Honeywell EC7830A, EC7850A, RM7830A, RM7850A Installation Instructions Manual

EC7830A, RM7830A, EC7850A, RM7850A
7800 SERIES Relay Modules
INSTALLATION INSTRUCTIONS
APPLICATION
The Honeywell EC/RM7830A and EC/RM7850A are microprocessor-based integrated burner controls for automatically fired gas, oil, or combination fuel single burner full modulation (EC/RM7850A) or on/off (EC/RM7830A) applications. The EC/RM7830A; EC/RM7850A system consists of a relay module, subbase, amplifier, and purge card. Options include keyboard display module (KDM), Personal Computer Interface, Data ControlBus Module™, remote display mounting and Combustion System Manager® Software.
Functions provided by the EC/RM7830A and EC/RM7850A include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting. Text readout on the Keyboard Display Module is available in English, Spanish, Portuguese, Katakana (Japanese), French, Chinese, German, and Italian languages.
This document provides installation and static checkout instructions. Other applicable publications are: 63-2278: Q7700 Network Interface Unit Product Data. 65-0084: Q7800A,B 22-Terminal Wiring Subbase
Product Data. 65-0090: S7800A Keyboard Display Module Product Data. 65-0091: S7810A Data ControlBus Module™ Product
Data. 65-0228: S7810B Multi-Drop Switch Module Product Data. 65-0095: S7820 Remote Reset Module Product Data. 65-0097: 221729C Dust Cover Packing Instructions. 65-0102: ZM7850A Combustion System Manager®
Operating Instructions. 65-0109: R7824, R7847, R7848, R7849, R7861, R7886
Flame Amplifiers for the 7800 SERIES
Product Data. 65-0131: 221818A Extension Cable Assembly Product
Data. 65-0229: 7800 SERIES Relay Modules Checkout and
Troubleshooting Product Data.
SPECIFICATIONS
Electrical Ratings (See Tables 3A, 3B, 3C and 3D):
Voltage and Frequency:
RM7830A and RM7850A:
120 Vac (+10/-15%), 50/60 Hz (±10%).
EC7830A and EC7850A:
220/240 Vac (+10%/-15%), 50/60 Hz 10%) Power Dissipation: 10W maximum. Maximum Total Connected Load: 2000 VA. Fusing Total Connected Load: 20A maximum, type FRN or
equivalent.
® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved
Environmental Ratings:
Ambient T emperature:
Operating: -40°F to 140°F (-40°C to +60°C). Storage: -40°F to 150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous,
noncondensing.
Vibration: 0.5G environment.
Approvals:
RM7830A and RM7850A:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ. Canadian Standards Association Certified: LR9S329-3. Factory Mutual Approved: Report No. J.I.1V9A0.AF. Industrial Risk Insurers: Acceptable. Federal Communications Commission: Part 15,
Class B, Emissions.
EC7830A and EC7850A: Factory Mutual Approved. These products also comply with the following European
directives: Gas Appliance Directive: 90/396/EEC. Low Voltage Directive: 73/23/EEC. EMC Directive: 89/336/EEC. GASTEC: CE-63AP3070/1. Lloyds Register Approval.
Oil appliances:
EC7830A: DIN-5F 106/96. EC7850A: DIN-5F 107/96.
These products are approved according to EN298, “Automatic gas burner systems for gas burners and gas burning appliances with or without fans.”
Please note the following to comply with EN60730 for remote mounting of the KDM and/or remote reset module. It is necessary to provide electrical separation using insulation at least equivalent to double or reinforced insulation. This can be accomplished by either:
1. Optically isolating the communication and/or remote reset lines from the control cabinet or
2. Providing physical separation from the communication and/or remote reset lines using electrical conduit and a 204718a Remote Display Cover Assembly or other suitable enclosure that meets ip40 class of protection.
66-1092-2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safeguard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
WARNING
Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
Carefully follow safety requirements when installing a burner control.
CA UTION
Electrical Shock Hazard or Equipment/ Control Damage. Can cause electrical shock or equipment damage.
Disconnect power supply before beginning installation.
IMPORTANT
1. Wiring connections for the relay modules are unique; refer to Fig. 3 and 4 or the appropriate Specifications for individual subbase wiring.
2. Wiring must comply with all applicable codes, ordinances and regulations.
3. Wiring must comply with NEC Class 1 (Line Voltage) wiring.
4. Loads connected to the EC/RM7830A and EC/RM7850A must not exceed those listed on the relay module label or the Specifications; see Table 1.
5. Limits and interlocks must be rated to simultaneously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component­recognized by authorities who have proper jurisdiction.
7. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safeguard control and the main fuel valve(s).
8. Two flame detectors can be connected in parallel with the exception of C7015 Infrared Flame Detectors.
9. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, can cause interference with radio communications. It has been tested and found to comply with the limits for a Class B computing device of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area can cause interference, in which case, the users, at their own expense, may be required to take whatever measures are required to correct this interference.
10. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Location
Humidity
Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85% relative humidity continuous, noncondensing, moisture environment. Condensing moisture can cause a safety shutdown.
Vibration
Do not install the relay module where it can be subjected to vibration in excess of 0.5G continuous maximum vibration.
Weather
The relay module is not designed to be weather tight. When installed outdoors, protect the relay module in an approved weather-tight enclosure.
Mounting Wiring Subbase
1. Mount the subbase in any position except horizontally
with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position decreases the maximum ambient temperature rating.
2. Select a location on a wall, burner or electrical panel. The Q7800 can be mounted directly in the control cabinet. Be sure to allow adequate clearance for service, installation, access or removal of the relay module, expanded annunciator, KDM, flame amplifier, flame amplifier signal voltage probes, run/test switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations, then drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws (not provided).
66-1092—2
2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
Wiring Subbase
CAUTION
Electrical Shock Hazard or Equipment Damage. Can cause electrical shock or damage equipment.
Disconnect the power supply before beginning installation.
The internal block diagram of the EC/RM7830A is shown in Fig. 1 and the internal block diagram of the EC/RM7850A is shown in Fig. 2.
1. For subbase wiring and sequence charts, refer to Fig. 3 and 4.
5
CONFIGURATION JUMPERS
RUN/TEST SWITCH
MICROCOMPUTER
RESET PUSHBUTTON
RELAY DRIVE CIRCUIT
ES2
6K1
3K1
RS485
2
SAFETY RELAY CIRCUIT
20 6
LD2
5
REMOTE RESET
3
17
RTLOS
7
STATUS LEDS
3K2
16
2
OPTIONAL KEYBOARD
DDL
DDL COMMUNICATIONS
1
120 VAC, 50/60 Hz POWER SUPPLY, RM7830A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7830A. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
DISPLAY MODULE
1
Fig. 1. Internal block diagram of EC/RM7830A (see Fig. 3 for detailed wiring instructions).
2. For remote wiring of the KDM, refer to the
Specifications for the KDM (65-0090), Network Interface Unit (63-2278), Data ControlBus Module™ (65-0091) or Extension Cable Assembly (65-0131).
3. Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect can be required.
4. All wiring must comply with all applicable electrical codes, ordinances and regulations. Wiring, where required, must comply with NEC Class 1 (Line Voltage) wiring.
5. For recommended wire size and type, see Table 1.
6. For recommended grounding practices, see Table 2.
L1 HOT
N
1
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
2K 3K
4K 5K
6K 7K
1K
POWER SUPPLY
2K2 5K1
1K1
RELAY CONTACT OPEN RELAY CONTACT CLOSED
RELAY COIL FIELD WIRING INTERNAL WIRING
4K1
7K1
2K1
PLUG-IN FLAME AMPLIFIER
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
CONTROL POWER
AL
10
8
21
9
4
3
F G ... 22
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS
USER TERMINALS
TEST JACK
F
G
22
2
SHUTTER
IGN
PV1
PV2
MV
FAN
AL
M15183B
3
66-1092—2
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
L1
N
HOT
RELAY DRIVE CIRCUIT
RTLOS
7
8K1
8K2
9K2
1
2K 3K
4K 5K
6K 7K 8K 9K
1K
POWER SUPPLY
1K1
HIGH FIRE
COMMON LOW FIRE
9K1
MODULATE
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
2K2 5K1
4K1
7K1
2K1
12
13
15
14
PLUG-IN FLAME AMPLIFIER
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
CONTROL POWER
F G ... 22
4
CONFIGURATION JUMPERS
RUN/TEST SWITCH
MICROCOMPUTER
RESET PUSHBUTTON
ES1
ES3
ES2
6K1
3K1
RS485
2
SAFETY RELAY CIRCUIT
20 6
LD2
5
REMOTE RESET
3
18
19
17
STATUS LEDS
3K2
16
2
OPTIONAL KEYBOARD DISPLAY MODULE
DDL
DDL COMMUNICATIONS
1
120 VAC, 50/60 Hz POWER SUPPLY, RM7850A; 220-240 VAC, 50/60 Hz POWER SUPPLY, EC7850A. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
TO CONNECT L1 DIRECTLY TO LOS, AT LEAST ONE CONTROLLED SHUTDOWN MUST BE PROVIDED EVERY 24 HOURS.
1
Fig. 2. Internal block diagram of EC/RM7850A (see Fig. 4 for detailed wiring instructions).
TEST JACK
F
G
SHUTTER
22
AL
10
8
21
9
5
3
INDICATES FEEDBACK SENSING OF RELAY CONTACT STATUS AND LINE VOLTAGE INPUTS
USER TERMINALS RELAY CONTACT OPEN RELAY CONTACT CLOSED RELAY COIL FIELD WIRING
INTERNAL WIRING
IGN
PV1
PV2
MV
FAN
AL
M15184B
2
66-1092—2
4
EC7830, RM7830A,EC7850A,RM7850A 7800 SERIES RELAY MODULES
L1 N
1
G 12 N 13 3 14 4 15 5 16 6 17 7 18 8 19
(L1)
9 20
10 21
F 22
AL
FAN
RT
LD2 PV1
MV
IGN
ES2
LOS PV2
FLAME DETECTOR
1
12O VAC, 50/60 Hz POWER SUPPLY (RM7830A). 220-240 VAC, 50/60 Hz POWER SUPPLY (EC7830A). PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
SEE FLAME DETECTOR INSTRUCTIONS FOR CORRECT WIRING.
LEGEND
ALARM (NORMALLY OPEN)
PREIGNITION INTERLOCK INPUT
BURNER/BLOWER MOTOR
IGNITION LINE VOLTAGE SUPPLY LOCKOUT INPUT AIRFLOW SWITCH INPUT MAIN FUEL VALVE PILOT VALVE 1
(INTERRUPTED) PILOT VALVE 2
(INTERMITTENT) LIMITS AND BURNER
CONTROL
AL ES2 FAN IGN
L1 LOS LD2 MV PV1
Q7800
2
2
INITIATE
POWER PILOT FLAME MAIN ALARM
STANDBY
RUN
STANDBY
PRE IGNITION
PILOT STABIL.
MAIN STABIL.
IGNITION
BURNER
POSTPURGE
MAIN VALVE
LIMITS AND BURNER CONTROL CLOSED
LOCKOUT INPUT
10 sec
AIRFLOW SWITCH CHECK
PILOT VALVE
V2
PREIGNITION INTERLOCK
OPTIONS
SAFE START CHECK
FLAME PROVING
3 sec
5 sec
5 sec
1 IF ON AT CALL FOR HEAT, HOLD (120 sec). LOCK OUT IF STILL ON.
3 or 5 sec
3 or 5 sec
SAFE START CHECK
IF OFF AFTER 10 SEC OF FAN, LOCK OUT.
2
2, 15 or 30 sec
3
4
5
TAKE LOCKOUT ACTION, CONTINUE POSTPURGE TIMING.
SELECT VIA ST7800A PURGE TIMER CARD.
4
5
6
SELECT VIA CONFIGURATION JUMPERS OR MODEL NUMBERS.
AFS CHK
1
2 sec
AFS CHK
AFS CHK
DUE TO ONE EXTRA SECOND FOR SAFETY RELAY TEST, TIMING CAN VARY FROM 3 TO 4 SECONDS.
6
LED DISPLAY
"PREPURGE"
WAITING
FIRST SAFETY
TIME
MAIN TRIAL
TIME
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
EC/RM7830A Power Burner ON/OFF, GAS or OIL Sequence
2
3
6
6
M15185B
PV2
RT
8
21
9
6
20
7
10
17
BURNER/BLOWER MOTOR
4
Fig. 3. Wiring subbase and sequence chart for EC/RM7830A.
5
66-1092—2