Honeywell EA79 Catalog Page

Air Vents and Eliminators
5
(128)
4-11/16
(120)
M6095D
3/4 INCH NPT EXTERNAL THREAD
1/2 INCH NPT INTERNAL THREAD
OPEN CLOSED
CAUTION!
!
Device may be hot Do not use tools to adjust the e damage to vent may result us only to adjust vent A wrench only on hex during installation
1/2 (12)
1-7/8 (48)
M2760B
250
300
200
150
100
50
0
CUBIC FEET/HOUR
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
PRESSURE (PSI)
EA79 Industrial Air Vents
The Honeywell EA79 Industrial Air Vent purges air from high pressure mains and equipment in hot or cold closed water systems.
• Built-in shutoff valve for servicing without system shutdown.
• Built-in vacuum breaker.
• Safety drain connection and vent cap with leakage guard.
• Brass shell construction.
• Internal parts made of corrosion-resistant and chemical-resistant materials for use with water systems containing propylene glycol, mineral oils, or petroleum-based oils. Replaces Hoffman # 79 or Dole # 75 Vents.
• Maintains quiet and efficient operation.
Dimensions in inches (millimeters)
EA79 capabilities
EA79 construction
BLACK COVER ASSEMBLY
O-RING
SEAT AREA— MAKE SURE AREA IS FREE OF DIRT AND DEBRIS.
OUTER RING
RED VENT CAP WITH LEAKAGE GUARD
VENT LEVER
SPRING
FLOAT
M6096B
Product Number Connection Type Connection Size Description
EA79A1004 3/4 in. male NPT pipe thread with 1/2 in. female NPT pipe thread 3/4 in. Industrial automatic air vent
218 customer.honeywell.com 70-6910
Application: Hydronics Corrosion Resistant: Internal parts made of corrosion-resistant and
chemical-resistant materials for use with hydronic systems that may contain concentrations of propylene or ethylene glycol.
Maximum Operating Temperature: 250 F (120C) Maximum Operating Pressure: 150 psi (1034 kPa)
Accessories:
Q122A1001-Safe waste connector (M20 thread connection)
Replacement Parts:
P79B1003-Replacement O-ring, cover and internals for EA79A1004
Loading...