The Honeywell EC/RM7830A and EC/RM7850A are
microprocessor-based integrated burner controls for
automatically fired gas, oil, or combination fuel single burner
full modulation (EC/RM7850A) or on/off (EC/RM7830A)
applications. The EC/RM7830A; EC/RM7850A system
consists of a relay module, subbase, amplifier, and purge
card. Options include keyboard display module (KDM),
Personal Computer Interface, Data ControlBus Module™,
remote display mounting and Combustion System Manager®
Software.
Functions provided by the EC/RM7830A and EC/RM7850A
include automatic burner sequencing, flame supervision,
system status indication, system or self-diagnostics and
troubleshooting. Text readout on the Keyboard Display Module
is available in English, Spanish, Portuguese, Katakana
(Japanese), French, Chinese, German, and Italian languages.
This document provides installation and static checkout
instructions. Other applicable publications are:
63-2278:Q7700 Network Interface Unit Product Data.
65-0084:Q7800A,B 22-Terminal Wiring Subbase
Data.
65-0229:7800 SERIES Relay Modules Checkout and
Troubleshooting Product Data.
SPECIFICATIONS
Electrical Ratings (See Tables 3A, 3B, 3C and 3D):
Voltage and Frequency:
RM7830A and RM7850A:
120 Vac (+10/-15%), 50/60 Hz (±10%).
EC7830A and EC7850A:
220/240 Vac (+10%/-15%), 50/60 Hz (±10%)
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 20A maximum, type FRN or
Operating: -40°F to 140°F (-40°C to +60°C).
Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous,
noncondensing.
Vibration: 0.5G environment.
Approvals:
RM7830A and RM7850A:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Canadian Standards Association Certified: LR9S329-3.
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
Industrial Risk Insurers: Acceptable.
Federal Communications Commission: Part 15,
Class B, Emissions.
EC7830A and EC7850A: Factory Mutual Approved.
These products also comply with the following European
directives:
Gas Appliance Directive: 90/396/EEC.
Low Voltage Directive: 73/23/EEC.
EMC Directive: 89/336/EEC.
GASTEC: CE-63AP3070/1.
Lloyds Register Approval.
Oil appliances:
EC7830A: DIN-5F 106/96.
EC7850A: DIN-5F 107/96.
These products are approved according to EN298, “Automatic
gas burner systems for gas burners and gas burning
appliances with or without fans.”
Please note the following to comply with EN60730 for remote
mounting of the KDM and/or remote reset module. It is
necessary to provide electrical separation using insulation at
least equivalent to double or reinforced insulation. This can be
accomplished by either:
1. Optically isolating the communication and/or remote
reset lines from the control cabinet or
2. Providing physical separation from the communication
and/or remote reset lines using electrical conduit and a
204718a Remote Display Cover Assembly or other
suitable enclosure that meets ip40 class of protection.
66-1092-2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and marked
on the product to make sure the product is suitable for
the application.
3. Installer must be a trained, experienced, flame
safeguard service technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage,
severe injury, or death.
Carefully follow safety requirements when installing a
burner control.
CA UTION
Electrical Shock Hazard or Equipment/
Control Damage.
Can cause electrical shock or equipment damage.
Disconnect power supply before beginning
installation.
IMPORTANT
1. Wiring connections for the relay modules are unique;
refer to Fig. 3 and 4 or the appropriate Specifications
for individual subbase wiring.
2. Wiring must comply with all applicable codes,
ordinances and regulations.
3. Wiring must comply with NEC Class 1
(Line Voltage) wiring.
4. Loads connected to the EC/RM7830A and
EC/RM7850A must not exceed those listed on the
relay module label or the Specifications; see Table 1.
5. Limits and interlocks must be rated to
simultaneously carry and break current to the
ignition transformer, pilot valve, and main fuel
valve(s).
6. All external timers must be listed or componentrecognized by authorities who have proper
jurisdiction.
7. For on-off gas-fired systems, some authorities who
have jurisdiction prohibit the wiring of any limit or
operating contacts in series between the flame
safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel
with the exception of C7015 Infrared Flame
Detectors.
9. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used
in accordance with the instructions, can cause
interference with radio communications. It has been
tested and found to comply with the limits for a Class
B computing device of Part 15 of FCC rules, which
are designed to provide reasonable protection
against such interference when operated in a
commercial environment. Operation of this
equipment in a residential area can cause
interference, in which case, the users, at their own
expense, may be required to take whatever
measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B
limits for radio noise for digital apparatus set out in
the Radio Interference Regulations of the Canadian
Department of Communications.
Location
Humidity
Install the relay module where the relative humidity never
reaches the saturation point. The relay module is designed to
operate in a maximum 85% relative humidity continuous,
noncondensing, moisture environment. Condensing moisture
can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to
vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When
installed outdoors, protect the relay module in an approved
weather-tight enclosure.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The
standard vertical position is recommended. Any other
position decreases the maximum ambient temperature
rating.
2. Select a location on a wall, burner or electrical panel.
The Q7800 can be mounted directly in the control
cabinet. Be sure to allow adequate clearance for
service, installation, access or removal of the relay
module, expanded annunciator, KDM, flame amplifier,
flame amplifier signal voltage probes, run/test switch,
electrical signal voltage probes and electrical field
connections.
3. For surface mounting, use the back of the subbase as a
template to mark the four screw locations, then drill the
pilot holes.
4. Securely mount the subbase using four no. 6 screws
(not provided).
66-1092—2
2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Wiring Subbase
CAUTION
Electrical Shock Hazard or Equipment Damage.
Can cause electrical shock or damage equipment.
Disconnect the power supply before beginning
installation.
The internal block diagram of the EC/RM7830A is shown in
Fig. 1 and the internal block diagram of the EC/RM7850A is
shown in Fig. 2.
1. For subbase wiring and sequence charts, refer to Fig. 3
and 4.
5
CONFIGURATION
JUMPERS
RUN/TEST
SWITCH
MICROCOMPUTER
RESET
PUSHBUTTON
RELAY
DRIVE
CIRCUIT
ES2
6K1
3K1
RS485
2
SAFETY RELAY
CIRCUIT
206
LD2
5
REMOTE
RESET
3
17
RTLOS
7
STATUS
LEDS
3K2
16
2
OPTIONAL KEYBOARD
DDL
DDL
COMMUNICATIONS
1
120 VAC, 50/60 Hz POWER SUPPLY, RM7830A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7830A.
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
DISPLAY MODULE
1
Fig. 1. Internal block diagram of EC/RM7830A (see Fig. 3 for detailed wiring instructions).
2. For remote wiring of the KDM, refer to the
Specifications for the KDM (65-0090), Network
Interface Unit (63-2278), Data ControlBus Module™
(65-0091) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main disconnect
before beginning installation to prevent electrical shock
and equipment damage. More than one disconnect can
be required.
4. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC Class 1 (Line Voltage)
wiring.
5. For recommended wire size and type, see Table 1.
6. For recommended grounding practices, see Table 2.
L1
HOT
N
1
PLUG-IN PURGE
TIMER CARD
FLAME SIGNAL
2K
3K
4K
5K
6K
7K
1K
POWER SUPPLY
2K2 5K1
1K1
RELAY CONTACT OPEN
RELAY CONTACT CLOSED
RELAY COIL
FIELD WIRING
INTERNAL WIRING
4K1
7K1
2K1
PLUG-IN
FLAME
AMPLIFIER
RELAY
STATUS
FEEDBACK
AND LINE
VOLTAGE
INPUTS
CONTROL
POWER
AL
10
8
21
9
4
3
F G ... 22
INDICATES FEEDBACK SENSING
OF RELAY CONTACT STATUS
AND LINE VOLTAGE INPUTS
USER TERMINALS
TEST
JACK
F
G
22
2
SHUTTER
IGN
PV1
PV2
MV
FAN
AL
M15183B
3
66-1092—2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
L1
N
HOT
RELAY
DRIVE
CIRCUIT
RTLOS
7
8K1
8K2
9K2
1
2K
3K
4K
5K
6K
7K
8K
9K
1K
POWER SUPPLY
1K1
HIGH FIRE
COMMON
LOW FIRE
9K1
MODULATE
PLUG-IN PURGE
TIMER CARD
FLAME SIGNAL
2K2 5K1
4K1
7K1
2K1
12
13
15
14
PLUG-IN
FLAME
AMPLIFIER
RELAY
STATUS
FEEDBACK
AND LINE
VOLTAGE
INPUTS
CONTROL
POWER
F G ... 22
4
CONFIGURATION
JUMPERS
RUN/TEST
SWITCH
MICROCOMPUTER
RESET
PUSHBUTTON
ES1
ES3
ES2
6K1
3K1
RS485
2
SAFETY RELAY
CIRCUIT
206
LD2
5
REMOTE
RESET
3
18
19
17
STATUS
LEDS
3K2
16
2
OPTIONAL KEYBOARD
DISPLAY MODULE
DDL
DDL
COMMUNICATIONS
1
120 VAC, 50/60 Hz POWER SUPPLY, RM7850A; 220-240 VAC,
50/60 Hz POWER SUPPLY, EC7850A. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED
SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
1
Fig. 2. Internal block diagram of EC/RM7850A (see Fig. 4 for detailed wiring instructions).
TEST
JACK
F
G
SHUTTER
22
AL
10
8
21
9
5
3
INDICATES FEEDBACK SENSING
OF RELAY CONTACT STATUS
AND LINE VOLTAGE INPUTS
USER TERMINALS
RELAY CONTACT OPEN
RELAY CONTACT CLOSED
RELAY COIL
FIELD WIRING
INTERNAL WIRING
IGN
PV1
PV2
MV
FAN
AL
M15184B
2
66-1092—2
4
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
L1
N
1
G12
N13
314
415
516
617
718
819
(L1)
920
1021
F22
AL
FAN
RT
LD2
PV1
MV
IGN
ES2
LOS
PV2
FLAME
DETECTOR
1
12O VAC, 50/60 Hz POWER SUPPLY (RM7830A). 220-240 VAC, 50/60 Hz POWER SUPPLY
(EC7830A). PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
SEE FLAME DETECTOR INSTRUCTIONS FOR CORRECT WIRING.
LEGEND
ALARM
(NORMALLY OPEN)
PREIGNITION
INTERLOCK INPUT
BURNER/BLOWER
MOTOR
IGNITION
LINE VOLTAGE SUPPLY
LOCKOUT INPUT
AIRFLOW SWITCH INPUT
MAIN FUEL VALVE
PILOT VALVE 1
(INTERRUPTED)
PILOT VALVE 2
(INTERMITTENT)
LIMITS AND BURNER
CONTROL
AL
ES2
FAN
IGN
L1
LOS
LD2
MV
PV1
Q7800
2
2
INITIATE
POWER
PILOT
FLAME
MAIN
ALARM
STANDBY
RUN
STANDBY
PRE
IGNITION
PILOT
STABIL.
MAIN
STABIL.
IGNITION
BURNER
POSTPURGE
MAIN VALVE
LIMITS AND BURNER CONTROL CLOSED
LOCKOUT INPUT
10 sec
AIRFLOW SWITCH CHECK
PILOT VALVE
V2
PREIGNITION INTERLOCK
OPTIONS
SAFE START CHECK
FLAME PROVING
3 sec
5 sec
5 sec
1 IF ON AT CALL FOR HEAT, HOLD (120 sec). LOCK OUT IF STILL ON.
3 or 5 sec
3 or 5 sec
SAFE START CHECK
IF OFF AFTER 10 SEC OF FAN, LOCK OUT.
2
2, 15 or 30 sec
3
4
5
TAKE LOCKOUT ACTION, CONTINUE POSTPURGE TIMING.
SELECT VIA ST7800A PURGE TIMER CARD.
4
5
6
SELECT VIA CONFIGURATION JUMPERS OR MODEL NUMBERS.
AFS CHK
1
2 sec
AFS CHK
AFS CHK
DUE TO ONE EXTRA SECOND FOR SAFETY RELAY TEST, TIMING CAN VARY FROM 3 TO 4 SECONDS.
6
LED
DISPLAY
"PREPURGE"
WAITING
FIRST SAFETY
TIME
MAIN TRIAL
TIME
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
EC/RM7830A Power Burner ON/OFF, GAS or OIL Sequence
2
3
6
6
M15185B
PV2
RT
8
21
9
6
20
7
10
17
BURNER/BLOWER MOTOR
4
Fig. 3. Wiring subbase and sequence chart for EC/RM7830A.
5
66-1092—2