Honeywell M7410E User Manual

M7410E
SMALL MODULATING LINEAR
VALVE ACTUATOR
PRODUCT DATA
APPLICATION
The Honeywell M7410E actuator is specifically designed to provide modulating control together with the V5822/23, V5832/33, and V5825B series of small linear valves.
The M7410E is used in fan-coil-units, induction units, small reheaters and recoolers, and for zone control applications. It is employed in electronic temperature control systems with hot and/or cold water as the controlled medium. This actuator is fully compatible with all controllers providing 0...10 V or
2...10 V output signals. The 7410E actuator is designed for applications where space
is limited and minimum power consumption is required. A microprocessor-based, high-performance positioner
0..10V
2..10V
guarantees accurate control. Reliable longtime operation is ensured due to the fact that no
mechanical feedback potentiometer and no mechanical end­switches are needed. Due to an automatic synchronization function, the close-off point is self-adjusting.
Based on a running time of 150 s, valve positioning and flow adjustment is very exact. Manual positioning is provided for all actuators. The actuator is both attractive and robust in design. A special version with auxiliary switch is available.
FEATURES
Microprocessor-based positioner ensures precise
stem positioning
Small size allows installation where space is limited
Low power consumption
Suitable for 0...10 V and 2...10 V controller output
signal (adjustable on site)
Easy-to-operate direct/reverse acting switch
Simple input signal override (e.g. for frost protection
function)
Reliable longtime operation because mechanical
feedback potentiometers and mechanical end switches are not required
Magnetic coupling for stem force limitation and self-
adjustment of the close-off point
Supplied with pre-wired connection cable
Simple, standardized valve/actuator coupling. No
tools required for mounting
® U.S. Registered Trademark EN0B-0097GE51 R0909 Copyright © 2009 Honeywell Inc. • All rights reserved
Visual valve position indicator furnished with
actuator
Manual operation provided by the valve adjustment
cap, extra knob, or with a hexagon key
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
SPECIFICATIONS
Motor
Input voltage:
Power consumption: 1.8 VA / 1.2 W (motor running)
Input signal: modulating 0...10 V, 2...10 V
Operation: direct/reverse (adjustable)
Stroke: 6.5 mm
Running time: 150 s at 50 Hz
Stem force: depending on type (see table)
Protection standard: IP 42 in accordance with EN 60529
Insulation class: III in accordance with EN 60730
Connection cable: 1.5 m
Ambient operating temperature limits:
Medium valve temperature
Weight: 0.4 kg
Suitable valves: see table
24 Vac ±15%; 50/60 Hz
0.6 VA / 0.2 W (motor stopped)
(adjustable); < 0.1 mA
125 s at 60 Hz
180 N (for valves DN 15..20) 300 N (for valves DN 25..40 and V5825B)
0...55 °C
max. 120 °C
Manual operation: see table
Auxiliary Switches
Ratings: 5...24 V max. 100 mA
24...230 Vac, max. 3(1) A
Switch position (factory supplied):
Switch S1 (fix) 17.8 ± 0.2 mm
Switch S2 (adjust.) 11.7 ±
0.2 mm
OPERATION
The movement of the electric actuator is produced by a screw spindle which is driven in both directions by a synchronous motor through a set of gears. A magnetic clutch limits the torque of the gear assembly and the driving force of the actuator. The actuator is fixed to the valve body by means of a coupling ring requiring no tools for mounting. The actuator is maintenance-free and supplied completely with a ready-to­wire connecting cable.
A microprocessor-based high performance positioner guarantees accurate control. The close-off position is self­adjusting by means of an automatic synchronization function. Synchronization is performed when the applied control signal is 0 V or 10 V. The actuator then drives every minute for 5 seconds into the end position in order to ensure close-off even after manual operation.
VERSIONS
Standard
With manual operation
With manual operation and auxiliary switches
Special versions
manual operation
Provided by the valve
adjustment cap
Integrated
"
Integrated
"
Special cable length length = 3 m / 5 m / 10 m
stem force
180 N 300 N
180 N 300 N
180 N 300 N
aux. switch S1
– –
– –
x x
upon request
aux. switch S2
– –
– –
x x
housing type
B B
C C
C C
OS number
M7410E1002 M7410E1028
M7410E2026 M7410E2034
M7410E4022 M7410E4030
EN0B-0097GE51 R0909
2
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
MOUNTING POSITION
The actuator may be mounted only beside or above the valve. Adjust the valve in the correct position before mounting the actuator.
Fig. 1. Mounting positions
MOUNTING
Before the actuator is fixed to the valve, the adjustment cap must be removed (Fig. 2). Make sure that the actuator is in the open position (factory-supplied position) before fixing the actuator to the valve body.
SWITCH SELECTION
The built-in selector switches must be set according to the valve type (2-way or 3-way), valve size, and the controller output signal (0...10 V or 2...10 V), see Fig. 4.
Y=+10V=
AB
Y=+10V=
AB
Y=+10V=
OPENS
OPENS
OPENS
A-AB
FACTORY
SETTING
100%...0%
0%...100% 0...10V
2...10V
A
AB
B
Fig. 4. Selecting valve type and output signal
ELECTRIC WIRING
The electrical installation must comply with Fig. 5.
INPUT SIGNAL OVERRIDE
To override the controller output signal, the input signal must be connected to COM (0 %) or 24 V (100 %) using an external switch (see Fig. 5).
AUTO
Y = 0...+10V
FACTORY
SETTING
Y = 2...+10V
Fig. 2. Removing protection cap
The actuator must be mounted by hand. Do not use tools or additional force insofar as this may damage the actuator and valve.
Fig. 3. Mounting the actuator
0%
24 VAC
BROWN
Y
GREEN
COM
WHITE
AUTO
100%
24 VAC
BROWN
Y
GREEN
COM
WHITE
Y
24 VAC
0 ... +10 V 2 ... +10 V
COM
Y
24 VAC
0 ... +10 V 2 ... +10 V
COM
0 / 2 V
10 V
Fig. 5. Connection of input switch
3 EN0B-0097GE51 R0909
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
MANUAL OPERATION
Actuators with the OS-number M7410E2... and M7410E4... feature a hexagonal key hole for manual operation. For more comfort, an additional knob for manual adjustment is packed separately. To prevent valve damage, operation is permitted only when there is no power applied to the motor.
4 mm
Adjustment of Auxiliary Switch 2
The auxiliary switch should be adjusted by a skilled person, only. Move the actuator to the position where the switch is to
Fig. 6. Manual operation
COMMISSIONING ADVICE
A functional check of the valve actuator can be carried out by changing the Y input signal. The movement of the actuator stem (Fig. 7) indicates whether the valve is opening or closing. If the direction of travel is not correct, the direct/reverse-switch must be reset.
be operated. Cut the plastic skin with a sharp knife. The adjustment screw can be accessed below the skin. Turn the screw clockwise until the end stop is reached. Turn the screw counterclockwise until the switch point is achieved. To check that the required position has been set, move the actuator. Finally, seal the adjustment hole with a piece of tape.
Fig. 8. Auxiliary switch cables
a b
c a
b c
17.8 mm 11.7 mm
Fig. 7. Movement of the actuator stem
AUXILIARY SWITCHES
The actuators with the OS-number M7410E4022 and M7410E4033 feature 2 auxiliary switches. Each switch has its own cable. Auxiliary switch S1 with fixed switchpoint when the stem position is in. Auxiliary switch S2 with adjustable switchpoint when the stem position is out.
Fig. 9. Adjustment of auxiliary switch S2
EN0B-0097GE51 R0909 4
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
Electric Wiring of Auxiliary Switches
The electrical installation must comply with the wiring diagram shown in Fig. 10. If the auxiliary switch is connected to 230 Vac, a switch with a contact gap of at least 3 mm for each pole must be fitted with the installation.
24 Vac: max. 100 mA
DN 15, DN 20
(230 Vac only):
open
AB
230 Vac: max. 5 (1)A
AB
M7410E
close
AB
Application Example: Switching Off an Electrical Appliance
2-Way-Valve
DN 15, DN 20
E. g. fan, pump etc.
BLUE
max. 5 (1)A
Fig. 11. Electric wiring of auxiliary switch
All Other Valves
DN 15 - DN 40 DN 25 - DN 40DN 15 - DN 20
BLACK
DN 25 ­DN 40
DN 15 ­DN 40
DN 15 ­DN 20
close
AB
AAB
B
close
AAB
B
BROWN
BLUE
BLACK
BROWN
AAB
BLUE
ABAB
AAB
B
B
BROWN
BLACK
BROWN
AAB
AAB
BLUE
open
openclose
B
open
B
BROWN
BLACK
BROWN
E. g. fan, pump etc.
BLUE
max. 5 (1)A
BLACK
Fig. 12. Electric wiring of auxiliary switch
BLUE
BLACK
BLUE
BLACK
BLUE
BLACK
Fig. 10. Electric wiring of auxiliary switch
5 EN0B-0097GE51 R0909
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
DIMENSIONS (MM)
58
100
82
109
49
Fig. 13. Housing type B
60
49
Fig. 14. Housing type C
87
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich / Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0097GE51 R0909