Honeywell HP970 Catalog Page

Pneumatic Humidstats
70-6910 643
Pneumatic
Controls
HP970 Pneumatic Humidistat
Two-pipe, single setpoint, pneumatic humidistat used to provide
proportional control of pneumatic valves on humidification or
dehumidification systems.
Durable HP970 series humidistat.
Pilot operated for high capacity.
Direct Acting (DA) and Reverse Acting (RA) models are available.
Vertical or horizontal mounting.
Backplate has molded air connections; no separate fittings needed.
Variety of cover finishes and display styles available.
HP970 Typical Piping
Application: Humidity
Dimensions, Approximate: 3 1/4 in. high x 2 in. wide x 1 5/8 in. deep
(83 mm high x 51 mm wide x 41 mm deep)
Airflow Usage: 0.011 scfm (5.2 mL/s)
Maximum Operating Temperature:
45 F to 125 F (7 C to 52 C)
Maximum Storage Temperature: -30 to +150 F (-34 to +66 C)
Maximum Operating Pressure:
25 psi (170 kPa)
Accessories:
AK3863-Honeywell Thermostat Tool Kit, TP970/TP900
CCT729A-Gauge Adapter for Calibration. Add 305965 0 to 30 psi gauge
for Complete Tool.
CCT735A-Thermostat Cal bration Tool includes Allen wrench for cover
installation.
305965-1-1/2 in. diameter, 1/8 NPT center stem back mount Pressure
Indicating gauge (0 to 30 psi scale) with ±4% accuracy
14002430-001-Thermostat Guard
14003192-001-Wallplate adapter kit. Adapts HP970 or TP970 series
humidistats to HP900 and TP900 flush mounted and TP910 series
flush or surface mounted installations
14004406-124-Humidistat Cover assembly Satin Chrome with setpoint
display and Honeywell logo for vertical mounting, scale range 15 to
75% RH
Replacement Parts:
14001865-001-Filter Cartridge Assembly
14002053-001-Back Plate Assembly
14002573-001-Modernization Kit to convert all 1 & 2 pipe Honeywell &
competitive pneumatic humidistats to TP970, TP971A, TP972, TP973,
TP974, TP9600 family; HP970, HP971 and HP972
-
C3225
N.C.
M
M B
HUMIDIFIER
VALVE
SUPPLY
HP972B
Product Number Action
Number of
Pipes
Scale Range (%
RH)
Throttling Range
(% RH) Setpoint Comments
HP970A1009/U Direct Acting 2 15 to 75% RH 3 to 15% RH Single Order Cover Separately
HP970B1007/U Reverse Acting 2 15 to 75% RH 3 to 15% RH Single Order Cover Separately
HP970B1015/U Reverse Acting 2 65 to 95% RH 3 to 15% RH Single Order Cover Separately
Loading...