Honeywell Ecomax 0C, Ecomax 1C, Ecomax 2C, Ecomax 4C, Ecomax 3C Technical Information

...
Page 1
7 Edition 10 .17
Technical Information · GB
• For direct and indirect heating
• Economical, energy-saving operation by virtue of internal air preheating up to 650°C
• Uniform distribution of temperature by means of a high burner impulse
• Highly efficient with a ceramic burled tube recuperator or a cast steel ribbed tube recuperator.
Self-recuperative burner ECOMAX for gas
Page 2
ECOMAX · Edition 10.17 2
= To be continued
Contents
Self-recuperative burner ECOMA X for gas ..........1
Contents ............................................2
1 Application ........................................4
1.1 Direct heating ......................................4
1.2 Indirect heating ....................................4
1.3 Application examples ..............................5
1.4 ECOMAX for direct heating systems...............6
1.4.1 Flow rate control.......................................6
1.4.2 Air/gas ratio control....................................7
1.4.3 No pneumatic air/gas ratio control system ...........8
1.5 ECOMAX® for indirect heating systems ...........9
1.5.1 No pneumatic air/gas ratio control system .........10
1.5.2 Air/gas ratio control .................................10
2 Certification ......................................11
3 Structure .........................................12
3.1 Burner body .......................................12
3.2 Recuperator.......................................13
3.3 Air guide tube .....................................14
3.4 Gas insert .........................................15
3.5 Version overview ..................................16
4 Function ..........................................17
5 Selection ........................................ 19
5.1 Burner type .......................................19
5.2 Burner size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.3 Burner length .................................... 20
5.4 Burner head .......................................21
5.4.1 Use....................................................21
5.4.2 Gas type ..............................................21
5.5 Type of heating ...................................22
5.6 Connection for additional furnace cooling .......23
5.7 Electrode made of Kanthal APM..................23
5.8 Selection table ...................................24
5.8.1 ECOMAX..C.......................................... 24
5.8.2 ECOMAX..M .........................................24
5.8.3 ECOMAX..P.......................................... 25
5.8.4 ECOMAX..F..........................................25
5.8.5 Type code............................................26
5.9 Selection table for flue gas eductor EJEK ........27
5.9.1 Type code............................................28
5.10 Selection table for flue gas connector FLUP....29
5.10.1 Type code ..........................................30
6 Project planning information for direct heating ..31
6.1 Heating system design ...........................31
6.2 Flue gas guide tube FGT set ......................32
6.3 Flue gas eductor EJEK............................33
6.4 Furnace flue gas system..........................34
6.5 Installation........................................35
6.5.1 Installation position ................................ 35
6.5.2 Tangential or angled burner installation ............35
6.5.3 Clearances .......................................36
6.5.4 Furnace temperature measurement.................37
6.5.5 Heat guard ...........................................37
6.6 Flame control .....................................38
6.7 Burner control units and ignition transformers ..39
6.7.1 Burner control unit congurations ..................40
6.8 Gas connection ..................................41
6.8.1 Selecting components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
6.8.2 Gas pressure .........................................41
6.8.3 Operation with LPG .................................42
6.9 Air connection ....................................43
6.9.1 Selecting components ..............................43
6.9.2 Air pressure ..........................................43
6.10 Air flow monitoring ............................. 44
6.11 Purge air and cooling air........................ 44
6.12 Condition on delivery............................45
6.13 Cooling with ECOMAX ..........................45
6.14 Emissions ...................................... 46
Page 3
ECOMAX · Edition 10.17 3
= To be continued
6.15 Build up of noise................................ 46
6.16 Process boundary conditions . . . . . . . . . . . . . . . . . . . 47
6.17 Resistance of SiSiC ..............................47
7 Project planning information for indirect heating 48
7.1 Heating system design........................... 48
7.2 Radiant tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
7.3 Flue gas channelling ............................. 50
7.4 Furnace flue gas system ..........................51
7.5 Installation ........................................52
7.5.1 Heat guard ...........................................52
7.6 Flame control......................................53
7.7 Burner control units and ignition transformers ...54
7.7.1 Burner control unit congurations...................55
7.8 Gas connection ...................................56
7.8.1 Selecting components...............................56
7.8.2 Gas pressure .........................................56
7.8.3 Operation with LPG ...................................57
7.9 Air connection .....................................58
7.9.1 Selecting components...............................58
7.9.2 Air pressure ..........................................58
7.10 Air flow monitoring ...............................59
7.11 Purge air and cooling air .........................59
7.12 Condition on delivery ........................... 60
7.13 Increased furnace cooling with ECOMA X..K.... 60
7.14 Build up of noise .................................61
7.15 Emissions ........................................61
8 Accessories.......................................62
8.1 Air connection set.................................62
8.2 Air flow detector set...............................62
8.3 VAH connection set ...............................63
8.4 UV adapter set ....................................63
8.5 Purge air/cooling air nozzles......................63
8.6 Flue gas guide tube FGT Set..D ...................64
8.7 Flue gas eductor EJEK............................65
8.8 Flue gas connector FLUP.........................65
8.9 Ceramic radiant tube SERC..................... 66
8.10 Segmented flame tube SICAFLEX ............. 66
8.11 Cruciform spacer ................................67
8.12 Flue gas guide tube FGT SET ECO..SERC......67
8.13 Piping........................................... 68
8.13.1 Direct heating......................................68
8.13.2 Indirect heating ....................................69
9 Technical data ................................... 70
9.1 Dimensions .......................................71
9.1.1 ECOMAX..C for direct heating........................71
9.1.2 ECOMAX..M for direct heating......................72
9.1.3 ECOMAX..F for direct heating.......................73
9.1.4 ECOMAX..C for indirect heating .................... 74
9.1.5 ECOMA X..M for indirect heating ....................75
9.1.6 ECOMAX..F for indirect heating.....................76
10 Maintenance ....................................77
Feedback ...........................................78
Contact.............................................78
Page 4
ECOMAX · Edition 10.17 4
ECOMAX..M
ECOMAX..C
Application
1 Application
Self-recuperative burners ECOMAX are used for heating on either direct or indirect furnace systems in ON/OFF intermittent mode. The hot flue gases are fed through the ceramic or metallic heat exchanger, which is integrat- ed in the burner, heating the additional supply of cold combustion air flowing in the opposite direction. The maximum achievable air preheat temperature amounts to approx. 650°C, depending on the application.
1.1 Direct heating
In conjunction with an eductor EJEK to extract the flue gases, the burner ECOMAX is used to save energy in a direct heating system without long hot air pipes requir- ing insulation.
Applications include heat treatment furnaces in the
iron and steel industry and in the non-ferrous metal industr y.
1.2 Indirect heating
Self-recuperative burners ECOMAX are used in con­junction with metallic or ceramic radiant tubes and ceramic segmented flame tubes SICAFLEX for indirect heating. Indirect heating equipment is used whenever the combustion gases are to be separated from the product, e.g. in heat treatment furnaces with inert gas atmospheres in the steel industry or when heat-treating aluminium.
Page 5
ECOMAX · Edition 10.17 5
Application
Roller hearth furnace Bogie hearth furnace Batch furnace
1.3 Application examples
Page 6
ECOMAX · Edition 10.17 6
ApplicationApplication > ECOMAX for direct heating systems
1.4 ECOMAX for direct heating systems
In direct heating systems, the burner ECOMAX is com- bined with a flue gas guide tube FGT Set..D for routing the flue gases through the furnace lining and a flue gas eductor EJEK.
AGK
ECOMAX
FGT-SET..D
EJEK
Eductor EJEK generates a negative pressure by forc-
ing air through a centrally positioned nozzle and thus draws the flue gases out of the furnace chamber through the burner’s heat exchanger. The motive air
flow is adjusted on the basis of the negative pressure
measured on the pressure tap between the burner and the motive air nozzle. A flue gas valve AGK on the educ- tor, which closes due to its own weight, minimizes back-
flow of hot flue gas from the furnace into the burner or
infiltrated air being sucked into the furnace when the burner is switched off.
1.4.1 Flow rate control
For direct heating, flow rate control should be inte­grated in the system. The pressure loss in the recu­perator depends on the furnace temperature. When the furnace temperature is increased (at a constant air supply pressure), the air flow rate drops. This change in the air flow rate is measured by the orifice and the VAH changes the gas volume accordingly to ensure that the air index (lambda) on the burner is not dependent on the furnace temperature.
BVHM + MB7..L
VMV EKO
LEH
ECOMAX
VAH
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
AKT
p
sa-
p
sa
p
d-
VAS..N
The ECOMAX is equipped with an integrated air orifice. This can be used for recording the air flow rate as a
reference variable for the VAH. A separate upstream air orice is then no longer required. The impulse line pd­for gas is connected to the burner downstream of the integrated orice so that the minimum gas pressure is sufcient.
Page 7
ECOMAX · Edition 10.17 7
Application
1.4.2 Air/gas ratio control
If the system does not include flow rate control, tem- perature-dependent pressure losses in the burner are not compensated for. The air index lambda drops with increasing furnace temperature (increasing air preheat- ing). Therefore, in a cold furnace, an increased lambda value is to be set to ensure sufcient excess air, even when the furnace temperature is at its maximum. A fur- nace at 1100°C with λ = 1.1 (approx. 2% O2) requires a burner setting of approx. 4% O2, for example, when the
furnace is cold.
BVHM + MB7..L
VMV
ECOMAX
VAS..N
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
AKT
VAG
Page 8
ECOMAX · Edition 10.17 8
ApplicationApplication
1.4.3 No pneumatic air/gas ratio control system
When there is no pneumatic air/gas ratio control sys-
tem, slow opening gas valves and quick opening air control valves are to be used to ensure a safe burner start.
If there is no pneumatic air/gas ratio control system, the gas and air pressures must be controlled and moni- tored in the supply lines. Fluctuations in the supply pressure affect the burner capacity and the air index (lambda).
Air flow monitoring is recommended as low air pressure
protection (pursuant to EN 7462 and ISO 135772) if the system does not include a pneumatic air/gas ratio control system. The ECOMAX is equipped with an inte- grated air orifice which can be used for this. The air flow monitoring system may also be used to monitor pre- purge.
BVHM + MB7..N
VMV EKO
LEH
ECOMAX
VAS VAS..L
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
PDZ
DG
AKT
Page 9
ECOMAX · Edition 10.17 9
Application
1.5 ECOMAX® for indirect heating systems
For indirect heating, various radiant tubes are used.
Single ended radiant tube
Indirect heating with the ECOMAX burner can be carried out using a metallic radiant tube SERM or a ceramic radiant tube SERC. A flame tube made of SICAFLEX elements is fitted inside the radiant tube to guide the flue gases. The flue gases are discharged via a flue gas connector FLUP.
The high outlet velocity of the flame causes a recircula-
tion of the flue gases and thus:
– a reduction in NO
X
emissions,
– a uniform radiant tube temperature.
SER-M
FLUP
ECOMAX..M
SICAFLEX
SER-C
SICAFLEX
FLUP
ECOMAX..C
P and twin P radiant tube
P and twin P radiant tubes are used in some processes, for example in heat treatment systems for steel strip as an alternative to U or W radiant tubes. The new burner version ECOMAX..P with a special recuperator head is for use in P radiant tubes.
Gas Cold air
P radiant tube
Flue gas
Gas Cold air
Twin P
radiant tube
Flue gas
Page 10
ECOMAX · Edition 10.17 10
Application
1.5.1 No pneumatic air/gas ratio control system
For indirect heating, slow opening gas valves and quick
opening air control valves are to be used to ensure a safe burner start.
If there is no pneumatic air/gas ratio control system, the gas and air pressures must be controlled and moni- tored in the supply lines. Fluctuations in the supply pressure affect the burner capacity and the air index (lambda).
A system which includes air flow monitoring is recom-
mended to monitor pre-purge and as low air pressure protection (pursuant to EN 7462 and ISO 135772).
The ECOMAX is equipped with an integrated air orice
which can be used for this.
VR..N
VMV
ECOMAX
VG VG..L
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
PDZ
DG
AKT
1.5.2 Air/gas ratio control
The pneumatic air/gas ratio control system ensures
that changes in the air pressure in the air supply line are compensated for by controlling the gas pressure at the burner accordingly.
VR..N
VMV VG..L
ECOMAX
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
PDZ
DG
AKT
VAG
A system which includes air flow monitoring is also
recommended to monitor pre-purge (pursuant to EN 7462 and ISO 135772) even if there is a pneumatic air/gas ratio control system.
Page 11
ECOMAX · Edition 10.17 11
Certification
2 Certification
Certificates – see w ww.docuthek.com.
Machinery Directive
The product ECOMAX is a partly completed machine
pursuant to Article 2g of Directive 2006/42/EC and complies with the essential health and safety require- ments in accordance with Annex I, as stated in the Dec- laration of Incorporation.
Eurasian Customs Union
The product ECOMAX meets the technical specica-
tions of the Eurasian Customs Union.
Page 12
ECOMAX · Edition 10.17 12
Structure
3 Structure
The burner ECOMAX is composed of four modules:
burner body, recuperator, air guide tube and gas insert.
The modular design facilitates adapting the burners to
the respective application or integrating them into an existing furnace system. Maintenance and repair times are reduced, and existing furnace installations can eas- ily be converted.
3.1 Burner body
The burner body is made of cast aluminium, which
means it has a low weight. The housing has a double- wall design. The combustion air is fed into the burner via the outer annular void. This cools the burner body and reduces emissions. A shaped part made of vacu- um-formed ceramic fibres (RCF) is fitted in the housing as internal insulation on the flue gas side.
From construction stage B, the ECOMAX is equipped with two pressure taps on the air connection, which al­low the differential pressure to be measured across the orice so that the burner can be adjusted.
Page 13
ECOMAX · Edition 10.17 13
StructureStructure
3.2 Recuperator
The burner ECOMAX is available in three versions: – ECOMAX..C with ceramic burled tube recuperator – ECOMAX..M and ECOMAX..P with cast steel ribbed
tube recuperator
– ECOMAX..F with metallic flat tube recuperator
Ceramic burled tube recuperator
The surface of the ceramic recuperator, which is made
of SiSiC for high thermal stress, is burled in order to achieve high efficiency.
Cast steel ribbed tube recuperator
The ribs on the cast steel ribbed recuperator offer a
large surface area, allowing it to achieve high efficiency even at low temperatures.
The burner version ECOMAX..P with a special recu-
perator head is available for use in P radiant tubes. The geometry is tailored to this application to improve gas recirculation and therefore the temperature uniformity of the radiant tube.
Flat tube recuperator
The flat tube recuperator has a smooth surface. It is a
cost-effective alternative at a lower efficiency level.
Page 14
ECOMAX · Edition 10.17 14
Structure
3.3 Air guide tube
ECOMA X..C
Burners ECOMAX..C are equipped with a ceramic air
guide tube that for sizes 0 to 3 also serves as the com- bustion chamber.
ECOMA X..M, ECOMAX..F and ECOMAX..P
Air guide tube for ECOMAX..M and ECOMAX..F
Burners ECOMAX..M and ECOMAX..F are equipped
with an air guide tube made of heat-resistant steel.
Page 15
ECOMAX · Edition 10.17 15
Structure
3.4 Gas insert
The gas insert consists of the gas connection flange,
the torch with burner head and the spark electrode (also serves as monitoring electrode). A measuring orifice, which is integrated in the gas insert, allows for simple measurement of the gas flow rate. The orice is designed depending on the gas types (see 5.4.2).
To ensure accurate measurements of the pressure
differential on the integrated orice, flow to the ori- fice must not be disturbed. For this reason, burners ECOMAX are equipped as standard with a special pipe
nipple to serve as inlet section on the gas connection.
Gas insert without combustion chamber for ECOMAX..C (sizes 0 to 3)
Gas insert with combustion chamber for ECOMAX..M (sizes 1 to 3)
Gas insert with combustion chamber for ECOMAX (sizes 4 to 5)
Page 16
ECOMAX · Edition 10.17 16
ECOMAX..C 0 – 3
ECOMAX..C 4 – 5
ECOMAX..M 1 – 3
ECOMAX..M 4 – 5
Structure
3.5 Version overview
Burner Size Gas insert Air guide tube
ECOMAX..C
0– 3 With mixing funnel
Ceramic,
with integrated
combustion chamber
4– 5
With swirl plate and
ceramic combustion
chamber
Ceramic
ECOMAX..M ECOMAX..P ECOMAX..F
1– 3
With mixing funnel
and ceramic
combustion chamber
Metallic
4– 6
With swirl plate and
ceramic combustion
chamber
Metallic
Page 17
ECOMAX · Edition 10.17 17
Function
4 Function
Recuperator
Combustion chamber
Air guide tube
Radiant tube or
flue gas guide tube
Flue gas
Combustion gas
Combustion air
Housing
Gas insert
The self-recuperative burner ECOMAX uses the heat
from the flue gases to preheat the combustion air. The
heat exchanger (recuperator) required for this is part of
the burner.
After entering the gap between the air guide tube and
the recuperator, the combustion air flows towards the
tip of the burner (blue arrows). Some of this air is fed
into the inside of the burner, where it is combusted in
the first combustion stage.
The rest of the combustion air flows out through the
gap between the combustion chamber and the recu­perator head at high speed before combustion takes place in the second combustion stage here (violet ar­rows). This process means that fewer pollutant emis­sions are produced. The hot flue gases, flowing in the opposite direction, leave the furnace chamber on the outside of the recuperator (red arrows). Heat is exchanged between the hot flue gases and the cold combustion air through the recuperator wall.
Page 18
ECOMAX · Edition 10.17 18
Function
Influence of the furnace temperature
The higher the furnace temperature, the greater the
pressure loss in combustion air and flue gas in the re-
cuperator.
When the furnace temperature is increased (at a
constant air supply pressure), the air mass flow rate
(= standard air flow rate) drops while the gas flow rate
remains virtually unchanged. In a system with air/gas
ratio control or without pneumatic air/gas ratio control,
temperature-dependent pressure losses in the burner
are not compensated for. The air index lambda drops
with increasing furnace temperature.
In direct heating systems with flue gas eductor EJEK, the quantity of flue gas extracted from the furnace chamber via the burner decreases as the furnace tem­perature increases. If flue gas extraction at maximum furnace temperature is 80–90%, negative furnace pressure is generally avoided even if the furnace tem­perature is reduced by 400–500°C.
Ignition and flame control
The burner is directly ignited.
Ignition and flame control are provided by a combined spark electrode/ame rod (single-electrode operation). Flame control with UV sensor is required if a furnace temperature of 1150°C (2102°F) for direct heating or
1050°C (1922°F) for indirect heating is exceeded.
Recuperator
Combustion chamber
Air guide tube
Radiant tube or
flue gas guide tube
Flue gas
Combustion gas
Combustion air
Housing
Gas insert
Page 19
ECOMAX · Edition 10.17 19
Selection
5 Selection
5.1 Burner type
Selection is dependent on the type of heating and
the furnace temperature. Details on selection, see
page 31 (Heating system design) for direct heat-
ing or page 48 (Heating system design) for indirect
heating.
Burner Max. flue gas temperature at recuperator inlet
[°C] [°F]
ECOMAX..C 1250 2282 ECOMAX..M
ECOMAX..P
1150 2102
ECOMAX..F 1050 1922
5.2 Burner size
Burner
Size
Capacity
1)
Recuperator
kW
2)
103 BTU/h
3)
C M P F
ECOMA X 0 25 95
ECOMA X 1 36 136
ECOMA X 2 60 227
ECOMA X 3 100 378
ECOMA X 4 180 681
ECOMA X 5 250 945
ECOMA X 6 500 1890
= available
1)
For operation with natural gas. For operation with coke oven gas,
the capacity is approx. 80%, for operation with LCV gas, approx. 65%.
2)
Capacities in kW refer to the lower calorific value Hu.
3)
Capacities in BTU/h refer to the upper calorific value Ho.
When using the burner in geodetic ranges over 500 m above MSL, the possible capacity is reduced due to a decrease in the density of gas and air. Guide value: reduction of 5% per 1000 m above MSL, more details on request.
Page 20
ECOMAX · Edition 10.17 20
SelectionSelection
5.3 Burner length
The recuperator length G should be selected so that the
burner is flush with the inside edge of the furnace lining
(S1 = 0 ± 20 mm).
S1
G
S1
G
When using P radiant tubes, the recuperator head should be positioned on the centre line of the radiant tube (S1 = 0 ± 20 mm).
S1
G
S1
G
Page 21
ECOMAX · Edition 10.17 21
SelectionSelection
5.4 Burner head
5.4.1 Use
The burner ECOMAX can be equipped with 2 different
burner heads. Stage combustion is standard. For some
burner variants, a menox version is also possible, which
allows for switchover to menox® low NOX mode with flameless combustion when the furnace temperature
exceeds 850°C in a direct heating system.
Use Burner head code letter
Standard flame mode S
menox
®
low NOX mode
1)
M
1)
menox® low NOX mode on request.
5.4.2 Gas type
Gas type Code letter Caloric value range
Density ρ
kWh/m
3
(n)
2)
BTU/scf
3)
kg/m3(n) lb/scf
Natural gas L and H quality B 8– 12 810– 1215 0.7– 0.9 0.041– 0.053 Propane, propane/butane, butane G 25– 35 2560– 3474 2.0– 2.7 0.118– 0.159 Coke oven gas, town gas D 4– 5 421– 503 0.4– 0.6 0.024– 0.035 Low calorific value gas L 1.7
1)
–3 161– 290 0.9– 1.15 0.053– 0.068
1)
Calorific value range < 1.7 on request.
2)
Calorific value ranges in kWh/m3 refer to the
lower calorific value Hu.
3)
Calorific value ranges in BTU/SCF refer to the
upper calorific value Ho.
Page 22
ECOMAX · Edition 10.17 22
Selection
5.5 Type of heating
The ECOMAX is supplied with an integrated orice on
the gas and air connections.
The gas orifices depend on the gas type, the air orices
on the type of control and the system conguration.
Type of heating Code letter Explanation
Direct heating with eductor
/D
Air orice adapted to an air
pressure of 65 mbar
(= EJEK motive air pressure)
Indirect heating without an eductor
/R
Air orice adapted to an air
pressure of 50 60 mbar
Page 23
ECOMAX · Edition 10.17 23
Selection
5.6 Connection for additional furnace
cooling
The air volume supplied to the burner in cooling mode
can be increased using an optional intermediate flange
with an additional cooling air connection on the burner ECOMAX.
The air supplied via the additional air connection flows
in the centre of the burner inside the air guide tube. The
air volume is twice the standard combustion air volume.
5.7 Electrode made of Kanthal APM
Burners ECOMAX..M and ECOMAX..P can be equipped with a bend-resistant electrode made of Kanthal APM as an option. This is recommend for direct heating as of 1050°C and indirect heating as of 950°C, see page 38 (Flame control).
On ECOMA X..C, the Kanthal electrode is standard.
Page 24
ECOMAX · Edition 10.17 24
Selection
5.8 Selection table
5.8.1 ECOMAX..C
395 475 545 556 593 613 617 636 641 681 689 S B D G L1)/D /R (1–99) A–E – K T
ECOMA X 0C
  
ECOMA X 1C
  
ECOMAX 2C
  
ECOMA X 3C
  
ECOMA X 4C
  
ECOMAX 5C
  
1)
On request.
ECOMA X..C is supplied with Kanthal electrodes as standard.
= standard, = available
Order example
ECOMA X 1C545SB/R(31)B
5.8.2 ECOMA X..M
545 595 645 695 S M B D G L1)/D /R (1–99) A–E K A T
ECOMAX 1M
ECOMAX 2M
ECOMA X 3M
ECOMAX 4M
ECOMAX 5M
ECOMA X 6M
1)
On request.
= standard, = available
Order example
ECOMA X 3M545SB/D(34)B
Page 25
ECOMAX · Edition 10.17 25
Selection
5.8.3 ECOMAX..P
645 695 S B D G L
1)
/R (1–99) A–E K T
ECOMAX 2P
ECOMA X 3P
ECOMAX 4P
1)
On request.
= standard, = available
Order example
ECOMA X 3P695SB/R(34)B
5.8.4 ECOMAX..F
545 595 645 695 S B D G L
1)
/D /R (1–99) A–E K T
ECOMAX 1F
ECOMAX 2F
ECOMA X 3F
ECOMAX 4F
ECOMAX 5F
1)
On request.
= standard, = available
Order example
ECOMA X 3F545SB/D(34)B
Page 26
ECOMAX · Edition 10.17 26
Selection
5.8.5 Type code
Code Description
ECOMAX Self-recuperative burner for gas 0– 6 Burner size C
M P F
Ceramic burled tube recuperator made of SiSiC
Cast steel ribbed tube recuperator
Cast steel ribbed tube recuperator for P radiant tube
Flat tube recuperator, metallic E Special recuperator version 395– 695 Recuperator length in mm S
M
1)
Standard ame
menox® low NOX operation
B D G L
1)
Gas type2):
natural gas
coke oven gas
LPG
LCV gas
/D /R /V /E /nnn­/N
For direct heating with eductor
For radiant tube heating without eductor
For radiant tube heating with VAH
Burner with customized ori ces
Burner construction stage X for nnn kW
Burner without ori ces (1–99) Burner head identi er X, A, B, … Construction stage The following features differ from the standard version:
K
Additional cooling air connection for increased furnace
cooling A Electrode made of Kanthal APM T NPT connections S SICAFLEX spacer W Air connection without intermediate ange Z Special version
1)
On request.
2)
Other t ypes of gas on request.
Page 27
ECOMAX · Edition 10.17 27
Selection
5.9 Selection table for flue gas eductor EJEK
Axis spacing Kxxx* Height Tzzz* H V 3* * 9** F.. R.. AGK HT*** A B S
EJEK 0 - K269
- M625
EJEK 1 - K269
- M625
EJEK 2 - K285
- M540
EJEK 3 - K292
- M620
EJEK 4 - K345
- M920
EJEK 5 - K345
- M1165
EJEK 6 - K530
- M1618
* Special dimensions on request. * Only relevant for special dimension Tzzz. *** HT version for ECOMAX..C.
= standard, = available
Order example
EJEK 4K345M920AGKHTAS
Page 28
ECOMAX · Edition 10.17 28
Selection
5.9.1 Type code
Code Description
EJEK Flue gas eductor 0– 6 Size for ECOMAX 1 – 6 Kxxx Axis spacing K in mm Myyy Height M in mm Tzzz* Distance T in mm
H V
Burner installation position:
horizontal
vertical
3 9
Installation on the burner**:
right-hand side
left-hand side
F5 to F15 R5 to R15
Eductor angle in °:
pointing towards furnace
pointing away from furnace AGK With fl ue gas valve HT*** High temperature version A
B
Construction stage
S Standard dimension
* If “none”, this letter is omitted. ** Only required for special dimension Tzzz. *** HT version for ECOMA X..C.
MKM
KT
M
Page 29
ECOMAX · Edition 10.17 29
Selection
5.10 Selection table forue gas connector FLUP
32 50 65 100 D F Kxxx Installation height Myyy* Tzzz* H** V** 0** 3** 9** C A HT B S
FLUP 0
-M230
FLUP 1–2
-M331
FLUP 3
-M353
FLUP 4–5
-M399
* Special dimensions on request. ** Only relevant for special dimensions K xxx and/or Tzzz.
= standard, = available
Order example
FLUP 365DM3530S
Page 30
ECOMAX · Edition 10.17 30
Selection
5.10.1 Type code
Code Description
FLUP Flue gas connector 0
1/2 3 4/5
For ECOMAX 0–5
32 to 100 Nominal size D
F
Pipe connector
Flange to ISO 7005 Kxxx Axis spacing K in mm Myyy Installation height M in mm Tzzz* Distance T in mm
H V
Burner installation position:
horizontal
vertical
0 3 9
Installation on the burner**:
top
right-hand side
left-hand side
C A
Measuring port with sealing clip
Threaded pressure tap with cap HT High temperature version A
B
Construction stage
S Standard dimension
* If “none”, this letter is omitted. ** Only required for special dimension Tzzz.
DN
K
M
M
DN
T
DN
M
Page 31
ECOMAX · Edition 10.17 31
Project planning information for direct heating
6 Project planning information for direct heating
6.1 Heating system design
Selection of the burner type is dependent on the fur- nace temperature.
Burner
Recommended
range of use
Max. flue gas temperature at
recuperator inlet
[°C] [°F] [°C] [°F]
ECOMAX..C up to 1250 up to 2282 1250 2282 ECOMAX..M up to 1100 up to 2012 1150 2102 ECOMAX..F up to 1000 up to 1832 1050 1922
Burners ECOMAX..M (sizes 1 to 5) and ECOMAX..F can
be used for furnace temperatures up to the max. appli- cation temperature if it is ensured that the burner head cannot overheat, e.g. due to burners positioned oppo- site the ECOMAX or non representative temperature measurements, see also page 37 (Furnace tempera- ture measurement).
Selection of the burner size is dependent on the net heat output. From this, the required burner capacity is calculated using the firing efciency value.
Net heat output [kW]
= Burner capacity [kW]
Firing efficiency η
400 500 600 700 800 900 1000 1100
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
1200
1300
1400
F
M
C
Firing efficiency η
Flue gas temperature on recuperator inlet [°C]
Cold air burner
Details on heating system design on request.
Page 32
ECOMAX · Edition 10.17 32
Project planning information for direct heating
6.2 Flue gas guide tube FGT set
The furnace flue gases are routed by the flue gas guide
tube through the furnace lining via the recuperator. The
FGT set must be ordered separately and is not included
in the burner delivery, see page 64 (Flue gas guide tube FGT Set..D).
The flange thickness P1 of the flue gas guide tube is 15 mm. Plan the length of the furnace extension M1 so
that the front edge of the recuperator is flush with the inside edge of the furnace lining (S1 = 0 ± 20 mm).
A
G
P1
S1
FGT-Set
Burner FGT OD A in mm
ECOMA X 0C 142 ECOMA X 1C 180 ECOMAX 2C 200 ECOMA X 3C 236 ECOMA X 4C 300 ECOMAX 5C 336
Force must not be applied to the flue gas guide tube by the furnace lining.
When installing the FGT, the tube must be wrapped in a ceramic fibre blanket so as to ensure that no hot fur­nace atmosphere may reach the furnace wall or furnace extension. The installation opening in the furnace wall must thus be larger than the FGT outside diameter A, leaving an annular gap corresponding to the size of the
fibre blanket, e.g. 25 mm.
S1
A
P1
G
M1
FGT-Set
Burner FGT OD A in mm
ECOMAX 1M/ECOMAX 1F 133 ECOMAX 2M/ECOMAX 2F 156 ECOMA X 3M/ECOMA X 3F 193 ECOMAX 4M/ECOMAX 4F 254 ECOMAX 5M/ECOMAX 5F 287 ECOMA X 6M/ECOMA X 6F 390
Page 33
ECOMAX · Edition 10.17 33
Project planning information for direct heating
6.3 Flue gas eductor EJEK
Flue gas eductor EJEK is available in 2 versions. The
standard version EJEK is used in conjunction with
ECOMAX..M and ECOMAX..F. The high temperature
version EJEK..HT is intended for use in conjunction with ECOMAX..C.
The eductors serve to extract the flue gas via the burner
ECOMAX and cannot be used for furnace pressure con-
trol. We recommend discharging 10 to 20% of the flue gases via an additional flue gas opening on the furnace
fitted with a furnace pressure control system.
With 80 to 90% flue gas extraction at max. furnace temperature, a positive furnace pressure can generally be maintained even at low furnace temperatures. In the case of heavily leaking furnaces, flue gas extraction must be reduced, where necessary, to avoid pulling in cold air due to negative pressure in the furnace cham- ber.
p
FG
p
atm
p
FG
0
p
FG
The motive air is set at the eductor by measuring the negative ue gas pressure pFG between the burner and eductor.
If the furnace temperature is too high, damage can oc­cur to burners which are switched off due to the flow of hot flue gases over them.
For direct heating, eductors EJEK..AGK with mechani­cal flue gas valve (AGK) are recommended so as to avoid gas creepage while the burner is switched off.
Page 34
ECOMAX · Edition 10.17 34
Project planning information for direct heating
6.4 Furnace flue gas system
A flue gas system must be fitted on the furnace as a
means of guiding the flue gas to the chimney. In the
flue gas system there should be a low negative pressure
thanks to the draught of the chimney or an exhaust fan.
The flue gas system on the furnace should be fitted
flush with the eductor (± 10 mm). The diameter of the flue gas pipe on the furnace should be twice the educ-
tor diameter P. If the diameter is too small, even with the EJEK..AGK with ue gas valve there is the danger of hot flue gases creeping through the burner when it is switched off.
The branch lines from the furnace flue gas manifold to
the individual burners should be designed such that condensate cannot seep upstream into the burner.
P
2P
0 mm (±10 mm)
1,5P
P
2P
0 mm
(±10 mm)
P [mm]
ECOMA X 0 EJEK 0(B) 43 ECOMA X 1 EJEK 1 43 ECOMA X 2 EJEK 2(A) 83 ECOMA X 3 EJEK 3(A) 98 ECOMA X 4 EJEK 4(A) 128 ECOMA X 5 EJEK 5(A) 153 ECOMA X 6 EJEK 6(A) 215
Page 35
ECOMAX · Edition 10.17 35
Project planning information for direct heating
6.5 Installation
6.5.1 Installation position
15°
90°
The burner ECOMAX can be installed in any position
between 0° (horizontal) and 90° (vertical from top to bottom). The ECOMAX may be oriented upwards at an angle of max. 15° from the horizontal.
Eductor EJEK installation position:
vertical, max. angle 10°.
If the burner is installed at an angle of more than 10°
from the vertical or horizontal, a special version of flue
gas eductor EJEK is required. This is available on re- quest.
6.5.2 Tangential or angled burner installation
If the burner is installed tangentially or at an angle, an opening should be provided in the furnace lining to ensure unobstructed flue gas extraction. The choice of furnace lining in this area should take account of the burners very high outlet velocity. In addition, reflection from the furnace wall to the burner must be considered.
B
1,5 x B
Page 36
ECOMAX · Edition 10.17 36
Project planning information for direct heating
6.5.3 Clearances
Y
X
X
X
2
X
X
RZ
Allow for adequate clearance from the charge and the
interior furnace wall so as to ensure complete combus- tion and avoid local overheating. Due to the high air preheat temperature of the ECOMAX, the flame tem- perature is also higher than usual.
Z
2
Z
X
The minimum lateral clearance between two burners
or between a burner and the furnace side wall is de- termined by the geometric dimensions of the burners including the eductor.
In addition, it must be noted that burners facing each other can cause overheating of the recuperator heads.
Flame mode
Burner
Reaction zone RZ (mm)
Clearance (mm)
X Z
ECOMA X 0 500 130 270 ECOMA X 1 700 155 270 ECOMA X 2 900 200 285 ECOMA X 3 1200 250 300 ECOMA X 4 1600 340 350 ECOMA X 5 1800 400 400 ECOMA X 6 2200 570 570
For menox® low NOX mode, a sufciently large reaction
zone (RZ) and undisturbed recirculation of the flue gas
into the reaction zone are required. Operation in very small combustion chambers leads to an increase in NOX emissions.
menox
®
low NOX mode
Burner
Reaction zone RZ (mm)
Clearance (mm)
X Y Z
ECOMA X 3M 2100 300 320 300 ECOMAX 4M 2800 360 400 360 ECOMAX 5M 3300 400 480 400
Page 37
ECOMAX · Edition 10.17 37
Project planning information for direct heating
6.5.4 Furnace temperature measurement
Measurement of the furnace temperature must be
representative for the flue gas temperature in the ex- traction zone on the burner. If measurement is not rep- resentative, this will involve a risk of overheating of the recuperator head.
6.5.5 Heat guard
During operation, the burner body and eductor or flue
gas connector can reach surface temperatures of over 80°C. Do not insulate the burner, eductor and flue gas connector to prevent material overheating.
We recommend that warning signs and a contact guard be fitted, for example made of perforated sheet metal.
Page 38
ECOMAX · Edition 10.17 38
Project planning information for direct heating
6.6 Flame control
Burners ECOMAX are equipped with a combined spark
electrode/flame rod. For direct heating, ionization con- trol is possible up to a temperature of 1150°C (single- electrode operation). In this respect, it must be noted that the burner control unit BCU must feature at least
firmware version FW 16xx, see page 39 (Burner con-
trol units and ignition transformers).
Flame control with UV sensor is only necessary if fur-
nace temperatures of 1050°C for direct heating or
1150 °C for indirect heating are exceeded.
We also recommend using bend-resistant Kanthal electrodes for ignition on ECOMA X..M as of a furnace temperature of more than 1050°C. These are fitted as standard on ECOMAX..C.
We recommend the UV sensor UVS 10D1 with inte­grated purge air connection (Order No. 84315202) for UV control.
For ECOMA X 0, the UV sensor UVS 10L1 (Order No. 84315203) with lens is required for UV control. For burners ECOMAX 1 –6 with a burner length of more than 545 mm, the UV sensor UVD 10L1 with lens is also required for UV control.
An adapter set is required for connection to the UVS 10,
see page 63 (UV adapter set).
Page 39
ECOMAX · Edition 10.17 39
Project planning information for direct heating
6.7 Burner control units and ignition
transformers
ECOMAX burners with burner control unit BCU
ECOMAX burners are designed for On/Off control.
We recommend burner control unit BCU 460..L or
BCU 465..L. In order to be able to carry out ionization
control up to 1150°C, the burner control unit must be equipped with firmware FW 16xx or higher.
For burners ECOMAX..K with additional cooling air connection, we recommend using burner control unit BCU..C with additional circuit board for signal distribu­tion.
For ignition, the ECOMAX burners require an ignition transformer with 7.5 kV high voltage and an output cur­rent of 20 mA. An appropriate ignition transformer is already integrated in burner control units BCU 460..8 and BCU 465..8.
For further information on burner control units and ig­nition transformers, see www.docuthek.com, Technical Information BCU 460, 465.
Page 40
ECOMAX · Edition 10.17 40
Project planning information for direct heating
6.7. 1 Burner control unit congurations
Description Conguration D1 Conguration D2 Conguration D3 Configuration D4
Flame control Ionization UVS 10 Ionization U VS 10 Pneumatic air/gas ratio control VAH/ VAG VAH/VAG None/VAH/VAG None/VAH/VAG Air flow monitoring
Differential pressure switch PDZ Differential pressure switch PDZ
Hardware BCU 460..L BCU 460..L BCU 465 BCU 465
Ignition transformer 8 = TZI 7,520/33 8 = TZI 7,520/33 8 = TZI 7,520/33 8 = TZI 7,520/33 Rewiring for electrode operation 1 electrode 2 electrodes 1 electrode 2 electrodes
Description Parameter Conguration D1 Conguration D2 Conguration D3 Configuration D4
Switch-off threshold of theame amplier 04
4 μA 4 μA 4 μA 4 μA
Air flow monitoring during purging 06 N /A N/A 1 1 Air flow monitoring during operation 07 N/A N/A 1 1 Delayed air flow monitoring 08 N/A N /A 1 1 Safety time during operation t
SB
for V1 and V2 14 1 1 1 1
Minimum burner on time t
B
20 8 8 8 8
Minimum burner pause time t
BP
21 4 4 4 4
Safety time on start-up t
SA
22 3 3 3 3 Air valve control 30 1 1 1 1 Air valve can be activated externally on start-up 31 1 1 1 1 Low fire over-run time t
KN
after a controlled shut-down 36 N/A N/A 0 0
Pre-ventilation time t
VL
before start-up 37 N/A N/A 0 0
Post-ventilation time t
NL
after a controlled shut-down 38 N /A N/A 0 0 Pre-ventilation time after safety shut-down 39 N/A N/A 0 0 Pre-ventilation for restart/start-up attempts 40 N/A N/A 0 0 Pre-ventilation after reset 41 N/A N/A 0 0
BCU for direct heating Conguration D1 Conguration D2 Conguration D3 Configuration D4
230 V 88613276 88614259 88614263 88614267 230 V, Profibus 88611901 88613865 88614264 88614268 230 V, HT operation 88614257 88614260 88614265 88614269 230 V, HT operation, Profibus 88611887 88611883 8 861426 6 88614270
Page 41
ECOMAX · Edition 10.17 41
Project planning information for direct heating
6.8 Gas connection
6.8.1 Selecting components
To ensure a safe burner start, use a pneumatic air/gas
ratio controller together with a slow opening air valve. If there is no pneumatic air/gas ratio control system, use a slow opening gas valve and a quick opening air valve.
The following gas valves are recommended for natural
gas:
Burner Flow rate control
Air/gas ratio
control
No pneumatic air/
gas ratio control
system
ECOMA X 0
VAS 115..N + VAH 115..B +
VMV 115
VAS 115..N + VAG 115..B +
VMV 115
VG 15..N + VG 15..L +
VMV 115
ECOMA X 1
VAS 115..N + VAH 115..B +
VMV 115
VAS 115..N + VAG 115..B +
VMV 115
VG 15..N + VG 15..L +
VMV 115
ECOMA X 2
VAS 115..N +
VAH 115..B +
VMV 115
VAS 115..N + VAG 115..B +
VMV 115
VG 15..N + VG 15..L +
VMV 115
ECOMA X 3
VAS 115..N +
VAH 115..B +
VMV 115
VAS 115..N + VAG 115..B +
VMV 115
VG 15..N + VG 15..L +
VMV 115
ECOMA X 4
VAS 120..N +
VAH 120..A +
VMV 120
VAS 120..N + VAG 120..B +
VMV 120
VAS 120..N + VAS 120..L +
VMV 120
ECOMA X 5
VAS 125..N +
VAH 125..A +
VMV 125
VAS 125..N + VAG 125..B +
VMV 125
VAS 125..N + VAS 125..L +
VMV 125
ECOMAX 6*
VAS 240..N + VAH 240..A +
VMV 240
VAS 240..N +
VAG 240 +
VMV 240
VAS 240..N +
VAS 240..L +
VMV 240
* As of 360 kW, ignition with a start rate of < 33% is required
(pursuant to EN 746-2 and ISO 13577-2); a pneumatic ratio control system and a BVH with IC 40 must be used for this.
A bellows unit EKO should be provided between the
burner and controls to prevent external force being ap­plied to the burner.
A connection set with 6 x 1 compression fittings
is available to connect the VAH control line, see page 63 (VAH connection set). The set is installed on the burner before delivery.
6.8.2 Gas pressure
The required gas pressure depends on the burner size,
the gas type and the system conguration.
Gas supply line pressure*
Gas pressure
upstream of
burner
Natural gas H
Natural gas L,
LPG
Flow rate control 50 –65 mbar 100 mbar 120 mbar
Air/gas ratio control**
50 –65 mbar 100 mbar 120 mbar
No pneumatic air/ gas ratio control system
50 –65 mbar 80 mbar 100 mbar
* If a stainless steel flexible tube ES is used instead of the
stainless steel bellows unit EKO, the higher pressure loss must be taken into account.
** Gas pressure in the supply line min. 10 – 20 mbar greater than
the air pressure in the supply line.
Page 42
ECOMAX · Edition 10.17 42
Project planning information for direct heating
6.8.3 Operation with LPG
GEH
For operation with LPG, it is essential to cool the gas
lance via a central air lance in order to prevent the LPG
from cracking in the gas lance and soot formation dur-
ing combustion.
GEH
The central air volume is approx. 3 to 5% of the com-
bustion air volume and must also flow while the burner is switched off.
Open the adjuster in the central air lance fully. On the ECOMAX 1, the adjuster must be restricted to 45° or 50%
.
If high temperature operation without flame control using ionization or a UV sensor is intended for LPG, air
ow monitoring using an ECO air flow detector set must
be provided to prevent backow of the central air into the gas line or of gas into the air line in the event of the
ue gas route being blocked.
Page 43
ECOMAX · Edition 10.17 43
Project planning information for direct heating
6.9 Air connection
6.9.1 Selecting components
In the case of a pneumatic air/gas ratio control system, slow opening air valves or buttery valves with solenoid ac- tuator are required. If the system does not include a pneu- matic air/gas ratio control system, quick opening air valves or butterfly valves with solenoid actuator are to be used.
The following air control valves are recommended for air:
Burner
Flow rate control or air/gas ratio control
No pneumatic air/gas
ratio control system
ECOMA X 0 VR 40..L VR 40..N ECOMA X 1 VR 50..L VR 50..N ECOMA X 2 VR 65..L VR 65..N ECOMA X 3 BVHM 65 + MB 7..L BVHM 65 + MB 7..N ECOMA X 4 BVHM 80 + MB 7..L BVHM 80 + MB 7..N ECOMA X 5 BVHM 80 + MB 7..L BVHM 80 + MB 7..N ECOMAX 6* BVHM 100 + MB 7..L BVHM 100 + MB 7..N
* As of 360 kW, ignition with a start rate of < 33% is required
(pursuant to EN 746-2 and ISO 13577-2); a pneumatic ratio control system and a BVH with IC 40 must be used for this.
VR LEH
LEH
ECOMAX 0 ECOMAX
1
ECOMAX 2
MB
7
+
BVHM
LEH
LEH
ECOMAX 3
ECOMAX 6
6.9.2 Air pressure
The motive air setting for eductor EJEK is critical when
designing the air supply. The required pressure depends on the burner capacity, the flue gas extraction via the burner and the furnace temperature:
Motive air pressure
upstream of
eductor*
Air supply
line pressure*
ECOMA X 0 and 1 at a furnace temperature of 1000°C
approx. 100 mbar approx. 115 mbar
ECOMA X 2C – 5C with EJEK ..HTA (construction stage A) at a furnace temperature of 1250°C
approx. 65 mbar approx. 80 mbar
ECOMA X 2M – 6M with EJEK ..A (construction stage A) at a furnace temperature of 1100°C
approx. 65 mbar approx. 80 mbar
* The air pressures apply for burner ratings at the specified
furnace temperatures and 80% flue gas extraction.
Flow rate curves are available in the Docuthek for EJEK construction stage A to allow precise dimensioning.
To ensure accurate measurements of the pressure dif-
ferential on the integrated orice, flow to the orifice must not be disturbed. We recommend using the con­nection set for air, which guarantees correct measure­ment at the measuring orice, see page 62 (Air con­nection set). The attachment of a coupling, a bellows unit or a pipe bend directly upstream of the orifice can cause turbulence in the gas flow resulting in the burner being incorrectly adjusted.
Page 44
ECOMAX · Edition 10.17 44
Project planning information for direct heating
6.10 Air flow monitoring
A system which includes air flow monitoring is recom-
mended to monitor pre-purge and as low air pressure protection (pursuant to EN 7462 and ISO 135772) if there is no pneumatic air/gas ratio control system. This is implemented using a differential pressure switch at the air connection together with a burner control unit
BCU 465. An air flow monitoring set is available for this
purpose as an accessory, see page 62 (Air flow de- tector set).
6.11 Purge air and cooling air
Purge air must be connected to the burner ECOMA X in
order to ensure safe ignition and monitoring. Otherwise, wet flue gas will enter the burner in the case of direct heating, due to the furnace pressure.
The required purge air volume is approx. 0.5 to 1.0%
of the air volume for rated capacity, or a minimum of
1 m
3
(n)
/h.
The purge air is connected to the gas connection flange
next to the electrode, or in the case of UV control to the purge air connection of the UV sensor. The purge air is tapped upstream of the air control valve so that the purge air continues to flow even if the burner is switched off.
In order to limit the volume of purge air, special nozzles can be used which are adjusted to the required air sup­ply pressure for the ECOMAX – see page 63 (Purge air/cooling air nozzles).
Burner
Nozzle for electrode
purge
Purge air nozzle on
UV sensor
ECOMA X 0
Nozzle electrode ECO 0
Rp 1/4 D = 2.5 /E
Nozzle UV ECO 03
Rp 1/4 D = 2.5 /B
ECOMA X 1–3
Nozzle electrode ECO 13
Rp 1/4 D = 2.5 /E
Nozzle UV ECO 03
Rp 1/4 D = 2.5 /B
ECOMA X 4–6
Nozzle electrode ECO 46
Rp 1/4 D = 4.0 /E
Nozzle UV ECO 46
Rp 1/4 D = 4.0 /B
At very high furnace temperatures, we recommend
cooling the burner head by selecting a larger nozzle or a supply line with a diameter of 8 mm without a nozzle.
Page 45
ECOMAX · Edition 10.17 45
Project planning information for direct heating
6.12 Condition on delivery
The position of the gas, air and flue gas connections
can be customized depending on how the burner is to be installed on the furnace. The connection positions are coded using the numbers 0, 3, 6 and 9.
Code Connection position
0 Top 3 Right-hand side 6 Bottom 9 Left-hand side
The codes relating to the positions of the connections
are specified in the following order: flue gas – air – gas.
Provided that there are no specications, the burners
are supplied as follows:
ECOMAX../D for direct heating with connector posi-
tion 366, i.e. flue gas connection for eductor installa- tion on the right-hand side and gas and air connections at the bottom.
0
3
6
9
The FGT Set..D for direct heating is installed on the
burner at the factory, provided that it is ordered at the
same time as the burner. This also applies to all add-on components with the marking /E, such as the air flow detector set, UV adapter set, purge air nozzle, inlet sec­tion for gas and air, see page 62 (Accessories).
6.13 Cooling with ECOMAX
Extraction of the flue gases via the burner and thus the preheating of the combustion air can be switched off to ensure controlled cooling of the furnace. Install sepa­rate valves for combustion air and motive air instead of an air valve for this. In this case, a separate flue gas route must be opened on the furnace, via which the cooling air can be discharged from the furnace.
Page 46
ECOMAX · Edition 10.17 46
Project planning information for direct heating
6.14 Emissions
CO and NOX values depend on the furnace tempera-
ture, air preheat temperature, burner type and burner settings (NOX values on request).
If operated with LPG, NO
X
values are approx. 25%
higher.
600 700 800 900 1000 1100 1200 1300
0
100
200
300
400
500
600
ECOMAX..C
ECOMAX..M
Flue gas temperature at recuperator inlet [°C]
NO
x
[mg/m
3
ref. 5 % O
2
]
NOX values in the diagram apply to natural gas.
6.15 Build up of noise
The sound level of a naked flame may be significantly
more than 90 dB(A) due to the high flame velocity. In the case of fitted burners, the sound level of the single burner which can be measured outside the furnace is usually between 75 and 82 dB(A).
In a furnace system, the value which can be measured depends on the capacity, excess air volume, flue gas extraction and flue gas temperature of the single burn­ers as well as the burner arrangement and ambient inuences.
Page 47
ECOMAX · Edition 10.17 47
Project planning information for direct heating
6.16 Process boundary conditions
In direct heating systems, the flue gases are routed out of the furnace chamber via the burner. Impurities
from the process can affect burner operation. Deposits
of dust or components from the material to be heated which turn to gas (e.g. molybdenum) can accumulate on the recuperator. This means that the volume of flue gas routed via the recuperator falls and thus the burner is less efficient. Furthermore, this can also lead to in- creased furnace pressure and damage to the furnace and burner. In this case, increased maintenance and shorter cleaning intervals are required.
Other impurities, such as alkalis formed during the
heating of cast parts or from cooling and washing liq- uids, can cause chemical attacks on the material. This reduces the service life of the recuperator and the flue gas guide tube. We therefore advise against use in forg- ing and heating furnaces, in which raw materials are heated. We also advise against use in aluminium smelt- ing furnaces due to the dusty furnace atmosphere, the danger of liquid metal spillings and possible chemical attacks.
Avoid sub-stoichiometric burner operation. A reducing
atmosphere can lead to damage to the burner insula- tion on the flue gas side, the metallic recuperator and
flue gas guide tube, and the vacuum-formed parts of
the flue gas guide tube for ECOMAX..C.
6.17 Resistance of SiSiC
The ceramic recuperator of the ECOMAX..C consists of
reaction-bound silicon carbide (SiSiC), infiltrated with metallic silicon. During the manufacturing process, a protective layer made of SiO2 is formed on the surface, which ensures good chemical resistance.
When installing the burners, it must be ensured that the protective layer on the ceramic surface is not dam­aged.
The burners should be adjusted so that an excess air
value of 1 – 5% O
2
in the flue gas is maintained in order to preserve the protective layer. In the case of sub­stoichiometric burner operation (concentration of CO
> 1000 ppm), white deposits can build up on the SiSiC
over a long period of time. This reduces the service life of the ceramic material.
Impurities such as fluorine, chlorine and alkali com­pounds (e.g. with sodium or potassium) in the furnace atmosphere also lead to chemical attack and shorten the service life of the ceramic recuperator. We therefore advise against use in forging and heating furnaces, in which raw materials are heated. We also advise against use in aluminium smelting furnaces.
Page 48
ECOMAX · Edition 10.17 48
Project planning information for indirect heating
7 Project planning information for indirect heating
7.1 Heating system design
When designing a radiant tube heating system, it must be ensured that the energy can be transferred to the
furnace chamber via the surface of the radiant tube
to avoid exceeding the maximum permissible flue gas temperature at the recuperator inlet of the burner.
It must also be ensured that the permitted material temperature of the radiant tube and, in the case of sin- gle ended radiant tubes, of the flame tube used is not exceeded.
Burner Max. flue gas temperature at recuperator inlet
[°C] [°F]
ECOMAX..C 1250 2282 ECOMAX..M/ECOMAX..P 1150 2102 ECOMAX..F 1050 1922
The possible radiation output in the furnace depends
on the furnace temperature and the surface of the radi- ant tube as well as the material that the radiant tube and burner are made of.
The burner capacity also depends on how efcient the
burner is.
The heat exchange must be determined to ensure safe
design of a radiant tube heating system. To this end, please consult a member of the sales team.
700 800 900 1000 1100 1200
0
60
40
20
50
30
10
90
70
80
100
0
60
40
20
50
30
10
90
70
80
100
1300
Furnace temperature [°C]
Max. radiation output in kW/m²
SER-C with ECOMAX..C SER-M with ECOMAX..M
Spec. burner capacity in kW/m²
Depending on the system conguration, it may be nec­essary to reduce the power input on the basis of the furnace temperature, e.g. by reducing the duty cycle. In this case, the combustion time should not exceed
2 minutes to avoid thermal overload of the radiant tube
and burner.
100 %
Power input
Furnace temperature
Page 49
ECOMAX · Edition 10.17 49
Project planning information for indirect heating
7. 2 Radiant tubes
For ECOMA X..C
Burners ECOMAX..C are intended for use with ceramic
radiant tubes SERC.
See Technical Information SERC.
Standard combinations:
Radiant tube Burner Segmentedame tube
SERC 100/088 ECOMA X 0C SICAFLEX 100/088/084 SE RC 142 /128 EC OMAX 1C SICAFLE X 142/127/123 SE RC 162/14 8 ECOMA X 2C SI CA FLEX 162 /147/143 SERC 202/188 ECOMAX 3C SICAFLE X 202/186/182
In special cases, a ceramic burner ECOMAX..C can be installed in a metallic radiant tube. Here, external forces on the ceramic burner due to the radiant tube being de-
formed must be excluded, however.
For ECOMAX..M
Metallic radiant tubes are available in a variety of di­mensions in either centrifugal casting or in welded form. The efciency of the burner ECOMAX..M is deter­mined by the inside diameter d
i
of the radiant tubes in the vicinity of the burner. The following dimensions are recommended:
Burner
Min.
radiant tube inside
diameter d
i
[mm]
Radiant tube inside
diameter d
i
as of which a
flue gas guide tube FGT
set is recommended
[mm]
ECOMAX 1M 128 140 ECOMAX 2M 147 164 ECOMA X 3M 185 202 ECOMAX 4M 248 266 ECOMAX 5M 280 298
If the inside diameter of the radiant tube is considerably larger than that of the burner, a flue gas guide tube FGT set should also be used.
Depending on the geometry, additional adapter flanges may be required for radiant tubes.
Page 50
ECOMAX · Edition 10.17 50
Project planning information for indirect heating
7.3 Flue gas channelling
A flue gas connector FLUP, which is to be ordered sepa-
rately, is available as standard to channel flue gas in an indirect heating system. In special cases, an educ- tor EJEK can also be installed to channel flue gas. This also must be ordered separately.
Flue gas connector FLUP
SER-C
SICAFLEX
FLUP
ECOMAX..C
Flue gas connector FLUP serves to discharge the flue
gases into the furnace flue gas system and features an opening which is closed by a clip to connect flue gas analysis equipment.
Eductor EJEK
SER-M
EJEK
SICAFLEX
In indirect heating systems with metal radiant tubes, eductor EJEK can generate a negative pressure in the radiant tube. This prevents the inert gas atmosphere in the furnace being contaminated by flue gases from the burner in the event of leakage from the single ended radiant tube.
Page 51
ECOMAX · Edition 10.17 51
Project planning information for indirect heating
7.4 Furnace flue gas system
A flue gas system must be fitted on the furnace as a
means of guiding the flue gas to the chimney. In the
flue gas system there should be a low negative pressure
thanks to the draught of the chimney or an exhaust fan.
The branch lines from the furnace flue gas manifold to
the individual burners should be designed such that condensate cannot seep upstream into the burner.
The branch lines to the burner should stop 10 mm away
from the flue gas connector FLUP, or be fitted flush
with the eductor EJEK.
For indirect heating with flue gas monitoring kit DW and BCU 465, excessive negative pressure in the flue gas
system or an excessively narrow flue gas pipe diameter on the furnace can cause problems with setting the switching point of the pressure switch.
Q
1,5Q
10 mm ±5
1,5Q
2Q*
2Q*
Q
10 mm ±5
P
1,5P
0 mm
(±10 mm)
* With flue gas monitoring kit DW; without flue gas monitoring
kit DW: 1.5Q to 2Q.
FLUP dia. Q EJEK dia. P
ECOMA X 0 DN 32 43 ECOMA X 1 DN 50 43 ECOMA X 2 DN 50 83 ECOMA X 3 DN 65 98 ECOMA X 4 DN 100 128 ECOMA X 5 DN 100 153
In a closed flue gas system, a pressure regulator is to be fitted. The gas and air flow rates depend on the total pressure differential between the supply lines and the
ue gas system. If the pressure in the flue gas system uctuates, the burner capacity changes. In a system
without air/gas ratio control, the lambda may also change.
Page 52
ECOMAX · Edition 10.17 52
Project planning information for indirect heating
7.5 Installation
Installation of burners with FLUP in the horizontal posi- tion, in the vertical position with the firing end pointing downwards or at an angle with the firing end pointing downwards.
Allow for adequate clearance between the radiant tubes
and the furnace wall to avoid local overheating, see
Technical Information SERC.
Ensure that there is a recirculation gap D1 between burn-
er and flame tube, e.g. SICAFLEX, (30 mm for ECOMAX 0–3 or 50 mm for ECOMAX 4–5). The deector gap V1 should equal 0.5 to 1.5 times the radiant tube diameter X.
X
SICAFLEX
SER
D1 (ECOMAX 0–3 = 30 mm)
(ECOMAX 4–5 = 50 mm)
V1 = 0.7 × max. 1.5 × X for SER-C
0.5 × max. 1.5 × X
for SER-M
7.5.1 Heat guard
During operation, the burner body and flue gas con-
nector or eductor can reach surface temperatures of over 80°C. Do not insulate the burner, flue gas connec- tor and eductor to prevent material overheating.
We recommend that warning signs and a contact guard
be fitted, for example made of perforated sheet metal.
Page 53
ECOMAX · Edition 10.17 53
Project planning information for indirect heating
7.6 Flame control
Burners ECOMAX are equipped with a combined
spark electrode/flame rod. For indirect heating, ionization control is possible up to a furnace tempera- ture of approx. 1050°C (single-electrode operation). In this respect, it must be noted that the burner con- trol unit BCU must feature at least firmware version
FW 16xx, see page 54 (Burner control units and igni-
tion transformers).
Flame control with UV sensor is required if a furnace
temperature of 1050°C for indirect heating is ex- ceeded. We recommend using bend-resistant Kanthal electrodes for ignition on ECOMA X..M as of a furnace temperature of more than 950°C. These are fitted as standard on ECOMAX..C.
We recommend the UV sensor UVS 10D1 with inte­grated purge air connection (Order No. 84315202) for UV control.
For ECOMA X 0, the UV sensor UVS 10L1 (Order No. 84315203) with lens is required for UV control. For burners ECOMAX 1 –6 with a burner length of more than 545 mm, the UV sensor UVD 10L1 with lens is also required for UV control.
An adapter set is required for connection to the UVS 10,
see page 63 (UV adapter set).
Page 54
ECOMAX · Edition 10.17 54
Project planning information for indirect heating
7.7 Burner control units and ignition transformers
ECOMAX burners are designed for On/Off control.
We recommend burner control units BCU 465. In order to be able to carry out ionization control up to 1050°C, the burner control units must be equipped with firm- ware FW 16xx or higher.
Pre-ventilation should be performed after every safety
shut-down in order to purge the radiant tube (param- eters 39 and 40 of the BCU 465).
For burners ECOMAX..K with additional cooling air
connection, we recommend using burner control unit
BCU..C with additional circuit board for signal distribu-
tion.
For ignition, the ECOMAX burners require an ignition
transformer with 7.5 kV high voltage and an output cur- rent of 20 mA. An appropriate ignition transformer is already integrated in burner control units BCU 460..8 and BCU 465..8.
For further information on burner control units and ig-
nition transformers, see www.docuthek.com, Technical Information BCU 460, 465.
Page 55
ECOMAX · Edition 10.17 55
Project planning information for indirect heating
7.7. 1 Burner control unit congurations
Description Conguration R1 Conguration R2
Recuperator Metallic Ceramic Flame control Ionization UV S 10 Pneumatic air/gas ratio control None/VAG None/VAG Air flow monitoring Differential pressure switch PDZ Differential pressure switch PDZ
Hardware BCU 465..L BCU 465..L
Ignition transformer 8 = TZI 7,520/33 8 = TZI 7,520/33 Rewiring for electrode operation 1 electrode 2 electrodes
Description Parameter Conguration R1 Conguration R2
Switch-off threshold of theame amplier 04
4 μA 4 μA
Air flow monitoring during purging 06 1 1 Air flow monitoring during operation 07 1 1 Delayed air flow monitoring 08 1 1 Safety time during operation t
SB
for V1 and V2 14 1 1
Minimum burner on time t
B
20 8 8
Minimum burner pause time t
BP
21 4 4
Safety time on start-up t
SA
22 3 3 Air valve control 30 1 1 Air valve can be activated externally on start-up 31 1 1 Low fire over-run time t
KN
after a controlled shut-down 36 0 0
Pre-ventilation time t
VL
before start-up 37 0 0
Post-ventilation time t
NL
after a controlled shut-down 38 0 0 Pre-ventilation time after safety shut-down 39 7 7 Pre-ventilation for restart/start-up attempts 40 1 1 Pre-ventilation after reset 41 1 1
BCU for indirect heating Conguration R1 Conguration R2
230 V 88 614271 88614275 230 V, Profibus 88614272 88614276 230 V, HT operation 88614273 88614277 230 V, HT operation, Profibus 88 614274 88614278
Page 56
ECOMAX · Edition 10.17 56
Project planning information for indirect heating
7.8 Gas connection
7.8.1 Selecting components
For indirect heating, slow opening gas valves and quick
opening air control valves are to be used to ensure a safe burner start.
The following gas valves are recommended for natural
gas:
Burner
No pneumatic air/gas
ratio control system
Air/gas ratio control
ECOMA X 0
VG 15..N + VG 15..L +
VMV 115
VAG 115..B +
VG 15..L +
VMV 115
ECOMA X 1
VG 15..N + VG 15..L +
VMV 115
VAG 115..B +
VG 15..L +
VMV 115
ECOMA X 2
VG 15..N + VG 15..L +
VMV 115
VAG 115..B +
VG 15..L +
VMV 115
ECOMA X 3
VG 15..N + VG 15..L +
VMV 115
VAG 115..B +
VG 15..L +
VMV 115
ECOMA X 4
VAS 120..N + VAS 120..L +
VMV 120
VAG 120..B + VAS 120..L +
VMV 120
ECOMA X 5
VAS 125..N + VAS 125..L +
VMV 125
VAG 125..A + VAS 125..L +
VMV 125
A bellows unit EKO should be provided between the
burner and controls to prevent external force being ap- plied to the burner.
7.8.2 Gas pressure
The required gas pressure depends on the burner size,
the gas type and the system conguration.
Gas supply line pressure*
Gas pressure
upstream of
burner
Natural gas H
Natural gas L,
LPG
Air/gas ratio control 65–70 mbar 100 mbar 120 mbar No pneumatic air/gas
ratio control system
65–70 mbar 80 mbar 100 mbar
* If a stainless steel flexible tube ES is used instead of the
stainless steel bellows unit EKO, the higher pressure loss must be taken into account.
Page 57
ECOMAX · Edition 10.17 57
Project planning information for indirect heating
7.8.3 Operation with LPG
GEH
For operation with LPG, it is essential to cool the gas
lance via a central air lance in order to prevent the LPG
from cracking in the gas lance and soot formation dur-
ing combustion.
GEH
The central air volume is approx. 3 to 5% of the com-
bustion air volume and must also flow while the burner is switched off.
Open the adjuster in the central air lance fully. On the ECOMAX 1, the adjuster must be restricted to 45° or 50%.
If high temperature operation without flame control is intended for LPG, air flow monitoring using an air flow detector set ECO must be provided. If the flue gas route is blocked, the central air will be prevented from flowing into the gas line or gas will be prevented from flowing into the air line.
Page 58
ECOMAX · Edition 10.17 58
Project planning information for indirect heating
7.9 Air connection
7.9.1 Selecting components
For indirect heating, a quick opening air valve should
always be used to ensure a safe burner start. The fol- lowing air valves or buttery valves/solenoid actuators are recommended:
Burner
No pneumatic air/gas
ratio control system
Air/gas ratio control
ECOMA X 0 VR 20..N VR 20..N ECOMA X 1 VR 25..N VR 25..N ECOMA X 2 VR 40..N VR 40..N ECOMA X 3 VR 50..N VR 50..N ECOMA X 4 VR 65..N VR 65..N ECOMA X 5 BVHM 65/MB 7..N BVHM 65/MB 7..N
VR
ECOMAX 0 … ECOMAX 4
MB 7
+
BVHM
ECOMAX 5
7.9.2 Air pressure
The required air pressure depends on the burner size,
the gas type and the system conguration.
Air supply line pressure
Air pressure
upstream of burner
Natural gas H
Natural gas
L / LPG
Air/gas ratio control
approx. 50–60 mbar 80 mbar 100 mbar
No pneumatic air/gas ratio control system
approx. 50–60 mbar 80 mbar 80 mbar
To ensure accurate measurements of the pressure dif-
ferential on the integrated orice, flow to the orifice must not be disturbed. We recommend using the con­nection set for air, which ensures correct measurement at the measuring orice, see page 53 (Connection set for gas and air). The attachment of a coupling, a bellows unit or a pipe bend directly upstream of the orifice can cause turbulence in the gas flow resulting in the burner being incorrectly adjusted.
Page 59
ECOMAX · Edition 10.17 59
Project planning information for indirect heating
7.10 Air flow monitoring
A system which includes air flow monitoring is recom-
mended to monitor pre-purge (pursuant to EN 7462 and ISO 135772). This is implemented using a dif-
ferential pressure switch at the air connection together
with a burner control unit BCU 465. An air flow monitor- ing set is available for this purpose as an accessory, see page 62 (Air flow detector set).
7.11 Purge air and cooling air
Purge air must be connected to the burner ECOMA X in
order to ensure safe ignition and monitoring, and in or- der to avoid problems caused by condensation and/or overheating:
The required purge air volume is approx. 0.5 to 1.0%
of the air volume for rated capacity, or a minimum of
1 Nm
3
/h.
The purge air is connected to the gas connection flange
next to the electrode, or in the case of UV control to the purge air connection of the UV sensor. The purge air is tapped upstream of the air control valve so that the purge air continues to flow even if the burner is switched off.
In order to limit the volume of purge air, special nozzles can be used which are adjusted to the required air sup­ply pressure for the ECOMAX – see page 63 (Purge air/cooling air nozzles).
Burner
Nozzle for electrode
purge
Purge air nozzle on
UV sensor
ECOMA X 0
Nozzle electrode ECO 0
Rp 1/4 D = 2.5 /E
Nozzle UV ECO 03
Rp 1/4 D = 2.5 /B
ECOMA X 1–3
Nozzle electrode ECO 13
Rp 1/4 D = 2.5 /E
Nozzle UV ECO 03
Rp 1/4 D = 2.5 /B
ECOMA X 4–5
Nozzle electrode ECO 46
Rp 1/4 D = 4.0 /E
Nozzle UV ECO 46
Rp 1/4 D = 4.0 /B
Page 60
ECOMAX · Edition 10.17 60
Project planning information for indirect heatingProject planning information for indirect heating
7.12 Condition on delivery
The position of the gas, air and flue gas connections
can be customized depending on how the burner is to be installed on the furnace. The positions of the con- nections are coded using the numbers 0, 3, 6 and 9.
Code Connection position
0 top 3 right-hand side 6 bottom 9 left-hand side
The codes relating to the positions of the connections
are specified in the following order: flue gas – air – gas – and cooling air (increased furnace cooling) if required.
Provided that there are no specications, the burners
are supplied as follows:
ECOMAX../R for indirect heating with connector posi-
tion 066, i.e. with flue gas connection at the top and gas and air connection at the bottom.
0
3
6
9
Add-on components with the marking /E, such as the
air flow detector set, UV adapter, purge air nozzle, etc, are installed on the burner at the factory, provided that they are ordered at the same time as the burner.
7.13 Increased furnace cooling with ECOMAX..K
VR..N
VG..L
BCU 465..C
12
23
DI
L1, N, PE
µC
P
22 4
19 18
17 16
A
P
5
3
DI
6
26
GEH
EKO
32
33
VG
PLC
Depending on the technical requirements for the pro­cess, cooling can be implemented in two stages.
Page 61
ECOMAX · Edition 10.17 61
Project planning information for indirect heating
Actuating the air valve for the burner (terminal 22) initi-
ates “normal” cooling; actuating a second air valve for the additional cooling air connection initiates additional cooling. The additional cooling air valve is actuated separately by the process control system. For wiring on site, we recommend using a BCU..C with a supplemen- tary terminal strip (e.g. terminals 32/33 for additional air valve).
In the case of “additional” cooling air, the combustion air valve must be activated together with the cooling air valve in order to prevent the recuperator from overheat- ing.
7.14 Build up of noise
In the case of fitted burners, the sound level of the sin- gle burner which can be measured outside the furnace is usually between 75 and 82 dB(A).
In a furnace system, the value which can be measured depends on the capacity, excess air volume, flue gas extraction and flue gas temperature of the single burn- ers as well as the burner arrangement and ambient influences.
7.15 Emissions
CO and NOX values depend on the furnace tempera­ture, air preheat temperature, burner type and burner settings (NOX values on request).
If operated with LPG, NO
X
values are approx. 25%
higher.
600 700 800 900 1000 1100 1200 1300
0
100
200
300
400
500
600
ECOMAX..C
ECOMAX..M
Flue gas temperature at recuperator inlet [°C]
NO
x
[mg/m
3
ref. 5 % O
2
]
NOX values in the diagram apply for natural gas
Page 62
ECOMAX · Edition 10.17 62
Accessories
8 Accessories
8.1 Air connection set
Specially machined barrel nipples which ensure reliable, correct measurement at the orices installed in the burner. Version /E is installed in the burner on delivery.
Designation Order No.
Air inlet pipe ECO 0–1 R 1 /E 22802897 Air inlet pipe ECO 2 R 1 1/2 /E 22802898 Air inlet pipe ECO 3–5 R 2 /E 22802899 Air inlet pipe ECO 6 R 3 /E 22802900
8.2 Air flow detector set
The differential pressure switch for air flow monitor-
ing is used for the automatic monitoring of the air flow on the burner ECOMAX in conjunction with the burner control unit BCU 465. The differential pressure switch monitors the air flow during pre-purge and burner op­eration. If there is no air pressure, the burner is switched off or is not enabled. The pressure switch switching point should be set to approx. 80% of the differential pressure in normal operation.
Designation Order No.
Air flow detector set ECO /E 21802994
Page 63
ECOMAX · Edition 10.17 63
Accessories
8.3 VAH connection set
The VAH connection set also comprises the connection
for gas control line pd-, which is connected behind the
gas orifice integrated in the burner to ensure that a gas supply pressure of 80 mbar in the supply line (recom- mended value: 100 mbar) is sufcient.
Designation Order No.
Connection set VAH ECO /E 21800791
8.4 UV adapter set
For attaching the UVS 10, an adapter is required.
Designation Order No.
Adapter set Eco 15UVS 10 /E 21800791
8.5 Purge air/cooling air nozzles
Nozzle to limit the volume of purge air in order to achieve safe ignition and monitoring of the ECOMAX burner and to avoid condensation and overheating.
Nozzle for electrode purge
Burner Nozzle designation Order No.
ECOMA X 0
Nozzle electrode ECO 0
Rp 1/4 D = 2.5 /E
21802944
ECOMA X 1–3
Nozzle electrode ECO 13
Rp 1/4 D = 2.5 /E
21802945
ECOMA X 4–6
Nozzle electrode ECO 46
Rp 1/4 D = 4.0 /E
21802946
UV sensor purge air nozzle
Burner Nozzle designation Order No.
ECOMA X 0–3
Nozzle UV ECO 03
Rp 1/4 D = 2.5 /B
21802989
ECOMA X 4–6
Nozzle UV ECO 46
Rp 1/4 D = 4.0 /B
21802990
Page 64
ECOMAX · Edition 10.17 64
Accessories
8.6 Flue gas guide tube FGT Set..D
for ECOMAX..C
for ECOMAX..M
When using the ECOMAX burners for direct heating, a
flue gas guide tube FGT Set..D is required.
The FGT Set..D is available in lengths in various incre-
ments, which are suited to different burner lengths.
For ECOMA X 1C, 2C and 3C, there is a standard ver-
sion for furnace temperatures up to 1200°C and a high temperature version for furnace temperatures from
1200°C to 1250°C.
Scope of delivery: flue gas guide tube FGT with burner gasket, mounting gasket, as well as 4 threaded bolts, washers and nuts for attaching it to the burner.
ECOMA X..C
Flue gas guide tube Order No.
FGT SET ECO 1C545/DHT 21800926 FGT SET ECO 2C545/DHT 21800928 FGT SET ECO 3C545/DHT 21800930 FGT SET ECO 4C545/DHT 21800629 FGT SET ECO 5C545/DHT 21801325
ECOMA X..M
Flue gas guide tube Order No.
FGT SET ECO 1M545/D 21800195 FGT SET ECO 2M545/D 21800177 FGT SET ECO 3M545/D 21800694 FGT SET ECO 4M545/D 21800162 FGT SET ECO 5M545/D 21800499 FGT SET ECO 6M545/D 21800660
Page 65
ECOMAX · Edition 10.17 65
Accessories
8.7 Flue gas eductor EJEK
For direct heating
The eductor EJEK generates a vacuum with a centrally
positioned nozzle and thus draws the flue gases out of the furnace chamber through the burners heat ex- changer.
Designation for ECOMAX..C Order No.
EJEK 1K269M625HAGKHTS 22800872 EJEK 2K285M540HAGKHTAS 22802953 EJEK 3K292M620AGKHTAS 22801413 EJEK 4K345M920AGKHTAS 22801701 EJEK 5K345M1165AGKHTAS 22801828
Special version on request.
Designation for ECOMAX..M Order No.
EJEK 1K269M625HAGKS 22800931 EJEK 2K285M540HAGKAS 22802952 EJEK 3K292M620AGKAS 22801159 EJEK 4K345M920AGKAS 22801700 EJEK 5K345M1165AGKAS 22801826 EJEK 6K530M1618AGKAS 22801903
8.8 Flue gas connector FLUP
In indirect heating systems, flue gas connector FLUP discharges the flue gas into the furnace flue gas sys­tem to be provided by the customer.
Designation Order No.
FLUP 032DM230CBS 21801830 FLUP 1/250DM331CS 21100612 FLUP 365DM353CS 21102259 FLUP 4/5100DM399CS 21102718
Special version on request.
Page 66
ECOMAX · Edition 10.17 66
Accessories
8.9 Ceramic radiant tube SERC
For heat treatment processes in which combustion
gases must be kept separate from the product. The pat- ented flange connection is air-tight.
Material: SiSiC, max. application temperature: 1300°C.
Further information can be found in the Technical
Information bulletinCeramic radiant tube SERC.
Order No. on request.
8.10 Segmentedame tube SICAFLEX
For guiding hot flue gases in single ended radiant tubes.
Further information can be found in the Technical Information bulletin “Segmented flame tube SICAFLEX.
Order No. on request.
Page 67
ECOMAX · Edition 10.17 67
Accessories
8.11 Cruciform spacer
For installation of the segmented flame tube SICAF LEX® in vertical radiant tubes. The cruciform spacer en-
sures optimum sizing of the recirculation gap between the segmented flame tube and the burner.
Material: refractory clay.
Available on request in different sizes depending on the
SICAFLEX
®
sizes and different heights.
8.12 Flue gas guide tube FGT SET ECO.. SERC
To guide the flue gases if smaller burners are used
than those normally intended; see page 49 (Radiant tubes). The flue gas guide tube ensures sufficient heat exchange via the burner recuperator.
Material: Shaped part made of vacuum-formed
ceramic fibres (RCF).
Available on request in different sizes and versions suit-
able for the SERC and ECOMAX burner sizes.
Page 68
ECOMAX · Edition 10.17 68
Accessories
8.13 Piping
The burners can be optionally supplied with pre-mounted pipework for gas and air.
8.13.1 Direct heating
BVHM + MB7..L
VMV EKO
LEH
ECOMAX
VAH
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
AKT
p
sa-
p
sa
p
d-
VAS..N
ECOMAX Material No. Designation Combinations
Gas
0– 3 86594777 GVRS 15R0515R05WECO 03 VASN + VAH… + VMV…
4 86594778 GVRS 20R0520R05WECO 4 VASN + VAH… + VMV… 5 86 494779 GVRS 25R0525R05WECO VASN + VAH… + VMV… 6 86594776 GVRS 40R0540R05WECO 6 VASN + VAH… + VMV…
Air
0 86594782 L 40R25R32RWECO 0EJEK VRL + LEH… + CIM… 1 86594783 L 50R25R32RWECO 1EJEK VRL + LEH… + CIM… 2 86594784 L 65R40R40RWECO 2EJEK VRL + LEH… + LEH… 3 86594785 L 65R50R50RWECO 3EJEK BVHMMB7LW6 + LEH… + LEH… 4 86594786 L 80F50R65RWECO 4EJEK BVHMMB7LW6 + LEH… + CIM… 5 86594787 L 80F50R65RWECO 5EJEK BVHMMB7LW6 + LEH… + CIM… 6 L 100F80R100FWECO 6EJEK BVHMMB7LW6 + CIM… + CIM…
Page 69
ECOMAX · Edition 10.17 69
Accessories
8.13.2 Indirect heating
VR..N
VMV
ECOMAX
VG VG..L
BCU
BZA
Prozess-Steuerung/
Process Control (PCC)
PDZ
DG
AKT
ECOMAX Material No. Designation Combinations
Gas
0– 3 86594195 GS 15R0215R02WECO 03 VG…N + VG…L + VMV…
4 86594654 GS 20R0520R05WECO 4 VCS 1 (VAS…N + VAS…L) + VMV… 5 86594687 GS 25R0525R05WECO 5 VCS 1 (VAS…N + VAS…L) + VMV…
Air
0– 1 86594689 L 25R25RWECO 01 VR…N + LEH…
2 86594693 L 40R40RWECO 2 VR…N + LEH… 3 86594694 L 50R50RWECO 3 VR…N + LEH… 4 86594696 L 65R50RWECO 4 VR…N + LEH… 5 86594697 L 65R50RWECO 5 BVHM… + CIM…
Page 70
ECOMAX · Edition 10.17 70
Technical data
9 Technical data
Gas supply pressure and air supply pressure
each depend on the use and gas type (gas and air pressures:see burner diagrams at www.docuthek.com – registration required).
Type of heating: direct with eductor or indirect in radiant
tube.
Control type: On/Off.
Adjusting range: 60% to 100%.
Flame velocity: approx. 130 to 170 m/s.
Flame control: direct ionization control (UV control as
an option).
Ignition: direct spark ignition.
Burner Recuperator
Max. flue gas tempera-
ture at recuperator inlet
ECOMAX..C Ceramic (SiSiC) 125C* ECOMAX..M Cast steel 1150°C ECOMAX..F Metallic 105C
* We advise against use in forging and heating furnaces, in which
raw materials are heated.
Burner Capacity [kW] Flame length [mm]*
ECOMA X 0 25 300 ECOMA X 1 36 300 ECOMA X 2 60 400 ECOMA X 3 100 450 ECOMA X 4 180 800 ECOMA X 5 250 800 ECOMA X 6 500 1000
* Visible range for natural gas operation in the open air,
max. connection rating and air index 1.15.
The visible flame diameter is 0.3 to 0.5 times that of
the burner Ø B for natural gas operation in the open air, max. connection rating and air index 1.15.
REACH Regulation
Information pursuant to REACH Regulation No. 1907/2006, Article 33. Insulation contains refractory ceramic fibres (RCF)/alu­minium silicate wool (ASW). RCF/ASW are listed in the Candidate List of the Euro­pean REACH Regulation No. 1907/2006.
400 500 600 700 800 900 1000 1100
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
1200
1300
1400
F
M
C
Firing efficiency η
Flue gas temperature on recuperator inlet [°C]
Cold air burner
Page 71
ECOMAX · Edition 10.17 71
Technical data
9.1 Dimensions
9.1.1 ECOMAX..C for direct heating
K
M
ØP
V
LA
GA
H1
S1 = +/- 20 mm
G
B A
C
D
G1
A1
ØF
I
Øn
m
Type ECOMAX FGT set EJEK
GA LA Ø B C
1)D1)
G1 G
H1
Ø A2)Ø F A1 Ø n I m V K M Ø P Weight
mm mm mm kg
3)
ECOMA X 0C R ½ Rp 1 86 60 179 ~78
395, 475,
556, 636
182 142 300 260 4 x 18 210 4 x M12 R 269 625 43 ~11
ECOMA X 1C R ½ Rp 1 123 60 212 ~80
545, 593,
641, 689
236 180 330 280 4 x 19 290 4 x M16 R 269 625 43 ~19
ECOMAX 2C R ½ Rp 1½ 142 60 212 ~80
545, 613,
681
236 200 330 280 4 x 19 290 4 x M16 R 285 540 83 ~21
ECOMA X 3C R ½ Rp 2 178 83 262 ~80
545, 617,
689
280 236 385 325 4 x 19 330 4 x M16 R 2 292 620 98 ~33
ECOMA X 4C R ¾ Rp 2 240 95 298 ~86 545 368 300 480 420 4 x 19 445 4 x M16 R 2½ 345 920 128 ~48 ECOMAX 5C R 1 Rp 2 273 95 298 ~86 545 368 336 480 420 4 x 19 445 4 x M16 G 2½ 345 1165 153 ~55
1)
Excluding gasket (t = 1.3 mm)
2)
Diameter excluding plate bracket (with plate bracket: Ø A + approx. 3 mm)
3)
Weight of burner of shortest length.
Page 72
ECOMAX · Edition 10.17 72
Technical data
9.1.2 ECOMAX..M for direct heating
S1
G
B A
C
D
G1
A1
ØF
I
Øn
m
K
M
ØP
V
LA
GA
H1
Type ECOMAX FGT set EJEK
GA LA Ø B C
1)D1)
G1 G
H1
Ø A Ø F A1 Ø n I m V K M Ø P Weight
mm mm mm kg
2)
ECOMAX 1M R ½ Rp 1 123 60 212 ~78
545, 595,
645, 695
236 133 330
280
4 x 19
290
4 x M16 R 269 625 43 ~35
ECOMAX 2M R ½ Rp 1½ 142 60 212 ~80
545, 595,
645, 695
236 156 330
280
4 x 19
290
4 x M16 R 285 540 83 ~41
ECOMA X 3M R ½ Rp 2 178 83 262 ~80
545, 595,
645, 695
280 193 385
325
4 x 19
330
4 x M16 R 2 292 620 98 ~53
ECOMAX 4M R ¾ Rp 2 24 0 95 298 ~86
545, 595,
645, 695
368 254 480 420 4 x 19
445
4 x M16 R 2½ 345 920 128 ~90
ECOMAX 5M R 1 Rp 2 273 95 298 ~86 545, 695 368 287 480 420 4 x 19
445
4 x M16 G 2½ 345
1165
153 ~91
ECOMA X 6M R 1½ Rp 3 370 150 401
~137
545, 695 540 390 74 0
690
8 x 23
650
4 x M20 DN 100 530
1618
215 ~265
1)
Excluding gasket (t = 4 mm)
2)
Weight of burner of shortest length.
Page 73
ECOMAX · Edition 10.17 73
Technical data
9.1.3 ECOMAX..F for direct heating
S1
G
B A
C
D
G1
A1
ØF
I
Øn
m
K
M
ØP
V
LA
GA
H1
Type ECOMAX FGT set EJEK
GA LA Ø B C
1)D1)
G1 G
H1
Ø A Ø F A1 Ø n I m V K M Ø P Weight
mm mm mm kg
2)
ECOMAX 1F R ½ Rp 1 109 60 212 ~78
545, 595,
645, 695
236 133 330
280
4 x 19
290
4 x M16 R 269 625 43 ~27
ECOMAX 2F R ½ Rp 1½ 128 60 212 ~80
545, 595,
645, 695
236 156 330
280
4 x 19
290
4 x M16 R 285 540 83 ~31
ECOMA X 3F R ½ Rp 2 164 83 262 ~80
545, 595,
645, 695
280 193 385
325
4 x 19
330
4 x M16 R 2
292
620 98 ~ 47
ECOMAX 4F R ¾ Rp 2 216 95 298 ~86
545, 595,
645, 695
368 254
480
420
4 x 19
445
4 x M16 R 2½
345
920 128 ~75
ECOMAX 5F R 1 Rp 2 224 95 298 ~86
545, 595,
645, 695
368 287
480
420
4 x 19
445
4 x M16 G 2½
345
1165 153 ~76
1)
Excluding gasket (t = 4 mm)
2)
Weight of burner of shortest length.
Page 74
ECOMAX · Edition 10.17 74
Technical data
9.1.4 ECOMAX..C for indirect heating
≥ 8 mm
≥ 0.315"
X
W
B1
P1 + N1
W2
G
C
D
G1
V1 = 0.7 × max. 1,5 × ØX
S1 = +/-20 mm
30 mm
LA
GA
H1
DN
FLUP
M
A1
ØF
I
Øn
m
Type ECOMAX SERC FLUP
GA LA C
1)D1)
G1 G
H1
P1 + N1 W2 B1 Ø X W Ø F A1 Ø n l m DN M
Weight
kg
2)
ECOMA X 0C
R ½ Rp 1 60 179 ~78
395,
475,
556,
636
182 ~34 35 160
100
1000– 2600
290 240 4 x 14 210 4 x M12 32
230
~11
ECOMA X 1C
R ½ Rp 1 60 212 ~80
545, 593, 641,
689
236 ~37 50
200
142
1500– 2600
330 280 4 x 19 290 4 x M16 50
331
~19
ECO MAX 2C
R ½ Rp 1½ 60 212 ~80
545, 613,
681
236 ~37 50 220 162
1500– 3000
330 280 4 x 19 290 4 x M16 50
331
~21
ECOMA X 3C
R ½ Rp 2 83 262 ~80
545,
617, 689
280 ~37 50
260
202
1500– 3000
385 325 4 x 19 330 4 x M16 65
353
~33
1)
Excluding gasket (t = 1.3 mm)
2)
Weight of burner of shortest length.
Page 75
ECOMAX · Edition 10.17 75
Technical data
9.1.5 ECOMAX..M for indirect heating
X
B
W
G
S1 = +/-20 mm
D1
V1 = 0,7 × bis 1,5 × ØX
C
D
G1
di
LA
GA
H1
DN
FLUP
M
A1
ØF
I
Øn
m
Type ECOMAX SERM FLUP
GA LA Ø B
C1)D1)G1 G
H1
D1 di Ø X2)Ø F3)A13)Ø n
3)
l m DN M Weight
mm mm mm kg
4)
ECOM AX 1M R ½ Rp 1 123 60 212 ~78
545, 595,
645, 695
236 30 > 128
di + 2
*
s
330 280 4 x 19 290 4 x M16 32
230
~35
ECOM AX 2M R ½ Rp 1½ 142 60 212 ~80
545, 595,
645, 695
236 30 > 147
di + 2
*
s
330 280 4 x 19 290 4 x M16 50
331
~41
ECOMA X 3M R ½ Rp 2 178 83 262 ~80
545, 595,
645, 695
280 30 > 185
di + 2
*
s
385 325 4 x 19 330 4 x M16 50
331
~53
ECOMA X 4M R ¾ Rp 2 240 95 298 ~86
545, 595,
645, 695
368 50 > 248
di + 2
*
s
480 420 4 x 19 445 4 x M16 65
353
~90
ECOM AX 5M R 1 Rp 2 273 95 298 ~86 545, 695 368 50 > 280
di + 2
*
s
480 420 4 x 19 445 4 x M16 100
399
~91
1)
Excluding gasket (t = 4mm)
2)
s = radiant tube wall thickness.
3)
provided by the customer. Data is just a recommendation.
4)
Weight of burner of shortest length.
Page 76
ECOMAX · Edition 10.17 76
Technical data
9.1.6 ECOMA X..F for indirect heating
X
W
G
C1
S1 = +/-20 mm
V1 = 0,7 × bis 1,5 × ØX
D1
C
D
G1
di
LA
GA
H1
DN
FLUP
M
A1
ØF
I
Øn
m
Type ECOMAX SERM FLUP
GA LA Ø B
C1)D1)G1 G
H1
D1 di Ø X2)Ø F3)A13)Ø n
3)
l m DN M
Weight
mm mm mm kg
4)
ECOMAX 1F R ½ Rp 1 109 60 212 ~78
545, 595,
645, 695
236 30 > 128
di + 2
*
s
330 280 4 x 19 290 4 x M16 32
230
~35
ECOMAX 2F R ½ Rp 1½ 128 60 212 ~80
545, 595,
645, 695
236 30 > 147
di + 2
*
s
330 280 4 x 19 290 4 x M16 50 331 ~41
ECOMA X 3F R ½ Rp 2 164 83 262 ~80
545, 595,
645, 695
280 30 > 185
di + 2
*
s
385 325 4 x 19 330 4 x M16 50 331 ~53
ECOMAX 4F R ¾ Rp 2 216 95 298 ~86
545, 595,
645, 695
368 50 > 248
di + 2
*
s
480 420 4 x 19 445 4 x M16 65
353
~90
ECOMAX 5F R 1 Rp 2 224 95 298 ~86
545, 595,
645, 695
368 50 > 280
di + 2
*
s
480 420 4 x 19 445 4 x M16 100
399
~91
1)
Excluding gasket (t = 4mm)
2)
s = radiant tube wall thickness.
3)
provided by the customer. Data is just a recommendation.
4)
Weight of burner of shortest length.
Page 77
ECOMAX · Edition 10.17 77
Maintenance
10 Maintenance
Twice per year, but if the media are highly contaminated,
this interval should be reduced.
Page 78
ECOMAX · Edition 10.17
Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs.
Clarity
Found information quickly Searched for a long time Didn’t find information What is missing?
Comprehension
Coherent Too complicated No answer
Scope
Too little Sufcient Too wide No answer
No answer
Navigation
I can find my way around I got “lost No answer
Use
To get to know the product To choose a product Planning To look for information
My scope of functions
Technical department Sales No answer
Remarks
Elster GmbH Postfach 2809 · 49018 Osnabrück Strotheweg 1 · 49504 Lotte (Büren)
Germany
Tel +49 541 12140
Fax +49 541 1214370 hts.lotte@honeywell.com
ww w.kromschroeder.com
The current addresses of our international agents
are available on the Internet: ww w.kromschroeder.de/ Weltweit.20.0.html?&L=1
We reserve the right to make technical modications in the interests of progress.
Copyright © 2017 Elster GmbH All rights reserved.
Contact
Feedback
03250971
Loading...