Honeywell C7044A, C7927A, C7035 User Manual

C7027A, C7035, C7044A, C7927A
Minipeeper® Ultraviolet Flame Detectors
C7027A
C7044A

APPLICATION

The C7027A, C7035A, C7044A and C7927A Minipeeper® Ultraviolet Flame Detectors detect the ultraviolet radiation emitted by combustion flames. The flame detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil, or combination gas-oil burners.

FEATURES

• C7027A, C7035A, and C7044A Flame Detectors are used with RA890G devices or R7249A, R7290A, R7749B and R7849A,B Amplifiers and the appropriate Honeywell controls.
C7035A
C7927A
PRODUCT DATA
• C7044A may also be used with the following 50 Hz Honeywell combustion controls/amplifiers: — R4341/R7323 — R4343/R7323 — R4344/R7323
• C7027A has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half-inch sight pipe.
• C7035A has an integral collar threaded (internal 1-11-1/2 NPSM) for mounting on a one-inch sight pipe.
• C7035A housing meets Underwriters Laboratories Inc. requirements for rain tightness and complies with NEMA enclosure standards, types 4 and 4X.
• C7044A mounts with a two screw bracket. The UV sensor tube is enclosed in a stainless steel housing.
• C7044A has the capability of side or end viewing in flame monitoring applications.
• Because of their compact size, the C7027A and C7044A are particularly suitable for blast tube mounting.
• Properly installed, the C7027A, C7035A and C7927 are pressure rated for 5 psi.
• C7035A ultraviolet radiation sensor tube is field replaceable.
• Two C7027A, C7035A or C7044A Flame Detectors can be wired in parallel for difficult flame sighting installations.
• C7927A is used with only the R7851B Flame Amplifier and the 7800 SERIES controls.
• C7927A has an integral collar threaded (internal 1/2-14 NPSM) for mounting on a one-half inch sight pipe.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Wiring (All Models—Fig. 10) ............................................. 8
Adjustments and Checkout .............................................. 9
Troubleshooting ................................................................ 12
Maintenance ..................................................................... 12
60- 2026- 11
C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS
E
.
S.

SPECIFICATIONS

4 (102)
3-1/2 (89)
COLLAR WITH 1/2-14 NPSM INTERNAL THREADS
1
C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES. C7027A1114 HAS 44 IN. (1.118 M) LEADWIRES WITH 22 IN. (558 MM) FLEXIBLE CONDUIT. MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL
2
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.
C7027
Fig. 1. Installation dimensions of C7027A in in. (mm).

C7027A Minipeeper® Ultraviolet Flame Detector:

Ambient Operating Temperature Ratings: 0°F to 215°F
(-18°C to 102°C), or -40°F to 215°F [-40°C to +102°C), depending on model.
Maximum Pressure Rating: 5 psi (34.5 kPa).
Mounting: Collar with 1/2-14 NPSM internal threads for
mounting on a 1/2 in. sight pipe.
Wiring Connections: Two 8 ft (2.44 m), color-coded,
NEC Class 1 leadwires, rated for 221°F (105°C). (C7027A1064 has 24 ft [7.32 m] leadwires.) Rear of detector has a clamp type connector for 1/2 in. flexible metallic conduit. (Models are available with 1/2 in. internally threaded spud connector instead of the clamp). C7027A1114 has 44 in. (1.118 m) leadwires and 22 in. (558 mm) flexible conduit.
8 FOOT (2.44 METER) LEADWIRES (2)
2
1-1/16
(27)
1
M1943
Dimensions: See Fig. 1.
Replacement Part: 129685 Flange Gasket.
NOTE: The ultraviolet radiation sensing tube is not field
replaceable.
Accessory:
136733 Heat Block, laminated plastic, insulating the
flame detector from sight pipe temperatures up to 266°F (130°C), 1/2-14 NPSM external threads on one end and 1/2-14 NPSM internal threads on the other end (see Fig. 8). Included with C7027A1080.
390427B Bushing, for mounting to 3/8 in. sight pipe. Included
with C7027A1080.
4-1/8 (105)
31/32
(25)
2
M1945C
COLLAR WITH 1–11-1/2 NPSM INTERNAL THREADS
INSERTION DEPTH
1 2 3
1
2-5/8 (67)
DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREAD C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES.
2 (51)
1-3/16
(30)
6 FOOT [1.83 METER] LEADWIRES (2)
1/2-14 NPSM INTERNAL THREADS
1-1/2
(38)
3
C7035
Fig. 2. Installation dimensions of C7035A in in. (mm).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
60-2026—11 2
C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS
6 L
B

C7035A Minipeeper® Ultraviolet Flame Detector:

Flame Detection: End viewing.
Ambient Operating Temperature Ratings: 0°F to 250°F
(-18°C to +121°C), or -40°F to 250°F (-40°C to +121°C), depending on model.
Maximum Pressure Rating: 5 psi (34.5 kPa).
Mounting: Collar with 1-11-1/2 NPSM internal threads for
mounting on a 1 in. sight pipe. (The DIN approved C7035A1064 has 1-11 BSP.P1 threads.)
Wiring Connections: Two 6 ft. [1.83 m], color-coded
NEC Class 1 leadwires rated for 302°F (150°C). One model is available with 12 ft. (3.66 m) leadwires. Rear of detector has 1/2-14 NPSM internal threads for connecting to a conduit. The DIN-approved C7035A1064
has 1/2-14 BSP-F threads. C7035A1056 has 12 ft (3.66 m) leadwires. C7035A1080 leadwire is rated for 600°F (204°C).
FOOT [1.83 METER] EADWIRES (2)
Dimensions: See Fig. 2.
Replacement Parts:
129808 Flange Gasket. 129464M Ultraviolet Sensing Tube, 0°F to 250°F
(-18°C to +121°C).
129464N Ultraviolet Sensing Tube, -40°F to +250°F
(-40°C to 121°C).
C7027A, C7035A AND C7044:
Approvals:
Underwriters Laboratories Inc. listed: File No. MP268. Canadian Standards Association certified:
Master Report LR 95329-1. Factory Mutual approved. Industrial Risk Insurers acceptable. DIN approved models: C7027A1056, C7035A1049,
C7035A1064.
General Accessories:
118367A Swivel Mount; provides adjustable positioning of
the C7027A or C7035A. 204342 Ultraviolet mirror, 3/4 in. NPT. 105172C Seal off adapter, 3/4 in. NPT.
MOUNTING BRACKET
3/8
(10)
7/8
(22)
9/16 (14)
1/2
3-5/8 (92)
(13)
C7044
1-27/64
(36)
M1944
Fig. 3. Installation dimensions of C7044A in in. (mm).

C7044A Minipeeper® Ultraviolet Flame Detector:

Flame Detection: Housing has two openings to permit either side or end viewing. Side viewing is 1/8 as sensitive as end viewing.

C7927A Minipeeper® Ultraviolet Flame Detector:

Ambient Operating Temperature Ratings:
C7927A1016 (U.S. Version): -40°F to +200°F
(-40°C to +93°C). C7927A1008 (European Version): -4°F to +140°F
Mounting: Bracket (included in 4074BVK Bag Assembly),
secured by two 8-32 RHIS (European M-4) screws (not included).
Wiring Connections: Two 6 ft. (1.83 m) color-coded NEC
Class 1 leadwires. Rear of detector has a clamp type connector for 1/2 in. flexible metallic conduit.
Dimensions: See Fig. 3.
(-20°C to +60°C).
Storage Temperature Rating: -20°F to +120°F
(-28°C to +49°C).
Maximum Pressure Rating: 5 psi 34.5 kPa).
Mounting: Collar with 1/2-14 NPSM internal threads for
mounting on a 1/2 in. (13mm) sight pipe.
Wiring Connections: Two four-foot (1.2 meter) color-coded
NEC Class 1 leadwires. Rear of detector has a clamp-type
connector for 1/2 in. (13mm) flexible metal conduit.
Dimensions: See Fig. 4 and 5.
Approvals:
Underwriters Laboratories Inc. (cUL), MP268, Volume 30. Factory Mutual (FM): Pending.
3 60-2026—11
C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS
3
4
-11/16 (94)
1 (25)
6-1/2 FT. (1.98M)
C7927A1008
3-1/4 (82)
C7927A1016
3-3/4 (95)
4 FOOT (1.2 METER) LEADWIRES (2)
1
(25)
M17783
Fig. 4. Installation dimensions of C7927A1016 (U.S.A. version) and C7927A1008 (European version) in in. (mm).

INSTALLATION

IMPORTANT
Ultraviolet radiation sensing tubes have a life expectancy of 40,000 hours of continuous use within

When Installing This Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced, flame safeguard control technician.
the flame detector's specified ambient temperature and voltage ratings. Wearout of an ultraviolet radiation sensing tube results in failure of the UV sensor to properly discriminate between flame conditions.
The C7027A, C7035A and C7044A Flame Detectors should only be used on burners that cycle on/off periodically or, in the absence of cycling, are periodically checked for proper operation.
4. After installation is complete, check out product operation as provided in these instructions.
Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. All wiring must comply with applicable electrical codes, ordinances and regulations. Use NEC Class 1 wiring.
Recommended industry standards for the frequency of sensor checks, either through cycling (employing safe-start check methods) or periodic maintenance, vary between once every ten seconds and once every week, depending on the standard used and the application needs.
M1778
Consult the equipment manufacturer or the governing standard for recommendations about frequency of checks.
Controls incorporating safe-start checks, and sensors and controls employing constant check means are available from Honeywell. See your Honeywell representative for specific information.
60-2026—11 4
Loading...
+ 8 hidden pages