The C7027A, C7035A, C7044A and C7927A Minipeeper®
Ultraviolet Flame Detectors detect the ultraviolet radiation
emitted by combustion flames. The flame detectors are used
with Honeywell flame safeguard controls to provide flame
supervision for gas, oil, or combination gas-oil burners.
FEATURES
• C7027A, C7035A, and C7044A Flame Detectors are
used with RA890G devices or R7249A, R7290A,
R7749B and R7849A,B Amplifiers and the appropriate
Honeywell controls.
C7035A
C7927A
PRODUCT DATA
• C7044A may also be used with the following 50 Hz
Honeywell combustion controls/amplifiers:
— R4341/R7323
— R4343/R7323
— R4344/R7323
• C7027A has an integral collar threaded (internal
1/2-14 NPSM) for mounting on a one-half-inch sight
pipe.
• C7035A has an integral collar threaded (internal
1-11-1/2 NPSM) for mounting on a one-inch sight pipe.
• C7035A housing meets Underwriters Laboratories Inc.
requirements for rain tightness and complies with
NEMA enclosure standards, types 4 and 4X.
• C7044A mounts with a two screw bracket. The UV
sensor tube is enclosed in a stainless steel housing.
• C7044A has the capability of side or end viewing in
flame monitoring applications.
• Because of their compact size, the C7027A and
C7044A are particularly suitable for blast tube
mounting.
• Properly installed, the C7027A, C7035A and C7927 are
pressure rated for 5 psi.
• C7035A ultraviolet radiation sensor tube is field
replaceable.
• Two C7027A, C7035A or C7044A Flame Detectors can
be wired in parallel for difficult flame sighting
installations.
• C7927A is used with only the R7851B Flame Amplifier
and the 7800 SERIES controls.
• C7927A has an integral collar threaded (internal
1/2-14 NPSM) for mounting on a one-half inch sight
pipe.
C7027A1064 HAS 24 FOOT (7.32 METER) LEADWIRES.
C7027A1114 HAS 44 IN. (1.118 M) LEADWIRES WITH
22 IN. (558 MM) FLEXIBLE CONDUIT.
MODELS AVAILABLE WITH SPUD CONNECTOR (1/2-14 NPSM INTERNAL
2
THREADS) INSTEAD OF CLAMP TYPE CONNECTOR.
C7027
Fig. 1. Installation dimensions of C7027A in in. (mm).
C7027A Minipeeper® Ultraviolet
Flame Detector:
Ambient Operating Temperature Ratings: 0°F to 215°F
(-18°C to 102°C), or -40°F to 215°F [-40°C to +102°C),
depending on model.
Maximum Pressure Rating: 5 psi (34.5 kPa).
Mounting: Collar with 1/2-14 NPSM internal threads for
mounting on a 1/2 in. sight pipe.
Wiring Connections: Two 8 ft (2.44 m), color-coded,
NEC Class 1 leadwires, rated for 221°F (105°C).
(C7027A1064 has 24 ft [7.32 m] leadwires.) Rear of
detector has a clamp type connector for 1/2 in. flexible
metallic conduit. (Models are available with 1/2 in.
internally threaded spud connector instead of the
clamp). C7027A1114 has 44 in. (1.118 m) leadwires and
22 in. (558 mm) flexible conduit.
8 FOOT (2.44 METER)
LEADWIRES (2)
2
1-1/16
(27)
1
M1943
Dimensions: See Fig. 1.
Replacement Part: 129685 Flange Gasket.
NOTE: The ultraviolet radiation sensing tube is not field
replaceable.
Accessory:
136733 Heat Block, laminated plastic, insulating the
flame detector from sight pipe temperatures up to
266°F (130°C), 1/2-14 NPSM external threads on one
end and 1/2-14 NPSM internal threads on the other end
(see Fig. 8). Included with C7027A1080.
390427B Bushing, for mounting to 3/8 in. sight pipe. Included
with C7027A1080.
4-1/8 (105)
31/32
(25)
2
M1945C
COLLAR WITH
1–11-1/2 NPSM
INTERNAL
THREADS
INSERTION DEPTH
1
2
3
1
2-5/8 (67)
DIN APPROVED C7035A1064 HAS 1-11 BSP.P1 INTERNAL MOUNTING THREADS
DIN APPROVED C7035A1064 HAS 1/2-14 BSP-F INTERNAL MOUNTING THREAD
C7035A1056 HAS 12 FOOT (3.66 METER) LEADWIRES.
2 (51)
1-3/16
(30)
6 FOOT
[1.83 METER]
LEADWIRES (2)
1/2-14 NPSM
INTERNAL THREADS
1-1/2
(38)
3
C7035
Fig. 2. Installation dimensions of C7035A in in. (mm).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Ambient Operating Temperature Ratings: 0°F to 250°F
(-18°C to +121°C), or -40°F to 250°F (-40°C to +121°C),
depending on model.
Maximum Pressure Rating: 5 psi (34.5 kPa).
Mounting: Collar with 1-11-1/2 NPSM internal threads for
mounting on a 1 in. sight pipe. (The DIN approved
C7035A1064 has 1-11 BSP.P1 threads.)
Wiring Connections: Two 6 ft. [1.83 m], color-coded
NEC Class 1 leadwires rated for 302°F (150°C). One
model is available with 12 ft. (3.66 m) leadwires.
Rear of detector has 1/2-14 NPSM internal threads for
connecting to a conduit. The DIN-approved C7035A1064
has 1/2-14 BSP-F threads.
C7035A1056 has 12 ft (3.66 m) leadwires.
C7035A1080 leadwire is rated for 600°F (204°C).
FOOT [1.83 METER]
EADWIRES (2)
Dimensions: See Fig. 2.
Replacement Parts:
129808 Flange Gasket.
129464M Ultraviolet Sensing Tube, 0°F to 250°F
(-18°C to +121°C).
129464N Ultraviolet Sensing Tube, -40°F to +250°F
(-40°C to 121°C).
C7027A, C7035A AND C7044:
Approvals:
Underwriters Laboratories Inc. listed: File No. MP268.
Canadian Standards Association certified:
Master Report LR 95329-1.
Factory Mutual approved.
Industrial Risk Insurers acceptable.
DIN approved models: C7027A1056, C7035A1049,
C7035A1064.
General Accessories:
118367A Swivel Mount; provides adjustable positioning of
the C7027A or C7035A.
204342 Ultraviolet mirror, 3/4 in. NPT.
105172C Seal off adapter, 3/4 in. NPT.
MOUNTING BRACKET
3/8
(10)
7/8
(22)
9/16
(14)
1/2
3-5/8 (92)
(13)
C7044
1-27/64
(36)
M1944
Fig. 3. Installation dimensions of C7044A in in. (mm).
C7044A Minipeeper® Ultraviolet
Flame Detector:
Flame Detection: Housing has two openings to permit either
side or end viewing. Side viewing is 1/8 as sensitive as end
viewing.
C7927A Minipeeper® Ultraviolet
Flame Detector:
Ambient Operating Temperature Ratings:
C7927A1016 (U.S. Version): -40°F to +200°F
(-40°C to +93°C).
C7927A1008 (European Version): -4°F to +140°F
Mounting: Bracket (included in 4074BVK Bag Assembly),
secured by two 8-32 RHIS (European M-4) screws (not
included).
Wiring Connections: Two 6 ft. (1.83 m) color-coded NEC
Class 1 leadwires. Rear of detector has a clamp type
connector for 1/2 in. flexible metallic conduit.
Dimensions: See Fig. 3.
(-20°C to +60°C).
Storage Temperature Rating: -20°F to +120°F
(-28°C to +49°C).
Maximum Pressure Rating: 5 psi 34.5 kPa).
Mounting: Collar with 1/2-14 NPSM internal threads for
mounting on a 1/2 in. (13mm) sight pipe.
Wiring Connections: Two four-foot (1.2 meter) color-coded
NEC Class 1 leadwires. Rear of detector has a clamp-type
connector for 1/2 in. (13mm) flexible metal conduit.
Fig. 4. Installation dimensions of C7927A1016 (U.S.A. version) and C7927A1008 (European version) in in. (mm).
INSTALLATION
IMPORTANT
Ultraviolet radiation sensing tubes have a life
expectancy of 40,000 hours of continuous use within
When Installing This Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame
safeguard control technician.
the flame detector's specified ambient temperature
and voltage ratings. Wearout of an ultraviolet
radiation sensing tube results in failure of the UV
sensor to properly discriminate between flame
conditions.
The C7027A, C7035A and C7044A Flame Detectors
should only be used on burners that cycle on/off
periodically or, in the absence of cycling, are
periodically checked for proper operation.
4. After installation is complete, check out product
operation as provided in these instructions.
Disconnect power supply before beginning installation to
prevent electrical shock and equipment damage. All wiring
must comply with applicable electrical codes, ordinances
and regulations. Use NEC Class 1 wiring.
Recommended industry standards for the frequency
of sensor checks, either through cycling (employing
safe-start check methods) or periodic maintenance,
vary between once every ten seconds and once
every week, depending on the standard used and
the application needs.
M1778
Consult the equipment manufacturer or the
governing standard for recommendations about
frequency of checks.
Controls incorporating safe-start checks, and
sensors and controls employing constant check
means are available from Honeywell. See your
Honeywell representative for specific information.
60-2026—114