Honeywell 11280S User Manual

Herculine 11280S Smart Actuator
9/01
Page 1 of 14
Overview
Honeywell’s HercuLine 11280S Smart actuators incorporate all of the high quality and reliable features of the traditional HercuLine the added benefits of a microprocessor­based Enhanced Electronics Unit (EEU). These additional benefits provide:
Faster set-up and commissioning
Network capability
Health parameter monitoring for proactive maintenance planning.
HercuLine 11280S Smart actuators enable operation at maximum process efficiency, minimal downtime, and access to all actuator parameters for real-time business decisions.
Honeywell’s 11280S actuators are industrial rated and engineered for very precise positioning of dampers and valves. The HercuLine 11280S performs especially well in extremely demanding environments requiring continuous duty, high reliability, and low maintenance. Typical applications are ID/FD fan dampers, furnace pressure dampers, coal mill dampers, burner tilts and more.
actuators plus
Actuator Operation
Microprocessor-based electronics continually monitor the performance, health, and position of the actuator for repeatable positioning and response to demand signal.
A double reduction worm gear set combines with a variable speed motor controller (inverter) that is continuous duty rated for accurate and repeatable positioning of final control elements.
The worm gear set combination also functions as a brake, capable of holding greater than two times the output torque in a back-driving condition.
Figure 1 Herculine 11280S Smart Actuator
Control options are available to interface with a modulating 4-20 mA input signal and 4-20 mA customer feedback or remote setpoint through Modbus. Internal balance, customer feedback and patented slidewire emulation is provided by a non­contacting position sensor.
Features
Performance 
Accurate Positioning – Motor/gear train provides accurate positioning with almost instantaneous start/stop characteristics.
Non-Contact Position Sensing – Non-contacting sensing lowers maintenance costs and improves performance.
Duty Cycle – Continuous duty rated motor.
Specification
Full Travel Speed – Full stroke travel speeds as fast as 10 seconds.
Torque – High torque capability in small package (425 – 5,500 lb-ft).
High Accuracy – Typically 0.25 % of 90° span.
High Repeatability - Typically
0.2 % of 90° span.
Characterization – Linear, square root or programmable user­configured 21-point characterization allows tailoring of control for specific applications.
Input Filter Setting – Four programmable combinations of input filter settings are provided to accommodate various customers needs. The combinations are none, spike, low pass, or spike + low pass filter.
Deadband – Deadband is programmable between 0.2 % to 5 % of 90° span.
Sensing and Control, 11 West Spring Street, Freeport, Illinois 61032
Printed in U.S.A. © Copyright 2000—Honeywell
61-86-03-13 Page 2
Features (continued) Health Monitoring
Operation 
Control Signals – 0/4 to 20 mA, 0/1 to 5 Vdc, 0 to 10 Vdc, Digital remote setpoint (RS485 Modbus RTU protocol).
Output Signals – 0/4 to 20 mA, 0/1 to 5 Vdc and slidewire emulation.
Manual Operation – All 11280S series actuators are supplied with a manual handwheel to operate the actuator when power is not available.
Auto-Manual – electric handswitch with auxiliary contacts indicating an "Out-of-Auto" position is available for local electric control.
RS485/Modbus RTU Communication – Simple and
easy to use Modbus RTU communication is standard with all 11280S actuators allowing seamless networking of Honeywell control products.
Auxiliary Outputs – Two types of auxiliary outputs can be specified, SPDT switches or electromechanical relay outputs. Relay outputs can be programmed to output alarm conditions, provide control of other equipment, or indicate status.
Alarm Functions – Alarms may be assigned to relay outputs or may be accessed through Modbus. Alarms can be triggered from stall, temperature limits, motor cycle count, out of automatic mode, digital input, position, input failure, position sensor failure, power up failure, and more.
Local HMI Configuration – An integral keypad and high intensity display is available for non-intrusive local configuration of the actuator (Figure 2).
Configuration Security – Password protection is provided, allowing users to lock out some, all, or no groups of setup parameters to prevent tampering.
Factory Calibration – Factory calibration is stored in non-volatile memory and can be restored via the local HMI at any time.
Direction of Rotation – Direction of rotation on increasing input signal is programmable.
Split Range Operation – Split range is programmable and infinitely adjustable.
Digital Input Override – A digital input is provided and is programmable to provide override of all other input signals as an emergency override of control. The digital input can be programmed to drive the actuator open, closed, remain in-place, or to a user­specified position on contact closure.
Failsafe – When input signal exceeds high or low range limits (or input signal failure), the actuator can be programmed to drive open, closed, remain in­place, or drive to a user-specified position.
Construction 
Enclosure – Rugged, industrial grade enclosure.
Low Maintenance – Simple- proven design means high reliability/low maintenance.
Output Shaft Hardware – All 11280S series actuators are supplied with an adjustable radius crank arm. Optional linkage kits are available.
Limit Switches – Two end-of- travel electric limit switches are supplied as standard equipment with all 11280S series actuators.
Warranty – Exceptional warranty.
A standard feature on all 11280S actuators accumulates information about actuator operation. This information then can be used to evaluate and determine predicted or scheduled maintenance periods. The parameters that are monitored include: accumulated stall time, thermal operating rating of the actuator exceeded, number of motor starts in a region of motor travel, total travel and current actuator travel.
Non-Contact
Position Sensing
Honeywell 11280S series actuators implement a variable inductance, non­contact position sensor mounted directly to the actuator output shaft providing precision position sensing from 0 to 90 degrees, (Figure 3). This technology eliminates maintenance items such as wipers, bearings, as well as static friction, hysteresis and electrical noise over a wide range of demanding environmental conditions.
Slidewire Emulation
The Slidewire Emulation Circuit (SEC) emulates the proportional voltage output of a typical slidewire through a high impedance circuit. The voltage output is proportional to the supply voltage and shaft position. A non­contact position sensor is used to determine shaft position in place of the slidewire.
61-86-03-13
Page 3
Local Display and Keypad
Configuration and set-up is through the local HMI, consisting of a display and keypad interface (Figure 2). A high intensity 10-character LED display and simple pushbuttons provide quick access for actuator set up and status information. If relay outputs are specified, all configuration can be done through either the local HMI interface. If mechanical switches are specified, then the user must manually set the auxiliary output.
Control Arm Rotation
CCW CW
Upper Display (Four Characters)
Lower Display (Six Characters)
Indicators
STALLED
ALARM
MANUAL
AUTO
LED Status Indicators
Pushbuttons to Access Actuator Set Up, Status and Calibration Parameters.
Non-Contact Sensor Sensing PWA
FUNCTIONSET UP
MAN/AUTO
DISPLAY
Figure 2 Local HMI (Display and Keypad)
Non-Contact Sensor Spoiler
Figure 3 Non-Contact Sensor Assembly
61-86-03-13 Page 4
Set Up/Configuration Parameters
Configuration parameters are logically grouped and accessed using the local HMI. Actuator calibration is also accomplished through a simple procedure using the keypad. By pressing the SETUP button on the HMI, you can step through the set up groups that contain all of the configuration parameters. The table below summarizes the configuration parameters available within the various set up groups. Full details of all configuration parameters are found in the 11280S Series Smart Actuator Installation, Operation and Maintenance Manual, document number 61-86-25-09.
Set Up Group Configuration Parameter Selections/Settings
SET INPUT Selects various
parameters that define actuator
operation.
SET RELAY When the actuator is equipped with optional relays, this set up group allows you to set relay action for various actuator operating conditions. Contact closure can be wired to external annunciators or alarm points to indicate conditions for any of the Relay Types.
SET CUROUT Selects the current (or voltage) output range of the actuator.
SET COMM Actuator can be defined as a master or slave device on a Modbus RTU RS-485 loop. Operating setpoint can be transmitted to the actuator and operating status can be read when connected to supervisory control systems.
SET DIGINP Selects digital input action upon contact closure.
SET DISPLA Selects desired decimal places and engineering units for local display.
CAL INPUT, MTR, CURENT If needed, calibration of the actuator input, motor position and actuator output can be performed using the local keypad and display.
IN TYP – Input Actuation Type
INP HI – Input High Range Value
INP LO – Input Low Range Value
FILTYP – Input Filter Type
LPFILT – Low Pass Filter Time Constant
Direct – Actuator Rotation
RTYPnn – Relay Type
Input Range Position Range Deviation Upper or Lower Limit Travel Temperature High or Low Motor Starts Motor Stalled Manual Mode Power Up Test Failure Input Signal Failure Position Sensor Signal Failure Digital Input Closure
CUROUT - Output Signal Range
4 – 20 mA, 0 – 20 mA, 1 – 5V, 0 – 5V, SW E (Slidewire Emulation)
COMM – Communications Parameters
ADDRES – Device Address
BAUD – Baud Rate
XmtDLY – Response Delay
DBLBYT – Floating Point Data Format
DIGINP – Digital Input State
Endpos – End Position Value
DECMAL – Decimal Point Location
EUNITS – Units Display
UNITS – Display Units
Dband – Input Deadband
FsTYP – Failsafe Type
FsVAL – Failsafe Value
CHAR – Input Characterization
LDCAL – Restore Calibration Type
RnnE – Relay Count Multiplier
RnnVAL – Relay Value
Rnn HL – Relay High/Low
RLYnHY – Relay Hysteresis
Continued on next page ⇒
Set Up Group Configuration Parameter Selections/Settings
61-86-03-13
Page 5
SET LOCKEnables lock
out or access to selected set up group parameters and calibration values.
READ STATUS
Displays failsafe condition and the results of various diagnostics performed during power up.
SET DRVINF Allows access to actuator device information.
SET MAINT Allows access to parameters that monitor operating conditions.
Physical
LOCKID – Set Security Password
LOCK – Lock Out
FAILSF – Failsafe
RAMTST – RAM Test Diagnostic
SEETST – Serial EEPROM Test Diagnostic
VERSON – Firmware Version
SPEED – Stroke Speed
POWER – Power Input Voltage and Line Frequency
TAG – Tag Name
TEMP – Actuator Temperature
TEMPHI – High Temperature Limit
TEMPLO – Low Temperature Limit
ACST – Accumulated Motor Stall Time
STARTS – Accumulated Motor Starts
Specifications – General
CFGTST – Configuration Test Diagnostic
CALTST – Calibration Test Diagnostic
MFGDAT – Manufacturing Date
LREP – Date of Last Repair
LCAL – Date of Last Field Calibration
REPTYP – Repair Type
RLnCNTS – Relay Cycle Counts
REGNn – Accumulated Motor Starts (Regions of Travel)
TOTDEG – Total Degrees of Motor Travel
MANRST – Reset Maintenance Statistics
Enclosure
Gear Train
Operating Temperature
Storage Temperature
Relative Humidity
Crank Arm
Rotation
Direction of Rotation
Manual Handwheel
Lubrication
Weight
Precision-machined ductile iron with corrosion resistant paint
Precision-machined double reduction worm gear
-30 °C to +65 °C (-20 °F to +150 °F) except Model 11287S which has a range of: -20 °C to +65 °C (-4 °F to +150 °F)
-40 °C to +93 °C (-40°F to +200 °F)
0-99% R.H. noncondensing, over the full operating temperature range.
Adjustable radii (8” to 14”) crank arm is standard
Factory set to 90 degrees, for 0% to 100% travel
Field programmable via local display and keypad
Provides a means of positioning the actuator in the event of a power failure or set-up
Mobil Synthetic bearing and gear lubricant SHC 634 (ISO 460) or equivalent
300 lb to 600 lb (136 kg to 272 kg)—See Table below for more information.
Specifications continued on next page ⇒
Loading...
+ 9 hidden pages