The Honeywell M7410E actuator is specifically designed to
provide modulating control together with the V5822/23,
V5832/33, and V5825B series of small linear valves.
The M7410E is used in fan-coil-units, induction units, small
reheaters and recoolers, and for zone control applications. It
is employed in electronic temperature control systems with
hot and/or cold water as the controlled medium. This actuator
is fully compatible with all controllers providing 0...10 V or
2...10 V output signals.
The 7410E actuator is designed for applications where space
is limited and minimum power consumption is required. A
microprocessor-based, high-performance positioner
100%..0%
0..10V
0%..100%
2..10V
guarantees accurate control.
Reliable longtime operation is ensured due to the fact that no
mechanical feedback potentiometer and no mechanical endswitches are needed. Due to an automatic synchronization
function, the close-off point is self-adjusting.
Based on a running time of 150 s, valve positioning and flow
adjustment is very exact. Manual positioning is provided for all
actuators. The actuator is both attractive and robust in design.
A special version with auxiliary switch is available.
FEATURES
•Microprocessor-based positioner ensures precise
stem positioning
• Small size allows installation where space is limited
• Low power consumption
• Suitable for 0...10 V and 2...10 V controller output
signal (adjustable on site)
• Easy-to-operate direct/reverse acting switch
• Simple input signal override (e.g. for frost protection
function)
•Reliable longtime operation because mechanical
feedback potentiometers and mechanical end
switches are not required
•Magnetic coupling for stem force limitation and self-
adjustment of the close-off point
• Supplied with pre-wired connection cable
• Simple, standardized valve/actuator coupling. No
•Manual operation provided by the valve adjustment
cap, extra knob, or with a hexagon key
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
SPECIFICATIONS
Motor
Input voltage:
Power consumption: 1.8 VA / 1.2 W (motor running)
Input signal: modulating 0...10 V, 2...10 V
Operation: direct/reverse (adjustable)
Stroke: 6.5 mm
Running time: 150 s at 50 Hz
Stem force: depending on type (see table)
Protection standard: IP 42 in accordance with EN 60529
Insulation class: III in accordance with EN 60730
Connection cable: 1.5 m
Ambient operating
temperature limits:
Medium valve
temperature
Weight: 0.4 kg
Suitable valves: see table
24 Vac ±15%; 50/60 Hz
0.6 VA / 0.2 W (motor stopped)
(adjustable); < 0.1 mA
125 s at 60 Hz
180 N (for valves DN 15..20)
300 N (for valves DN 25..40 and
V5825B)
0...55 °C
max. 120 °C
Manual operation: see table
Auxiliary Switches
Ratings: 5...24 V max. 100 mA
24...230 Vac, max. 3(1) A
Switch position
(factory supplied):
Switch S1 (fix) 17.8 ± 0.2 mm
Switch S2 (adjust.) 11.7 ±
0.2 mm
OPERATION
The movement of the electric actuator is produced by a screw
spindle which is driven in both directions by a synchronous
motor through a set of gears. A magnetic clutch limits the
torque of the gear assembly and the driving force of the
actuator. The actuator is fixed to the valve body by means of
a coupling ring requiring no tools for mounting. The actuator is
maintenance-free and supplied completely with a ready-towire connecting cable.
A microprocessor-based high performance positioner
guarantees accurate control. The close-off position is selfadjusting by means of an automatic synchronization function.
Synchronization is performed when the applied control signal
is 0 V or 10 V. The actuator then drives every minute for 5
seconds into the end position in order to ensure close-off
even after manual operation.
VERSIONS
Standard
With manual operation
With manual operation
and auxiliary switches
Special versions
manual operation
Provided by the valve
adjustment cap
Integrated
"
Integrated
"
Special cable length
length = 3 m / 5 m / 10 m
stem
force
180 N
300 N
180 N
300 N
180 N
300 N
aux.
switch S1
–
–
–
–
x
x
upon request
aux.
switch S2
–
–
–
–
x
x
housing
type
B
B
C
C
C
C
OS number
M7410E1002
M7410E1028
M7410E2026
M7410E2034
M7410E4022
M7410E4030
EN0B-0097GE51 R0909
2
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
MOUNTING POSITION
The actuator may be mounted only beside or above the valve.
Adjust the valve in the correct position before mounting the
actuator.
Fig. 1. Mounting positions
MOUNTING
Before the actuator is fixed to the valve, the adjustment cap
must be removed (Fig. 2). Make sure that the actuator is in
the open position (factory-supplied position) before fixing the
actuator to the valve body.
SWITCH SELECTION
The built-in selector switches must be set according to the
valve type (2-way or 3-way), valve size, and the controller
output signal (0...10 V or 2...10 V), see Fig. 4.
Y=+10V=
AB
Y=+10V=
AB
Y=+10V=
OPENS
OPENS
OPENS
A-AB
FACTORY
SETTING
100%...0%
0%...100% 0...10V
2...10V
A
AB
B
Fig. 4. Selecting valve type and output signal
ELECTRIC WIRING
The electrical installation must comply with Fig. 5.
INPUT SIGNAL OVERRIDE
To override the controller output signal, the input signal must
be connected to COM (0 %) or 24 V (100 %) using an
external switch (see Fig. 5).
AUTO
Y = 0...+10V
FACTORY
SETTING
Y = 2...+10V
Fig. 2. Removing protection cap
The actuator must be mounted by hand. Do not use tools or
additional force insofar as this may damage the actuator and
valve.
Fig. 3. Mounting the actuator
0%
24 VAC
BROWN
Y
GREEN
COM
WHITE
AUTO
100%
24 VAC
BROWN
Y
GREEN
COM
WHITE
Y
24 VAC
0 ... +10 V
2 ... +10 V
COM
Y
24 VAC
0 ... +10 V
2 ... +10 V
COM
0 / 2 V
10 V
Fig. 5. Connection of input switch
3 EN0B-0097GE51 R0909
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
MANUAL OPERATION
Actuators with the OS-number M7410E2... and M7410E4...
feature a hexagonal key hole for manual operation. For more
comfort, an additional knob for manual adjustment is packed
separately. To prevent valve damage, operation is permitted
only when there is no power applied to the motor.
4 mm
Adjustment of Auxiliary Switch 2
The auxiliary switch should be adjusted by a skilled person,
only. Move the actuator to the position where the switch is to
Fig. 6. Manual operation
COMMISSIONING ADVICE
A functional check of the valve actuator can be carried out by
changing the Y input signal. The movement of the actuator
stem (Fig. 7) indicates whether the valve is opening or
closing. If the direction of travel is not correct, the
direct/reverse-switch must be reset.
be operated. Cut the plastic skin with a sharp knife. The
adjustment screw can be accessed below the skin. Turn the
screw clockwise until the end stop is reached. Turn the screw
counterclockwise until the switch point is achieved. To check
that the required position has been set, move the actuator.
Finally, seal the adjustment hole with a piece of tape.
Fig. 8. Auxiliary switch cables
a
b
c
a
b
c
17.8 mm 11.7 mm
Fig. 7. Movement of the actuator stem
AUXILIARY SWITCHES
The actuators with the OS-number M7410E4022 and
M7410E4033 feature 2 auxiliary switches. Each switch has its
own cable. Auxiliary switch S1 with fixed switchpoint when the
stem position is in. Auxiliary switch S2 with adjustable
switchpoint when the stem position is out.
Fig. 9. Adjustment of auxiliary switch S2
EN0B-0097GE51 R0909 4
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
Electric Wiring of Auxiliary Switches
The electrical installation must comply with the wiring diagram
shown in Fig. 10. If the auxiliary switch is connected to
230 Vac, a switch with a contact gap of at least 3 mm for each
pole must be fitted with the installation.
24 Vac:
max. 100 mA
DN 15,
DN 20
(230 Vac only):
open
AB
230 Vac:
max. 5 (1)A
AB
M7410E
close
AB
Application Example:
Switching Off an Electrical Appliance
2-Way-Valve
DN 15, DN 20
E. g. fan, pump etc.
BLUE
max. 5 (1)A
Fig. 11. Electric wiring of auxiliary switch
All Other Valves
DN 15 - DN 40DN 25 - DN 40DN 15 - DN 20
BLACK
DN 25 DN 40
DN 15 DN 40
DN 15 DN 20
close
AB
AAB
B
close
AAB
B
BROWN
BLUE
BLACK
BROWN
AAB
BLUE
ABAB
AAB
B
B
BROWN
BLACK
BROWN
AAB
AAB
BLUE
open
openclose
B
open
B
BROWN
BLACK
BROWN
E. g. fan, pump etc.
BLUE
max. 5 (1)A
BLACK
Fig. 12. Electric wiring of auxiliary switch
BLUE
BLACK
BLUE
BLACK
BLUE
BLACK
Fig. 10. Electric wiring of auxiliary switch
5 EN0B-0097GE51 R0909
M7410E SMALL MODULATING LINEAR VALVE ACTUATOR
DIMENSIONS (MM)
58
100
82
109
49
Fig. 13. Housing type B
60
49
Fig. 14. Housing type C
87
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich / Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com