Honeywell ECC-RPU Product Installation Document

1Overview

Figure 1 ECC-RPU
screw
location
Figure 2 Removing the Dress Panel
1. lift up
2. pull out
3. slide down
keyholes
10.0” (25.4cm) O.C.
lower mounting holes
Figure 3 Backbox Mounting
One Fire-Lite Place Northford, CT 06472-1653 USA 203-484-7161 • FAX 203-484-7118 www.firelite.com
ECC-RPU Remote Page Unit
Product Installation Document
PN LS10030-000FL-E:B 8/9/2013 13-696

2.2 Mounting the Backbox

1. Mark and predrill holes for the top two backbox keyhole mounting bolts using the dimensions shown.
2. Install two upper fasteners in the wall with the screw heads protruding.
3. Using the upper 'keyholes', mount the backbox over the two screws.
4. Mark and drill the lower two holes.
5. Install the remaining fasteners and tighten all fasteners to complete backbox mounting.
NOTE: Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinances.

2Installation

2.1 Removing the Dress Panel

1. Open the door and lift the door off the pin hinges.
2. Loosen the screw securing the dress panel to the backbox.
3. Open dress panel and disconnect the ground wire from the back.
4. Lift up dress panel and pull out lower pivot flange. Slide the upper pivot flange down to completely remove the dress panel from cabinet. Store in a safe location.
6. Carefully reinstall the dress panel by reversing the steps in Section 2.1. Remember to reattach the ground cable.
7. Reinstall door.
A trim ring, TR-6-R, is available for semi-flush mount installations.

2.3 Mounting/Wiring an Optional Monitor Module

An MMF-300 monitor module may be mounted inside the cabinet. This can be used for HVAC shutdown applications when the monitor module is connected to the FACP SLC polling loop. The monitor module is wired to TB4 on the RPU and is activated by the 9th button on the RPU keypad. The module’s LED is visible through the keypad next to the 9th button.
1. Remove the two (2) keps nuts that secure the RPU board to the dress panel using a 5/16” socket.
2. Set the SLC address on the MMF-300. Remove the four (4) break-away tabs from the monitor module. See Figure 4.
3. Insert the bottom of the monitor module (SLC address dials facing inward) into the mounting tabs on the left side of the RPU. The RPU mounting screws will go through the top of the monitor module. Situate the LED on the front of the module over the hole in the PC board.
4. Replace the keps nuts over the mounting screws to secure the monitor module to the board.
5. Connect the SLC wiring to the module terminals 1 (–) and 2 (+). Refer to the SLC Wiring Manual for more information.
6. Wire TB4 on the RPU to T6/T7 on the monitor module as shown below. No ELR is required as it is built into TB4.

3 Wiring

Connections are made from TB24, TB12, and TB22 on the ECC-50/100 main control board to TB1, TB3, and TB2 on the RPU. If the ECC-RPU is the last device on the audio and data bus chain, signal terminations are required. For the last device on the external data bus, a removable jumper must be on pins 1 and 2 of JS4. If the ECC-RPU is not the last device, the jumper must be on pins 2 and 3 of JS4 as shown below. For the external audio riser, termination (15K ohm resistor) must be connected to pins 4 and 5 on TB2. A ferrite clamp (P/N: 50116546-001) must be installed around all wires in both the input and output wire runs
ECC main
control board
inside the RPU cabinet as shown below.
external operator interface
external
data bus
external
audio
riser
+
-
power - 24VDC
TB24
TB12
TB22
+
-
B A
SLC Out
Remove break-away tabs (4) from module
mounting
tabs
SLC In
+ -
LED on other
side of module
TB4
Figure 4 Wiring an MMF-300 to the RPU
keps
nuts
RPU board
24V
OUT
Data
JS4
(shown jumpered
on pins 2 and 3)
Audio
Figure 5 Remote Page Unit Wiring
TB1
+
1
-
IN
2 3
+
4
-
5
TB3
B
1
IN
A
2 3
B
4
OUT
OUT
A
5
TB2
+
1
IN
-
2 3
+
4
-
5
(Class B/Style Y)
ferrite clamp
to next operator interface/
amplifier or 15K ELR
(if last device)
2 ECC-RPU Installation Document — P/N LS10030-000FL-E:B 8/9/2013
Loading...
+ 1 hidden pages