Honeywell M7164, M7184, M7161 User Manual

Page 1
M7161, M7164, M7184
The M7161, M7164 and M7184 Electronic Modutrol Motors provide proportioning control of zone dampers and valves when used with modulating dc voltage input.
M7161 and M7164 replace M734H,J Motors and
Ranco LA2-1000 and 2000 Linear Actuators.
M7184 replaces M744D Motors.
M7161, M7164 rated for 35 lb-in. torque.
M7184 rated for 150 lb-in. torque.
M7164G is electrically normally open; all other
motors are electrically normally closed.
Oil immersed motor and gear train for reliable
performance and long life.
Wiring box provides NEMA 3 weather protection.
Actuator motor and circuitry operate from 24 Vac.
Models available with factory installed transformer,
or an internal transformer can be field added.
Quick-connect terminals standard—screw termi­nal adapter available.
Adapter bracket for matching shaft height of older motors is standard with replacement motors.
Nominal timing of 30 seconds for 90° stroke and 60 seconds for 160° stroke.
Valve and damper linkages, explosion proof hous­ing, and auxiliary switches available as accessories.
Die-cast magnesium housing.
Used with Honeywell W7080 Multizone System.
CONTENTS
Specifications ................................................ 2
Ordering Information .................................... 2
Installation .................................................... 4
Operation and Replacement.......................... 9
Checkout...................................................... 11
G. R. • Rev. 12-92 • ©Honeywell Inc. 1992 • Form Number 63-2197—2
Page 2
M7161, M7164, M7184 SPECIFICATIONS • ORDERING INFORMATION
Specifications
MODELS:
M71 6 1 A,B,G M71 6 4 A,B,G M71 8 4 A
Control Type Suffix Letter 71 is dc voltage input A: is fixed stroke
0.8-3.3, 4-7, 6-9 or (90° or 160°), electrically
10.5-13.5 Vdc normally closed, no auxiliary switches.
Power Rating B: is fixed stroke 6 is low power— (90° or 160°), electrically
35 lb-in. torque normally closed,
8 is high power— 1 auxiliary switch.
150 lb-in. torque G: is fixed stroke
(90° or 160°), electrically normally open, no auxiliary switches.
Output Drive 4 is dual-ended shaft, nonspring return. 1 is single-ended shaft, nonspring return.
MOTOR ROTATION:
Normally closed M7161A,B and M7164A,B; M7184A
drives to fully counterclockwise (as viewed from the power end) to the fully closed position when powered input signal is at a minimum.
Electrically normally open M7161G and M7164G drive
clockwise (as viewed from the power end) to the fully open position when the powered input signal is at a minimum.
STROKE: Fixed 90° or 160° stroke models available. TIMING: Nominal 30 seconds for 90° stroke and 60 seconds
for 160° stroke.
DEAD WEIGHT LOAD ON SHAFT:
Power End Auxiliary End
M7161 100 lb (45.4 kg) N/A M7164 100 lb (45.4 kg) 100 lb (45.4 kg) M7184 200 lb (90.8 kg) 200 lb (90.8 kg)
300 lb (136.2 kg) maximum combined (power and auxil-
iary end) dead weight load.
MAXIMUM DAMPER RATING:
M7161A,B,G and M7164A,B,G: B dimension = 48 in. M7184A: B dimension = 202 in.
AMBIENT TEMPERATURE RATINGS:
Maximum: 150° F [66° C] at 25% duty cycle. Minimum: -40° F [-40° C].
SHAFT: 3/8 in. [9.5 mm] square.
M7161 Models: Single-ended shaft.
M7164 and M7184 Models: Dual-ended shaft. DIMENSIONS: See Fig. 1. UNDERWRITERS LABORATORIES INC. LISTED:
File No. E4436, Guide No. XAPX. CANADIAN STANDARDS ASSOCIATION CERTIFIED:
General Listing File No. LR1620, Guide 400-E.
ELECTRICAL RATINGS:
Voltage Vac @ Current Power Con­50/60 Hz Draw (A) sumption (W)
M7161 24 0.62 14 M7164 120 0.20 19 M7184 24 0.80 18
AUXILIARY SWITCH RATINGS (Amperes):
One Contact
a
Rating
Full Load 7.2 3.6 Locked Rotor 43.2 21.6
a
40 VA pilot duty, 120/240 Vac on opposite contact.
ACCESSORIES:
ES650117 Explosion-proof Housing: Encloses motor for
use in explosive atmospheres. Not for use with Q601, Q618, and Q455 Linkages. Order separately from Nelson Electric Co. Requires Honeywell 7616DM Coupling.
Q607 External Auxiliary Switch: Controls auxiliary equip-
ment as a function of motor position.
120V 240V
Ordering Information
When purchasing replacement and modernization products from your wholesaler or your distributor, refer to the price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Satisfaction Honeywell Inc., 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (612) 951-1000
In Canada—Honeywell Limited/Honeywell Limitée, 740 Ellesmere Road, Scarborough, Ontario M1P 2V9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
2
Page 3
M7161, M7164, M7184
SPECIFICATIONS
Q605 Damper Linkage: Connects motor to damper. In-
cludes motor crank arm.
Q618 Linkage: Connects Modutrol Motor to water or
steam valve.
Q601 Bracket and Linkage Assembly: Connects
Modutrol Motor to water or steam valve.
Q5001 Valve Linkage: Connects Modutrol Motor to
water or steam valve.
Q100 Linkage: Connects Modutrol Motor to butterfly
valve.
221455A Motor Crank Arm: Infinitely adjustable crank
arm. Approximately 0.75 inch shorter than the 4074ELY Crank Arm; can rotate through downward position and clear base of motor without requiring use of adapter bracket.
through the downward position and clear base of motor without requiring use of adapter bracket.
220738A Adaptor Bracket: Raises shaft height 0.75 in.
[19 mm].
220741A Screw Terminal Adapter: Converts the standard
quick-connect terminals to screws terminals.
Transformers: Mounted internally, provide 24 Vac power
to motor.
198162JA: 24 Vac, 50/60 Hz (for electrical isolation). 198162EA: 120 Vac, 50/60 Hz. 198162GA: 220 Vac, 50/60 Hz. 198162AA: 120/208/240 Vac, 50/60 Hz.
4074ERU Weatherproofing Kit: Provides NEMA 3 rat-
ing when Modutrol IV Motor is mounted in other than upright position.
7617ADW Motor Crank Arm: Approximately 0.75 inch
shorter than the 7616BR Crank Arm; can rotate
Fig. 1—Dimensions in in. [mm].
NOTE: M7161 does not have auxiliary shaft. All other dimensions are the same.
TOP VIEW OF 220738A BRACKET ONLY
WIRING BOX
BASE MOTOR
AUXILARY END
4.88 124]
3.93
6.45
[164]
[100]
.64 [16]
.43
[11]
POWER END
.27 [7]
4.88 [124]
5.54 [141]
5.5
[140]
.80 [20]
1.47 [37]
.76 [19]
POWER END
2.59 [66]
5.39
[137]
.27
[7]
.96
[24]
4.06 [103]
1.5 [38]
.50 [13]
2.4 [61]
1.75 [44]
4.22
[107]
5.82
[148]
2.3
[58]
.67
[17]
.15
[4]
ADAPTER BRACKET
.60 [15]
7.3 [185]
1.25 [32]
2.50 [64]
.75 [19]
M302F
3 63-2197—2
Page 4
M7161, M7164, M7184 INSTALLATION
Installation
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
!
1. Disconnect power supply before beginning installation to prevent electrical shock and equipment damage.
2. Never turn the motor shaft by hand or with a wrench—this will damage the motor.
3. Always conduct a thorough checkout when installation is complete.
LOCATION
Install the Modutrol Motor in any location except where acid fumes or other deteriorating vapors might attack the metal parts, or in atmospheres of escaping gas or explosive vapors. Motors are rated for ambient temperatures between
-40° F [-40° C] and 150° F [ 66° C].
Allow enough clearance for installing accessories and servicing the motor when selecting a location (see Fig. 1). When mounting the motor outdoors in an upright position, use liquid-tight conduit connectors and wiring box to provide NEMA 3 weather protection. When mounting the motor outdoors in other than an upright position, use the 4074ERU Weatherproofing Kit and liquid tight conduit connectors to provide NEMA 3 weather protection.
MOUNTING
Always install motors with the crankshaft horizontal.
Mounting flanges extending from the bottom of the motor housing are drilled for 1/4 inch [6.4mm] machine screws or bolts.
M7161A,B; M7164A,B and M7184A Motors are ship­ped from the factory in the closed position (at the limit of counterclockwise rotation as viewed from the power end of the motor). M7161G and M7164G are shipped in the open position (at the limit of clockwise rotation as viewed from the power end of the motor). See Fig. 2.
damper linkage applications (either to provide clearance for the crank arm to rotate through the downward position, or to allow the damper linkage to reach the shaft).
To mount the motor with the bracket:
1. Mount the bracket to the equipment with existing or
standard bolts.
2. Mount the motor to the bracket, with the bolts pro­vided, through the threaded holes in the bracket. See Fig. 3. For valve linkage applications, see Fig. 4, the bracket should first be mounted to the linkage so the bracket can provide a convenient base for positioning the motor. After the motor shaft is aligned, it can then be attached to the bracket with the four bolts provided. The bolts are inserted through the inner set of slots on the motor flange and into the threaded holes of the bracket.
DAMPER LINKAGES
A 220738A Mounting Bracket is packed with replace­ment motors. Using this bracket is optional for many damper applications. The bracket may be needed in damper
Fig. 2—Limits of motor rotation.
VERTICAL REFERENCE
10°
90 DEGREE STROKE
M7161, M7164
FULLY CLOSED
10 °
90°
FULLY OPEN
VERTICAL REFERENCE
VERTICAL REFERENCE
10°
160 DEGREE STROKE M7161, M7164, M7184
45°
FULLY CLOSED
90°
FULLY OPEN
FULLY CLOSED
160°
FULLY OPEN
ADAPTER BRACKET
The 220738A Adapter Bracket, positioned between the motor and the equipment, raises the shaft height of the motor by 0.75 inch to match that of the M734 and M744 Motors. This is required on all valve linkage applications, Q607 External Auxiliary Switch applications, and on some
90 DEGREE STROKE
M7184
M777A
4
Page 5
M7161, M7164, M7184
INSTALLATION
applications requiring the crank arm to rotate through the bottom plane of the actuator. If the bracket is not used in a replacement application, the damper linkage must be ad­justed to the new shaft position.
The motor comes without a crank arm. The crank arm is included in the Q605 Linkage or may be ordered separately (see Accessories).
For detailed instructions on the assembly of specific linkages, refer to the instructions packed with each linkage. In general, however, check the following points of operation when installing a motor and linkage:
1. Linkages for valves and louver type dampers should
the maximum required distance while the motor moves through its full stroke.
2. With modulating control, maximum damper opening
should be no more than 60°. Little additional airflow is provided beyond this point.
3. The motor must be stopped at the end of its stroke by the limit switch and must not be stalled by the damper or valve. The motor will be damaged if it is not permitted to complete its full stroke.
4. Do not exceed the motor ratings in any installation.
5. Do not turn motor shaft manually or with a wrench— this will damage the motor.
be adjusted so that the damper or valve moves through only
Fig. 3—Mounting motor with an adapter bracket. The bracket is first mounted to the equipment with standard bolts. The motor is then mounted to the bracket using the bolts provided that thread into the bracket holes.
BOLTS
STANDARD BOLTS (4)
1
PROVIDED (4)
WIRING BOX
POWER END
ADAPTER BRACKET
EQUIPMENT BASE
1 NO. 12 OR 1/4 IN. ZINC PLATED MACHINE SCREWS OR BOLTS.
M307G
MOTOR
POWER END
POWER END
5 63-2197—2
Page 6
M7161, M7164, M7184 INSTALLATION
Fig. 4—Motor mounting on Q618 Valve Linkage.
VALVE LINKAGE
STANDARD BOLTS
2
1
VALVE
ADAPTER BRACKET
BOLTS PROVIDED (4)
POWER END OF MOTOR
WIRING BOX
MOTOR
1
NO. 12 OR 1/4 IN. ZINC PLATED MACHINE SCREWS OR BOLTS.
FIRST HAND TIGHTEN BOLTS
2
SECURING BRACKET TO LINKAGE. TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOUR BOLTS PROVIDED.
VALVE LINKAGES
The 220738A Mounting Bracket must be used with the Q100, Q601 and Q618 Linkages in all valve applications. Refer to instructions packed with each linkage for detailed assembly instructions. The 220738A Mounting Bracket is not required for the Q5001 Linkage.
WIRING
Disconnect power supply before wiring to prevent electri­cal shock or equipment damage. All wiring must agree with applicable codes, ordinances, and regulations.
Make sure that the voltage and frequency stamped on the motor correspond to the characteristics of the power supply. See Figs. 6-7 for typical system wiring.
Make certain that the voltage and frequency stamped on the transformer correspond to the characteristics of the power supply.
The motor terminals are quick-connects located on top of the printed circuit board shown in Fig. 5. Access to the wiring compartment is gained by removing the four screws on the top of the wiring box and lifting off the cover.
AUXILIARY SWITCH
The auxiliary switch in the M7161B and M7164B is an spdt switch that is actuated by an adjustable cam. The cam is factory-mounted on the motor shaft at the power end of the motor. The setting of the cam determines the point in the motor shaft rotation at which the auxiliary equipment will be switched on or off. Auxiliary switch wiring is shown in Fig. 8.
M316G
Fig. 5—Terminals and auxiliary switch.
RIGHT INNER AUXILIARY SWITCH
INNER AUXILIARY
F
C(+)
R(-)
T2
T1
*
M7161B1018 INNER CAM IS RED; OUTER CAM IS BLUE.
NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY.
SWITCH CAM (BLUE)
POWER END
OUTER AUXILIARY SWITCH CAM (RED)
*
*
M439D
6
Page 7
M7161, M7164, M7184
INSTALLATION
Fig. 6—Parallel-connected motors with one
input signal.
DAMPER MOTORS
L1
(HOT)
1
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
C
L1
R
L2
F
C
L1
R
L2
F
C
L1
R
L2
F
+
MODULATING DC VOLTAGE SOURCE
M3005
Fig. 7—Optional override switches to drive
motor open or closed.
Fig. 8—Auxiliary switch color-coded leadwires in M7161B, M7164B.
RIGHT AUXILIARY SWITCH
BLACK/BLUE
BLACK/RED
BLACK/YELLOW
NORMALLY CLOSED CONTACT MAKES RED TO YELLOW WHEN
1
SWITCH FOLLOWER IS ON UPPER LEVEL.
WIRING SHOULD BE NEC CLASS 1 UNLESS POWER SUPPLY MEETS
2
CLASS 2 REQUIREMENTS. TAPE UNUSED LEADS. MAKE CERTAIN THE CURRENT DRAW OF THE EXTERNAL CIRCUIT IS LESS THAN CONTACT RATING OF SWITCH.
LEADS ARE BLACK WITH COLORED TRACERS.
3
N.C.
1
COM.
N.O.
M3003
NOTE: The following instructions are for normally closed
motors (motor shaft rotates clockwise , as viewed from the power end of the motor, on an increase in signal).
DAMPER MOTOR
C
L1
(HOT)
1
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
OPTIONAL N. O. SWITCH, MOTOR WILL RUN TO FULLY CLOSED
2
(M7161G, M7164G) OR FULLY OPEN (M7161A,B; M7164A,B; M7184A) POSITION WHEN SWITCH CLOSES, AS LONG AS POWER IS AVAILABLE AT L1, L2.
3
OPTIONAL N. C. SWITCHES, FINE SILVER OR DRY CIRCUIT CONTACTS REQUIRED. MOTOR WILL RUN TO FULLY OPEN (M7161G, M7164G) OR FULLY CLOSED (M7161A,B; M7164A,B; M7184A) WHEN EITHER C OR R LEAD IS OPENED.
L1
R
L2
F
3
+
MODULATING
2
3
DC VOLTAGE SOURCE
M3004A
AUXILIARY SWITCH SETTING PROCEDURE (Fig. 9)
CAUTION
!
1. Live circuits are exposed during the auxiliary switch adjustment procedure. Always turn off power before adjusting switch cams.
2. Do not turn motor shaft by hand or with wrench as damage to the motor can result.
1. Remove cover of wiring box.
2. Run motor to fully closed position.
3. Determine amount of shaft rotation, in degrees, desired
before switch is energized.
4. Turn off power. Note position of cam slots:
a. If 10° differential is desired, rotate the cam with
screwdriver to the desired position for switch action.
b. If 1° differential is desired, rotate the cam ap-
proximately 180° with screwdriver, then rotate to desired position for switch action.
NOTE: Each division on the cam represents 15° of motor
rotation. Therefore, if 60° of motor rotation is desired before switch operates, rotate the cam four divisions from the reference point.
5. Connect auxiliary equipment to auxiliary switch leads.
See Wiring section.
6. Turn on power and check for proper switch differen­tial and switching of auxiliary equipment by driving the motor through full stroke in both directions. If necessary, re­peat steps 4 and 6 until correct switching action is obtained.
7. Replace cover of wiring box.
CAUTION
!
Before servicing, disconnect all power supplies to de-energize the auxiliary switches.
7 63-2197—2
Page 8
M7161, M7164, M7184 INSTALLATION
Fig. 9—Auxiliary switch adjustments.
M7161B1018
2
L2 L1
(HOT)
1
MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM.
1/8 IN. STRAIGHT-BLADE SCREWDRIVER
RIGHT/INNER AUXILIARY SWITCH
T1 T2
1
2
R(-)
C(+) F
RIGHT/INNER AUXILIARY SWITCH
INNER AUXILIARY CAM (RED)
POWER END
OF MOTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TRANSFORMER MAY BE EXTERNAL OR INTERNAL.
OUTER AUXILIARY CAM (BLUE)
M7161A,G; M7164; M7184
2
(HOT)
T1 T2
R(-)
C(+) F
RIGHT/INNER AUXILIARY SWITCH
SLOW RISE PORTION (APPROX. 10° DIFF.)
MOVE SCREWDRIVER AT TOP ONLY TO ADJUST CAM.
L2
1
L1
1/8 IN. STRAIGHT-BLADE SCREWDRIVER
SLOW RISE PORTION (APPROX. 10° DIFF.)
INNER
AUXILIARY
CAM
(RED)
INNER
AUXILIARY
CAM
(BLUE)
SWITCH FOLLOWER
SWITCH FOLLOWER
FAST RISE PORTION (APPROX. 1° DIFF.)
RIGHT/INNER AUXILIARY SWITCH
FAST RISE PORTION (APPROX. 1° DIFF.)
INNER AUXILIARY CAM (BLUE)
POWER END
OF MOTOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
TRANSFORMER MAY BE EXTERNAL OR INTERNAL.
OUTER AUXILIARY CAM (RED)
M440D
8
Page 9
M7161, M7164, M7184
OPERATION AND REPLACEMENT
Operation and Replacement
OPERATION
The M7161, M7164 and M7184 Motors operate in response to a dc voltage input signal to terminals C and R, positioning a valve or damper at any position between fully open and fully closed. The input signal causes the modified dc bridge circuit in the motor to become unbalanced. The small signal resulting from the bridge unbalance is ampli­fied and energizes 1 of 2 triacs to run the motor. As the motor
REPLACEMENT OF RANCO LA2 LINEAR ACTUATORS AND HONEYWELL SPECIAL PACKAGED HVAC UNIT MOTORS
The M7164 Motors may be used for field replacement of Ranco LA2-1000 Series Zone Mixing Damper Actuators and LA2-2000 Series Modulating Heating Valve Actuators as described below. To select the appropriate model, refer to Table 1.
runs, a feedback potentiometer driven by the motor moves to rebalance the bridge. When the bridge is balanced, the motor stops.
TABLE 1—CROSS REFERENCE OF RANCO AND HONEYWELL ELECTRONIC MOTORS.
Ranco Input Linkage
Actuator Family Voltage dc Honeywell Motor Replacement Required
LA2-1000 Zone Mixing Damper Actuator direct-action, spring return, nominal 35 lb
10.5 to 13.5 M7161G1009 M7164G1006 M7164G1030 M7164A1017
a,e a,e a,e
a
90 deg, 30 sec, 120 Vac, Q605, 19W, 35 lb-in. [4.0 N-m], pushrod electrically normally openc. 90 deg, 30 sec, 24 Vac, Q605, 14W, 35 lb-in. [4.0 N-m], pushrod
electrically normally closedc. [155.6N] force, 2 in.[50.8 mm] stroke.
LA2-2000 Modulating Heating
4.0 to 7.0 M7161G1017 M7164G1014
Valve Actuator reverse-acting, spring return,
M7161G1025 M7164G1022
nominal 35 lb [155.6 N] force, 2 in. [50.8 mm]
M7164A1009
stroke.
a
New damper linkage and pushrod required.
b
This motor is used with modulating gas valves (butterfly valves).
c
On the Ranco Actuator, electrical normal is the position (extended = open; retracted = closed) of the actuator drive shaft (as
b,e b,e
d,e d,e
d
90 deg, 30 sec, 120 Vac, Q100 19W, 35 lb-in. [4.0 N-m], electrically normally openc.
160 deg, 60 sec, 24 Vac, Q601, Q618 14W, 35 lb-in. [4.0 N-m], or Q5001 electrically normally openc.
160 deg, 60 sec, 24 Vac, Q601, Q618 19W, 35 lb-in. [4.0 N-m], or Q5001 electrically normally closedc.
viewed from the power end) when power is applied to the motor and input (command) signal is at the lowest point of the input voltage range.
d
These motors are for use with modulating steam or hot water valves: valve and linkage replacement are required.
e
This normally open motor provides power end damper linkage connection when space constraints prevent using a normally closed motor.
9 63-2197—2
Page 10
M7161, M7164, M7184 OPERATION AND REPLACEMENT
Fig. 10Replacing Ranco Linear Actuator with M7164 in a damper application. Use linkage (Q605 recommended) and pushrod to change from a linear to a circular force.
RANCO
HONEYWELL
90 DEGREE MOTOR
CRANK ARM (221455A)
PUSH ROD NO. 27520 C THRU L
BALL JOINT NO. 27518
MOUNTING IN A DAMPER APPLICATION
Remove the Ranco Actuator and mount the M7164 re-
placement as shown in Fig. 10.
MOUNTING IN A VALVE APPLICATION
Remove the Ranco Actuator and linkage and install the appropriate linkage and Modutrol IV motor according to the instructions in the Installation section supplied with the linkage.
WIRING CONVERSION
Disconnect power supply before beginning installation to prevent electrical shock or equipment damage. All wiring must comply with local electrical codes, ordinances, and regulations.
To wire the M7161, M7164, proceed as follows. See Table 2. Disconnect power, then remove wiring from Ranco Actuator and connect to the motor according to Table 2 and Fig. 11.
M 493A
TABLE 2—LA2-1000/2000 TO M7164 TERMINAL INTERCHANGES.
From Ranco LA2-1000/2000 To Honeywell M7161G, M7164A,G
Terminal Function Terminal Function
1—COMD (+) + command signal C + signal 6—REF (—) signal common R - common 9—24 Vac power supply L1a or T1 power supply 10—24 Vac power supply L2a or T2
b
F
a
Terminals L1 and L2 are used for 120 Vac motors. New power supply wiring must be run for 120 Vac motors.
b
This terminal is not used when replacing Ranco Actuators.
10
Page 11
M7161, M7164, M7184
OPERATION AND REPLACEMENT • CHECKOUT
Fig. 11Wiring for replacement of Ranco LA2-1000/2000 Series Actuators with Honeywell 24V M7164A,G.
TRANSFORMER
L1
(HOT)
1
L2
TO OTHER ZONE TR3/TR4
ZONE DISCHARGE SENSOR
TR1
ZONE
2 3
5
24 VAC
C
3
C
2
C
1
1
2
4
6
TR-3 ZONE THERMOSTAT
EA3
ZONES
HI
1
3
8
9
7
L0
2
5
4
LOAD ANALYZER MODULE
3
4
6
5
24VDC
H
H
H
10
11
COMD(+)
1
LA1-1000/2000
REF( )
TRANSFORMER
L1
(HOT)
1
TO OTHER ZONE TR3/TR4
L2
T1
T2
L1
L 2
C
R
F
MOTOR
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND DIS-
1
CONNECT MEANS AS REQUIRED.
SOLID LINES ( ) ARE EXISTING CONNECTIONS. DASHED LINES
2
( ) ARE NEW CONNECTIONS. "X'S" INDICATE REMOVAL OF EXISTING WIRING.
CONNECTIONS SHOWN ARE FOR 24V MOTORS. MODELS WITH
3
L1, L2 TERMINALS REQUIRE NEW 120V POWER SUPPLY WIRING
+
3
2
1
12
ZONE
12 11
10
9 8 7
6
24 VAC
9
10
24 VAC
3
SERIES
ACTUATORS
(ZONE)
M3006
After installation and linkage adjustment, operate the
motor through the thermostat or panel. Make sure that:
• The motor operates the damper or valve properly.
• The motor responds properly as input voltage is varied.
• The auxiliary switch, if used, operates at the desired point of motor rotation.
Inspect the motor, linkage, and valve or damper to see that all mechanical connections are correct and secure. In damper installations, the pushrod should not extend more than a few inches past the ball joints. Check to see that there is adequate clearance for the linkage to move through its stroke without binding or striking other objects. See System Instructions for additional checkout procedures.
Checkout
MOTOR OPERATION CHECK
M7161A,B, M7164A,B and M7184A
Jumper terminals C and F; motor should drive to the fully open (clockwise ) position as viewed from the power end. Remove jumper. Remove the lead from terminal C or R; motor should drive to the closed (fully counterclock­wise ) position.
M7161G and M7164G
Jumper terminals C and F; motor should drive full closed (fully counterclockwise position as viewed from the power end). Remove jumper. Remove the lead from termi­nal C or R; motor should drive to the open (fully clock­wise ) position.
11 63-2197—2
Page 12
Home and Building Control Home and Building Control Helping You Control Your World
Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, Minnesota 55422 Scarborough, Ontario
M1P 2V9
Printed in U.S.A.
QUALITY IS KEY
Loading...