Honeywell HP300ULM Product Installation Document

Honeywell 12 Clintonville Road Northford, CT 06472 http://www.honeywellpower.com
Access Control Power Supply/Charger
with Power Distribution Controller
PN 52387:A 12/29/05 ECN 04-350
HP300ULM
This product follows under the UL1481 Fire Alarm Systems, UL603 Burglary Alarm Systems and UL294 Access Control Systems. The HP300ULM unit is to be installed in a fail safe mode unless authorized by the local AHJ. This product must be installed in compliance with Article 760 of the National Electrical Code, NFPA70, as well as NFPA72 National Fire Alarm Code and all applicable local codes.
1 Description
The HP300ULM is a 12VDC or 24VDC power supply with an HPMOM6 distribution controller to be used with Card Access Systems. It provides 12/24VDC through 6 power-limited outputs. The 6 outputs will switch ON or OFF security devices such as Magnetic Locks, Door Strikes, Magnetic Fire Door Holders, etc. The HPMOM6 offers a choice of two (2) outputs, “Fail Safe or Fail Secure” and a choice of two (2) Fire inputs, N/O or N/C, and Reverse Polarity triggered by the FACP. The Controller also has 2 Trouble/Alarm dry contact outputs type “Form C”; 1) Power Fail/ PTC Activated, and 2) FACP Triggered. The unit has not been evaluated as elevator equipment, and is not authorized for bell output in Mercantile applications.
2 Specifications
A) Power Supply Board
1. Input voltage: 120VAC 60Hz; Current: 1.40A max.
2. Output Voltage: 12VDC or 24VDC, jumper selectable; Current: 2.5A continuous output maximum, 2.0A plus battery charger (not supervised).
3. Fail safe dry contact output on AC Failure (within one minute).
4. Built-in charger for sealed lead acid or gel cell type batteries.
5. Instantaneous transfer to stand-by battery on AC failure.
6. Battery presence detection (within 1 minute)
7. Battery low disconnect at 9.90VDC or 19.90VDC.
8. High voltage disconnect at 15VDC or 30VDC.
9. Yellow LED (L3) indication for battery disconnected and battery low.
10. Fail safe dry contact output for Battery trouble (Fail Safe).
11. Battery polarity reversal protection.
12. Thermal overload and short circuit protection.
13. DC output PTC activated indication by Red LED (L2).
14. DC output failure indication by Red LED ( L4 ).
15. AC presence indication by Green LED ( L1 ).
16. DC output indication by Red LED ( L5 ).
17. Battery Leads included.
18. Power Board Dimensions: 5”L x 3.9”W x 1.5”H.
19. Enclosure Dimension: 17”L x 13.5”W x 4.75”H. Accommodates two 12 Volt 12AH batteries. When using larger batteries, a UL approved enclosure must be used.
B) Distribution Controller Board
Output (not supervised)
– 6 Fail Safe or Fail Secure
Continued on next page...
– Each PTC protected output rated 2.5A @ 23C with a maximum of 2.0A @ 49C. – Automatic Yellow LED status indication of activated PTC. – Test push button lights Yellow LED’s to verify their operation. – Red LED for power on indication.
Fire Alarm Control Panel Input
– Polarity reversing input. – Normally open (NO) or normally closed (NC) supervised input with 2.2K Ohm (EOL) resistor. – Engineering Reset (Optional) normally open (NO) or normally closed (NC) input with 2.2 K Ohm (EOL) resistor.
Alarm Outputs
– Alarm outputs are Fail Safe – When FACP activation occurs dry contacts activated. – Green LED indication when FACP is activated. – Dry contacts output for power failure to the HPMOM5.
Board Dimensions: 5.3" L x 3.5" W x 1.0" H (13.46 cm L x 8.89 cm W x 2.54 cm H).
3 Installation Instructions
1. Mounting
The power supply should be installed in accordance with all Governing National Electrical and Local Codes. Mount the power supply securely in the desired location using the four (4) mounting holes.
2. Power Supply Input Connection
Before connecting power review the entire wiring diagram for correct installation (see Fig. 1). With the AC power disconnected, connect 120VAC to the Fuse Block as follows; L=Black (HOT), N=WHITE (Neutral), G=GREEN (Ground). Select the output voltage 12VDC or 24VDC using Jumper J1 of the Power Board J1 OFF=12VDC, J1 ON=24VDC. Voltage is Factory set and Re-Adjusting will void Warranty.
3. Output Connections
There are 6 outputs selectable together as Switched Normally Open (NO) or Switched Normally Closed (NC). There are 2 possible output type connections in either case connect device negative to Neg terminal on HPMOM5.
1.) For Fail Safe operation connect device positive to DC STANDBY OUTPUT (+) on HPMOM6. DC power is
present in normal condition and will switch OFF when the FACP is triggered. Fail Safe operation devices such as Magnetic Locks should be connected to this output.
2.) For Fail Secure operation connect device positive to DC ALARM OUTPUT (+) on HPMOM6. DC power is not
present in normal condition and will switch ON when the FACP is triggered. Fail Secure operation devices such as Door Strikes should be connected to this output.
4. Fire Alarm Interface
Normally Open (NO), Normally Closed (NC) input or polarity reversal (Rev. Volt) input from the FACP are available to trigger the HPMOM6 operation. Connect the positive (+) and negative (-) from the FACP to the “REV. VOLT” terminals observing polarity, (polarity is referenced in alarm condition) or connect the NO or NC from the FACP output to the “FIRE INTRFC” terminals. Install the 2.2K Ohm (EOL) resistor provided at the FACP as shown in Fig 1 to supervise this connection.
5. Engineering Reset Input
This option is available when the jumper JL is removed. This will cause the HPMOM6 to latch upon receiving an alarm condition from the FACP. With this option in place and when the FACP resets, the unit will only reset by activating the “RESET” circuit.
a.) JL ON
terminals.
2 HP300ULMCB Installation Document P/N 52387:A 12/29/05
will cause the unit to follow the status of the FACP. Connect 2.2K Ohm resistor to the “RESET”
Continued on next page...