Honeywell C7046A User Manual

C7046A,B,C,D
)
D
)
A
(25)
3
)
)1 (25)
)
)
GASKET
R
)
USH
)
C
G
Air Temperature Sensors
INSTALLATION INSTRUCTIONS
APPLICATION
The C7046 series of Air Temperature Sensors function as primary and/or secondary sensors in electronic control systems.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
The sensor assembly (see Fig. 1) consists of an aluminum sensor probe (element housed internally) with attached flange that can be mounted on a flat duct or plenum surface, or in a 2 in. by 4 in. (51 by 102 mm) junction box using two No. 8 screws. Connections to the sensor are made through two 6 in. (152 mm) leadwires.
2 (51
/4 (19
5/16 (9) DIAMETE
(BUSHING
INSERTION LENGTH DEPENDS UPON THE MODEL.
1
Fig. 1. C7046A,B,C,D Air Temperature
Sensor dimensions in in. (mm).
8 (203
PLASTI
BUSHIN
LOCKING P
NUTS (2
1/4 (6
IAMETER (2 HOLES
1/16 (2
NEOPRENE
M22402
NOTE: Sensor probe diameter is 1/4 in. (6 mm).
Location
The sensor should be located in the air duct or plenum where it will sample an average air temperature. Avoid locations where air stratification can cause sensing errors.
Mounting
Mounting on Flat Duct or Plenum Surface (Fig. 2)
1. Cut a 3/8 in. (9.5 mm) hole in the duct or plenum surface at the desired location.
2. Insert sensor probe into the duct or plenum until the flange rests against the duct or plenum wall.
3. If necessary, use the flange as a template to mark and drill two holes for No. 8 mounting screws.
4. Fasten the sensor to the duct or plenum surface with two No. 8 sheet metal screws (not provided).
Mounting in a Junction Box (Fig. 3)
1. Cut a 3/8 in. (9.5 mm) hole in the duct or plenum surface at the desired location.
2. Remove the center rear knockout from the junction box and insert the sensing probe through the knockout with the flange flat against the outlet box.
3. Using the flange as a template, mark and drill two holes in the junction box and the duct or plenum surface for No. 8 mounting screws.
4. Insert sensor probe through both the junction box knockout and the 3/8 in. (9.5 mm) hole drilled in the duct or plenum and fasten the junction box and sensor to the duct or plenum surface.
® U.S. Registered Trademark Copyright © 2004 Honeywell International Inc. • All Rights Reserved
62-0216
C7046A,B,C,D AIR TEMPERATURE SENSORS
SENSO
OBE
GE
)
S
(
)
O
E
SYSTEM
COMPO
S
CO
O
S
(
)
A
SENSO
E
SYS
DUCT O
UM
GE
S
Y
CONDU
OX
CONNECTOR
CONDUIT
E
(
)
SYS
COMPO
S
CO
S
W
)
A
S
)
R
PR
T APPROPRIAT
NENT
M22403
Fig. 2. Mounting C7046 Air Temperature Sensor on a flat duct or plenum surface.
TANDARD UTILIT
IT B
LOCKNUT
TO APPROPRIATE
TEM
NENT
TEM
R
PLEN
Fig. 3. Mounting C7046 Air Temperature
Sensor in a junction box.
FLAN
R
PROB
NNECT SENSOR WIRE
ITH TWO WIRENUT
CONNECTORS (NOT PROVIDED
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
SYSTEM DUCT OR PLENUM
NO. 8 (4mm MOUNTING SCREW
NOT PROVIDED
FLAN
NNECT SENSOR WIRES WITH TW WIRENUT CONNECTOR
NOT PROVIDED
NO. 8 (4 mm) MOUNTING
CREWS (NOT
PROVIDED
FACEPLAT
OPTIONAL
M22404
CAUTION
Erratic System Operation Hazard. Failure to follow proper wiring practices can introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large
inductive loads such as motors line starters, lighting ballasts, and large power distribution panels.
Shielded cable is required in installations where
these guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
1. All wiring must agree with applicable codes, ordinances and regulations.
2. Do not mount sensor in incorrect environment.
3. Wire according to the applicable controller instructions.
4. Erratic temperature readings from a sensor can be caused by improper wiring practices. These must be avoided to assure proper operation:
•Avoid poor wiring connections.
•Avoid intermittent or missing building earth
ground.
•Do not mount sensor in incorrect environment.
Connect low voltage wiring from the sensor to the appropriate system component terminals using solderless connectors. See Fig. 3.
NOTES:
1. For connections to the W973 Single Zone
Logic Panel, see Fig. 4.
2. For connections to the W7080 Multizone
System, see Fig. 5.
3. For connections to the Excel 500 Control
System, see Fig. 6.
4. For additional wiring information, refer to the
appropriate specification.
W973 LOGIC PANEL
SENSOR STAT 24 VAC ECONO
C +20 H N
TT134251TRTRWBY
C7046A
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. Connecting C7046A Air Temperature Sensor to a W973 Single Zone Logic Panel.
1
L1
L2
(HOT)
R
M17965
62-0216 2
A
W7081
LIMIT CONTROLLER
ECONOMIZER/MIXED AIR LOW LIMIT–A5
21
3456
50
55
COLD DECK LOW LIMIT–A6
21
HOT DECK HIGH LIMIT–A7
21
12C7100B AVERAGING
TEMPERATURE SENSOR MAY BE SUBSTITUTED IF SPACE PERMITS.
REMOTE RETURN AIR SENSOR USED WITH T7080B ONLY.
Fig. 5. Connecting C7046B Air Temperature Sensor
for mixed air, cold deck and hot deck sensing, zone
discharge and optional remote return air sensing
in W7080 Multizone System.
C7046D XF521A/XF526
1
2
Fig. 6. Connecting C7046D Air Temperature
Sensor to Excel 500 Control System.
60 NO JUMPER
3456
45
55
55 NO JUMPER
3456
90
110
130 NO JUMPER
24 Vdc
78
–+
+24 VDC
C7046B
(OR C7100B)
REMOTE RETURN
AIR SENSOR
(IF USED)
1
2
T7080A,B
7
6
5
4
2
1
AI 1
2
3
AI 2
4
5
AI 3
6
7
8
AI 4
9
10
AI 5
11
12
AI 6
13
14
AI 7
15
16
AI 8
17
18
1
2
3
8
(OR C7100B)
MIXED AIR
SENSOR
(OR C7100B)
COLD DECK
SENSOR
(OR C7100B)
HOT DECK
SENSOR
C7046B (OR C7100B) ZONE (N) DISCHARGE SENSOR
M2825
C7046B
C7046B
C7046B
M17966
C7046A,B,C,D AIR TEMPERATURE SENSORS
OPERATION AND CHECKOUT
Operation
The C7046A,B,C Air Temperature Sensors consist of a thermistor sensing element mounted in a tubular probe. They are applied at various locations throughout single zone and multizone duct systems. The negative temperature coefficient (NTC) characteristic of the thermistor element causes its resistance to decrease as the sampled air temperature increases. This resistance shift is balanced with other system sensor signals by appropriate system logic panels to stabilize system control.
The C7046D Air Temperature Sensor consists of a platinum thin film sensor element mounted in a tubular probe. It can be applied at various locations throughout single zone and multizone duct systems. The positive temperature coefficient (PTC) characteristics of the platinum thin film element causes its resistance to increase as the sampled air temperature increases. This resistance shift is balanced with other system sensor signals by the Excel 500 Control System.
Checkout
Allow the C7046 Air Temperature Sensor to soak in the air moving through the duct or plenum for a minimum of five minutes before taking a resistance measurement.
1. Disconnect the sensor leadwires from the associ­ated system components.
2. Connect an ohmmeter across the leadwires.
3. Assure nominal resistance measurements are in
accordance with the resistance/temperatu re curves shown in Figs. 7, 8 and 9.
4. Reconnect sensor leadwires to associated system components.
5. Check operation of the complete control system.
17000
16000
15000
14000
13000
12000
11000
10000
9000
8000
7000
6000
RESISTANCE (OHMS)
5000
4000
3000
2000
1000
0-10
TEMPERATURE (DEGREES)
605040 70
5
15
Fig. 7. C7046A,C Sensor resistance vs. temperature.
2010
3,000 OHMS AT 77 F (25 C)
8010 20 30 90 100
30 35
25-5
M17969
F
C
3 62-0216
C7046A,B,C,D AIR TEMPERATURE SENSORS
120000
100000
80000
60000
40000
20000
0
RESISTANCE (OHMS)
20
-7 50 60
50 70 90
30
40
0 10 20 30 40
5 15 25
22,800 OHMS AT 77 F (25 C)
60 80 100
TEMPERATURE (DEGREES)
35
110
120
45 55
130
M17973
Fig. 8. C7046B Sensor resistance vs. temperature.
RESISTANCE (OHMS) 1159
1141
1126
F
140
C
1111
1096
1081
1066
1051
60 65 70 75 80 85 90 95 100 105
55
13 15
20
TEMPERATURE (DEGREES)
1097 OHMS AT 77 F [25 C]
25
30 35 38 41
M2826
F
C
Fig. 9. C7046D Sensor resistance vs. temperature.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
62-0216 B.B. 11-04 www.honeywell.com
Loading...