Assembly - 2 Switches 220738A-Adapter Bracket. Adjusts shaft height to match Modutrol III motors 221455A-Infinitely adjustable Motor Crank Arm 50017460-001-24/120/230 Vac Internal Transformers for Series 2 and 3
Motors
50017460-003-120 Vac Internal Transformers for Series 2 and 3 Motors
from power end) (normally closed)
Torque/Force
Product Number
M7685A1025/U 60 lb-in. 6.8 Nm 24V 30-60 sec 0 90 degrees Adjustable; 90 to 160
Voltag e
Nominal Timing (sec)
Internal Auxiliary Switch
Factory Stroke Setting Stroke Includes
degrees, Asymmetrical
Minimum Position Potentiometer
Internal Transformerlb-in., lb Nm, N
None
428 customer.honeywell.com 70-6910