Honeywell C7046A User Manual

C7046A,B,C,D
)
D
)
A
(25)
3
)
)1 (25)
)
)
GASKET
R
)
USH
)
C
G
Air Temperature Sensors
INSTALLATION INSTRUCTIONS
APPLICATION
The C7046 series of Air Temperature Sensors function as primary and/or secondary sensors in electronic control systems.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
The sensor assembly (see Fig. 1) consists of an aluminum sensor probe (element housed internally) with attached flange that can be mounted on a flat duct or plenum surface, or in a 2 in. by 4 in. (51 by 102 mm) junction box using two No. 8 screws. Connections to the sensor are made through two 6 in. (152 mm) leadwires.
2 (51
/4 (19
5/16 (9) DIAMETE
(BUSHING
INSERTION LENGTH DEPENDS UPON THE MODEL.
1
Fig. 1. C7046A,B,C,D Air Temperature
Sensor dimensions in in. (mm).
8 (203
PLASTI
BUSHIN
LOCKING P
NUTS (2
1/4 (6
IAMETER (2 HOLES
1/16 (2
NEOPRENE
M22402
NOTE: Sensor probe diameter is 1/4 in. (6 mm).
Location
The sensor should be located in the air duct or plenum where it will sample an average air temperature. Avoid locations where air stratification can cause sensing errors.
Mounting
Mounting on Flat Duct or Plenum Surface (Fig. 2)
1. Cut a 3/8 in. (9.5 mm) hole in the duct or plenum surface at the desired location.
2. Insert sensor probe into the duct or plenum until the flange rests against the duct or plenum wall.
3. If necessary, use the flange as a template to mark and drill two holes for No. 8 mounting screws.
4. Fasten the sensor to the duct or plenum surface with two No. 8 sheet metal screws (not provided).
Mounting in a Junction Box (Fig. 3)
1. Cut a 3/8 in. (9.5 mm) hole in the duct or plenum surface at the desired location.
2. Remove the center rear knockout from the junction box and insert the sensing probe through the knockout with the flange flat against the outlet box.
3. Using the flange as a template, mark and drill two holes in the junction box and the duct or plenum surface for No. 8 mounting screws.
4. Insert sensor probe through both the junction box knockout and the 3/8 in. (9.5 mm) hole drilled in the duct or plenum and fasten the junction box and sensor to the duct or plenum surface.
® U.S. Registered Trademark Copyright © 2004 Honeywell International Inc. • All Rights Reserved
62-0216
C7046A,B,C,D AIR TEMPERATURE SENSORS
SENSO
OBE
GE
)
S
(
)
O
E
SYSTEM
COMPO
S
CO
O
S
(
)
A
SENSO
E
SYS
DUCT O
UM
GE
S
Y
CONDU
OX
CONNECTOR
CONDUIT
E
(
)
SYS
COMPO
S
CO
S
W
)
A
S
)
R
PR
T APPROPRIAT
NENT
M22403
Fig. 2. Mounting C7046 Air Temperature Sensor on a flat duct or plenum surface.
TANDARD UTILIT
IT B
LOCKNUT
TO APPROPRIATE
TEM
NENT
TEM
R
PLEN
Fig. 3. Mounting C7046 Air Temperature
Sensor in a junction box.
FLAN
R
PROB
NNECT SENSOR WIRE
ITH TWO WIRENUT
CONNECTORS (NOT PROVIDED
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
SYSTEM DUCT OR PLENUM
NO. 8 (4mm MOUNTING SCREW
NOT PROVIDED
FLAN
NNECT SENSOR WIRES WITH TW WIRENUT CONNECTOR
NOT PROVIDED
NO. 8 (4 mm) MOUNTING
CREWS (NOT
PROVIDED
FACEPLAT
OPTIONAL
M22404
CAUTION
Erratic System Operation Hazard. Failure to follow proper wiring practices can introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large
inductive loads such as motors line starters, lighting ballasts, and large power distribution panels.
Shielded cable is required in installations where
these guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
1. All wiring must agree with applicable codes, ordinances and regulations.
2. Do not mount sensor in incorrect environment.
3. Wire according to the applicable controller instructions.
4. Erratic temperature readings from a sensor can be caused by improper wiring practices. These must be avoided to assure proper operation:
•Avoid poor wiring connections.
•Avoid intermittent or missing building earth
ground.
•Do not mount sensor in incorrect environment.
Connect low voltage wiring from the sensor to the appropriate system component terminals using solderless connectors. See Fig. 3.
NOTES:
1. For connections to the W973 Single Zone
Logic Panel, see Fig. 4.
2. For connections to the W7080 Multizone
System, see Fig. 5.
3. For connections to the Excel 500 Control
System, see Fig. 6.
4. For additional wiring information, refer to the
appropriate specification.
W973 LOGIC PANEL
SENSOR STAT 24 VAC ECONO
C +20 H N
TT134251TRTRWBY
C7046A
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. Connecting C7046A Air Temperature Sensor to a W973 Single Zone Logic Panel.
1
L1
L2
(HOT)
R
M17965
62-0216 2
Loading...
+ 2 hidden pages