Read this owner information to become familiar with the capabilities and use
of your appliance. Keep this with literature on other appliances where you
have easy access to it in the future. If a problem occurs, check the instructions
and follow recommendations given. If these suggestions don’t eliminate your
problem, call your installing contractor or distributor in your area.
INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to do
it effi ciently. Effi ciency means less cost to you while keeping you comfortable.
WHY YOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY
1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by
this same coil.
2. Air is then delivered through the main duct, via registers, into your home.
3. Return air is drawn through the return register.
4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidifi ed. Then the cycle begins again.
Page 2
SECTION 1.
OWNER INFORMATION
make sure it’s working right, clean or change
fi lters and make any needed adjustments.
OPERATING INSTRUCTIONS
To Turn On Air Conditioner
If you have a heating/cooling thermostat:
1. Set the system switch to “Cool.”
2. Set the thermostat at the temperature level
you desire.
3. Turn the power on. Your air conditioner
should start as soon as room temperature
rises above the setting on the thermostat.
If you have one thermostat for heating
and another for cooling, they must be
interlocked to prevent simultaneous
operation (See Figure 1):
1. Turn the heating thermostat to its lowest
possible setting.
2. If the cooling thermostat has an “On/Off”
switch, turn it “On.”
3. Set the cooling thermostat to the desired
temperature.
4. Turn the power on. Your air conditioner
should start when room temperature exceeds the thermostat setting.
To Shut Off Air Conditioner
If you have a heating/cooling thermostat:
1. Turn the system switch to “Heat” or “Off.”
2. Turn the thermostat to the desired heating
temperature setting.
3. If you are turning your air conditioner off for
the winter or an extended period, shut off
the power to the air conditioner.
If you have one thermostat for heating
and another for cooling, they must be
interlocked to prevent simultaneous
operation (See Figure 1):
1. Turn your cooling thermostat “Off” or to its
highest setting.
2. Turn the heating thermostat to the desired
temperature.
3. If you are turning your air conditioner off for
the winter or an extended period, shut off
the power to the air conditioner.
In addition, follow these simple rules:
1. Never run your system without fi lter. If you
do, the cooling coils will get dirty and may
become clogged.
2. Set your thermostat at the comfort level you
wish -- and then leave it alone. Let it control
the operation of the air conditioning system.
If you get chilly, turn it up a degree at a time
until comfort is restored.
3. It takes longer for an air conditioner to cool
your dwelling than it does for your furnace
to heat it. So . . . don’t turn the unit on and
expect a dramatic drop in temperature, at
least not right away. If your home is hot and
humid, the temperature will drop slowly.
4. Check your fi lters every ten days in summer
to see if they are dirty. To keep them clean,
use a mild solution of detergent and water
on washable types. Replace non washable
fi lters.
5. Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.
If your air conditioner isn’t working:
1. Make sure the fuses are not blown or that
your circuit breakers are on.
2. See that your thermostat is set at the desired
temperature and that your system’s switch
is on “Cool.”
3. For free air fl ow, make sure your return
register is not covered and that the fi lter is
clean.
4. Check the outdoor condenser coil and make
sure it is clean and not clogged with grass
or leaves.
If your air conditioner still isn’t working, call your
nearest distributor.
Cooling
Thermostat
R
Double Throw
Double Pole Switch
Furnace
Thermostat
R
BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the
start of each air conditioning season. He will
2
To Air Conditioner
To Furnace
Figure 1. Thermostat Interlock System
Page 3
SECTION 2.
INSTALLER INFORMATION
GENERAL
Read the following instructions completely
before performing the installation.
These instructions are for the use of qualifi ed
personnel specially trained and experienced
in the installation of this type of equipment
and related system components. Some states
require installation and service personnel to
be licensed. Unqualifi ed individuals should not
attempt to interpret these instructions or install
this equipment.
is any question concerning the power supply,
contact the local power company.
Inspecting Equipment: All units are securely
packed at the time of shipment and, upon arrival,
should be carefully inspected for damage. Claims
for damage (apparent or concealed) should be
fi led immediately with the carrier.
INSTALLATION
1. SELECT THE BEST LOCATION FOR THE
AIR COND ITIONING UNIT
IMPORTANT: DO NOT PLACE UNIT UNDER
THE HOME.
The single packaged air conditioners are designed for outdoor installation only and can be
readily connected into the high static duct system
of a home. The only connections needed for
installation are the supply and return ducts, the
line voltage, and thermostat wiring. A complete
air conditioning system typically consists of:
• Single Package Air Conditioner
• Home Fittings Kit
• Unit Fittings Kit
• Thermostat
The single package air conditioner is completely
assembled, factory wired, and factory run tested.
The units are ready for easy and immediate
installation.
PRE-INSTALLATION CHECK
Before any installation is attempted, the cooling load of the area to be conditioned must be
calculated and a system of the proper capacity
selected. It is recommended that the area to
be conditioned be completely insulated and
vapor sealed.
The installer should comply with all local codes
and regulations which govern the installation
of this type of equipment. Local codes and
regulations take precedence over any recommendations contained in these instructions.
Consult local building codes and the National
Electrical Code (ANSI CI) for special installation
requirements.
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level,
and parallel to the home.
• The hot condenser air must be discharged
up and away from the home, and if possible,
in a direction with the prevailing wind.
• Do not place the unit in a confi ned space.
• If practical, place the air conditioner where it
and the ducts will be shaded from the afternoon sun when the heat load is greatest.
• Try to select a site for the unit that is as close
as possible to the proposed return grille location.
• Keep in mind that the length of the supply and
return ducts should be kept to a minimum with
no sharp radiused bends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked
at the installation site to minimize damage due
to handling.
CAUTION:
Do not tip the unit on its side. Oil
may enter the compressor cylinders
and cause starting trouble. If unit has
been set on its side, restore to upright
position and do not run for several
hours. Then run unit for a few seconds.
Do this three or four times with fi ve
minutes between runs.
The electrical supply should be checked to determine if adequate power is available. If there
a. Remove the bands from around the unit.
b. Unfold the top and bottom cap fl anges.
c. Carefully remove the top cap and tube.
3
Page 4
6 ft.
24"
12"
12"
Figure 2. Minimum Unit Clearances
3. INSTALL THE RETURN AND SUPPLY AIR
FITTINGS ON THE UNIT
The supply and return fi ttings are included with
select models. If supplied, the duct fi ttings are
shipped in the supply duct. They attach to the unit
openings with a fl ange and bead arrangement,
secured with two sheet metal screws. Note: For
ease of access, install fi tting before positioning
unit in fi nal location.
SUPPLY DUCT
Position the supply duct collar, if supplied, so the
edge of the unit opening fi ts between the fl ange
and the bead. Overlap the collar ends keeping the
small screw holes underneath. Align the holes in
the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fi tting. Re-tighten when installation is complete.
Tap collar as necessary to ensure engagement
with unit opening and install second screw.
Tighten fi rst screw. Rotate collar clockwise so
joint is near three o’clock position.
RETURN DUCT
Align the 14” return duct slots with the holes in
the collar and install two screws. Position the
collar over the opening and align the four notches
in the collar with the four dimples in the panel.
Using self-drilling screws (10-16x.5) attach the
collar to the rear panel.
4. LOCATING AND INSTALLING THE RETURN AIR ASSEMBLY
To avoid complications, locate and install the
return air assembly fi rst. The return air box
with grille and fi lter (Figure 4) should not be
located in heavy traffi c areas like hallways or
center of rooms. A good spot is in a corner or
under a table, if a minimum two inch clearance
is available. If desired, the return opening can
be located inside a closet with louvered doors
that have an open area equal to or greater than
the 12” x 20” grille furnished. The return air grille
can be placed in the wall of a closet and the air
ducted into the fi lter box through a boxed-in area
at the closet fl oor level. Make sure the fi lter is
readily accessible.
After determining the location of the return air
opening, start the installation from under the
home by cutting a small hole in the fi ber underboard to determine how the fl oor joist location
will affect cutting the opening needed for the box.
Floor joists generally are located on 16” centers,
leaving 14-3/8” between joists. After measuring
the return air box (approximately 12-1/4” x 141/4”), cut the hole through the fl oor so that the
box will fi t between the fl oor joists. Care should
be taken when cutting through carpeting to avoid
snags. In most installations it will be necessary to
cut a similar hole in the fi berboard directly under
the hole in the fl oor. However, if the fl oor is more
Transition Duct Screws
Supply Air
14” Duct Dimples
Return Air
Figure 3. Return and Supply Air FittingsFigure 4. Return Air Box
4
Page 5
than ten inches deep, it will only be necessary
to cut a hole for the collar on the return air box
or for the insulated duct.
Set the box into the opening and fasten with
screws or nails. Put the fi lter and return air
grille in place.
5. LOCATING AND INSTALLING THE
SUPPLY DAMPER(S)
Figure 5. Supply Damper
CAUTION:
When a home is not equipped with a
make-ready kit means must be provided to prevent simultaneous operation of the heating and cooling units.
A heat/cool thermostat is available for
this purpose.
When installing this air conditioning
system in conjunction with a furnace,
a damper must be installed in the furnace base assembly to prevent cold
air being discharged around the heat
exchanger. Damage to the heat exchanger and asphyxiation may occur
if a damper is not installed.
Check with the furnace manufacturer
for damper requirements. Failure to
install the required furnace damper
may invalidate code agency listing and
limited warranty on the furnace.
if the damp
over all tabs fl at on the inside of the heat duct.
Seal the opening between the fi berboard and
damper or fl exible duct.
DUCTING SYSTEM
DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more effect on the performance of an air conditioning
system than any other factor. The duct must be
suffi ciently large to conduct an adequate amount
of air to each register.
THE AIR CONDITIONING OUTPUT OF THE
SYSTEM WILL NOT COOL THE HOME IF THE
AIR IS LOST TO THE OUTSIDE THROUGH
LEAKS IN THE DUCT SYSTEM. ALSO, DUCTS
WHICH ARE COLLAPSED OR RESTRICTED
BY FOREIGN OBJECTS WILL PREVENT
ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may be
necessary to add an additional return air duct and
or supply to achieve maximum performance and
prevent coil icing and refrigerant fl ood back.
When locating the supply damper(s), carefully
check fl oor joists and frame members that could
interfere with the installation of the damper or
fl exible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from
the nearest register. The round supply opening
in the slanted side of the damper should face
the side of the home where the air conditioner
is located. To locate the center of the heat duct,
fi rst cut a small hole in the fi berboard below the
duct at the desired location. After locating the
duct center, cut a hole approximately 3/4” larger
than the damper opening in the fi berboard. Cut
a 9-1/8” x 13-1/8” hole in the duct and bend
over all tabs fl at on the inside of the heat duct.
After inserting the damper into the duct, bend
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
a. The supply duct for all units is twelve inches
in diameter. The return duct is 14” diameter
for all air conditioning units.
b. The fl exible ducts can be connected to the
corresponding fi ttings with the clamps provided with the ducts. Note: All connections
should be leak tight or a loss in cooling
capacity will result.
c. The fl exible ducts may be cut to the required
length, see instructions packed with duct.
Keep all ducts as short and straight as possible. Avoid sharp bends.
d. Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories below.)
5
Page 6
TYPICAL APPLICATIONS
4
3
2
1
5
6
3
2
1
4
6
7
5
4
6
MULTIPLE DUCT APPLICATIONSINGLE DUCT APPLICATION
Ref. No.Description
1
2
3
4
12” x 20” Return Air
16” x 20” Air Filter
12” x 20” Grille
Supply Damper
5
6
7
14” Diameter Flex Return Duct
12” Diameter Flex Supply Duct
12” x 12” x 12” “Y” Fitting
Figure 6. Typical Applications
e. Once the inner duct is connected to the
proper fi tting, the insulation and plastic
sleeve should be pulled over the connection
and clamped.
f. For homes with multiple supply ducts or for
special applications, a Y fi tting is available
to divide the supply air so it can be ducted
to different areas of the home for more
effi cient cooling. Note: The Y fi tting should
be insulated for maximum performance.
Blower Speed — For optimum system
performance and comfort, it may be necessary
to change the factory set speed. See table 1 for
factory settings. To change the blower speed:
If Standard Motor:
1. Disconnect all electrical power to the
unit and remove the service panel.
2. Remove the motor lead from terminal #4 of
the blower relay. Cut the wire tie holding the
motor lead bundle. The motor leads are
color coded as shown in Figure 7.
3. If the desired heating blower speed is different
than the cooling speed, remove and discard
the jumper wire between terminals #6 and
#4. on the blower relay. Place the desired
heating blower speed lead on terminal #6
and the desired cooling blower speed
lead on terminal #4 of the blower relay. Use
another wire tie (fi eld supplied) to bundle the
remaining motor leads.
6
Page 7
If Fixed Torque Motor:
1. Disconnect all electrical power to the unit
and remove the blower panel.
2. Locate the orange and red wires terminated
to the blower motor. The orange wire controls
cooling operation while the red wire controls
heating operation.
3. Verify the required speed from the airfl ow
data found in fi gure 7. Place appropriate wire
on the appropriate motor speed tap for the
required airfl ow point.
Note: If the same speed is required for both
heating and cooling, remove either the red
or orange wire from the blower motor. Next,
obtain the jumper wire from the homeowners
packet and connect it to the blower relays
at the coils on the blue wire and red wire
side.
Model
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
Wire Color /
Speed Tap
RedLow760
BlackHigh1000
RedLow760
BlackHigh1000
RedLow760
BlackHigh1000
T1Low750
T2Med/Low1,000
Orange / T3Medium1,140
Red / T4Med/High1,300
T5High1,350
T1Low1,340
Orange / T2Med/Low1,450
Red / T3Medium1,650
T4Med/High1,750
T5High1,965
T1Low1,340
T2Med/Low1,450
Orange / T3Medium1,650
Red / T4Med/High1,750
T5High1,965
Motor
Speed
Air Flow
(0.3 In. WC)P3RD
Figure 7. Standard Motor Lead Connection
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.
CAUTION:
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated metal components
of the unit.
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.
CONDENSATE DRAIN
A 3/4” condensate fi tting extends out of the side
of the unit. The drain trap, shipped in the electrical
compartment, must be installed to prevent water
from collecting inside the unit. Thread the elbow
provided with the unit into the drain connection
until hand tight. Install the trap into the fi tting and
seal the joint. Make sure it is level. Route the
condensate from the trap to a suitable drain. Any
connecting tubing or hose must have the outlet
below the trap level for proper drainage.
WARNING:
Turn off electrical power before servicing controls. Severe electrical shock
may result unless power is turned off.
Unit must be installed in compliance
with the National Electrical Code (NEC)
and local codes.
Elbow
P-Trap
Figure 8. Drain Trap
High Voltage
Low Voltage
Figure 9. Power Entry
7
Page 8
ELECTRICAL CONNECTIONS
1. ELECTRICAL SERVICE
High Voltage
a. Install a branch circuit disconnect of ad-
equate size per NEC. Locate the disconnect
within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
c. Ground the air conditioning unit using the
green grounding screw provided in the
control panel.
Low Voltage
a. Route 24v control wires through the sealing
grommet near the power entrance.
b. Connect the control wires to the leads in
the low voltage area. (See Figure 10).
Y terminals respectively on the thermostat
subbase. Connect the green wire to the
yellow wire at the unit. See the instruction
sheet packed with the thermostat for detailed
methods of mounting.
Note: The cooling-only thermostat must be
connected to an interlock switch to prevent
simultaneous operation of the furnace and
the air conditioner. (See Figure 1, Page
2.)
b. Connect the Heat-Cool Thermostat: The
heat-cool thermostat is equipped with a
system HEAT-COOL switch, which provides
a positive means of preventing simultaneous operation of the heating and cooling
units. The thermostat is also equipped with
an ON-AUTO fan switch which allows the
home owner to operate the indoor blower
when air circulation is desired.
2. OVERCURRENT PROTECTION
In general, the best fuse or breaker for any air
conditioner is the smallest size that will permit
the equipment to run under normal use and
service without nuisance trips. Such a device,
sized properly, gives maximum equipment
protection. The principal reason for specifying
a time delay type is to prevent nuisance trips
when the unit starts.
In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not arbitrarily put in a larger fuse or breaker and do not,
in any case, exceed the maximum size listed on
the data label of the unit.
3. LOCATING THE THERMOSTAT
Locate the thermostat away from drafts and
slamming doors and place it where there is a free
fl ow of air. Mount on an inside wall approximately
fi ve feet from the fl oor.
Connect the red, yellow, green and brown
low voltage wires to the R or RC, Y, G and
W terminals respectively on the thermostat
base. The black wire is the 24 volt common
required on some thermostats. See thermostat instruction sheet for more detailed
information.
Refer to furnace installation instructions
for required connections and proper heat
anticipator setting when installing unit with
an external furnace.
c. If two stage heating is desired, an
optional outdoor thermostat may be
installed: Connect the thermostat to the
orange low voltage wire and the W terminal
on the indoor thermostat base (See Figure
10). See the thermostat instructions for
details on setting the outdoor thermostat.
4. ELECTRIC HEAT PACKAGE (OPTIONAL)
Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air fl ow from supply
registers.
a. Connect Cooling Thermostat: The cooling
thermostat available for use with this system
is equipped with a selector switch. To shut
down the air conditioner, set the selector
switch to the OFF position. Connect the red
and yellow wires from the unit to the R and
8
The air conditioner is shipped without an auxiliary electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be fi eld
installed. See Specifi cations Sheet for available
kits and their applications.
• Select the correct size heat package for the
installation.
Page 9
Control Wire Legend
Green - Blower Relay
Red - Transformer
24V
Yellow - Cooling 1st
Stage
Brown - Heating 1st
Stage
Orange - Heating 2nd
Stage
4 Wire Heat/Cool Thermostat
Single Stage Electric Heat
R
Y
G
W
Two Stage Electric Heat
RED
YELLOW
GREEN
BROWN
ORANGE
2 Wire Cooling Thermostat
R
Y
RED
YELLOW
GREEN
BROWN
R
Y
G
W
Outdoor Thermostat
Optional
(Field Supplied)
Figure 10. Low Voltage Connections
• Follow installation instructions provided
with each heater kit.
• Installation is most easily accomplished
before making duct or electrical connections.
• The blower must be set to high speed for
electric heat operation.
SYSTEM OPERATION
1. PRE-START CHECK LIST
The following check list should be observed
prior to starting the unit.
Is the unit level? It should be level or
slightly slanted toward the drain for proper
condensate drainage.
Is the unit installed with the proper clear-
ances (See Figure 2)?
Is the wir ing correct according to the wiring
diagram and electrical codes?
Are all the wir ing connections tight? Check
the condenser fan to make sure it turns
freely.
Is the overcurrent protection properly
sized?
RED
YELLOW
GREEN
BROWN
ORANGE
Is the thermostat wired correctly? Is it
installed in a proper location?
2. START-UP PROCEDURE
a. Set the system switch to the OFF posi-
tion.
b. Dial thermostat setting as high as it will
go.
c. Turn on power supply at the disconnect
switch.
d. Set the system switch to ON or COOL.
Set the temperature setting to below room
temperature. Verify that the indoor blower,
outdoor fan, and compressor are energized
and the cooling function starts.
e. Verify that the discharge air grilles are
adjusted and the system is balanced.
f. Verify that there are no air leaks in the duct
work.
g. Verify that the condensate drain is properly
installed and that it functions correctly.
h. Dial the thermostat higher than room tem-
perature. The unit should stop.
i. If using a combination heating-cooling ther-
mostat, set to the HEAT position. Proceed
to check for correct furnace operation.
Refrigerant Charging Chart Legend for Cooling Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate
fl ooded conditions
- Rated Design Values. Suction Pressure will be lower than design value if indoor air
fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
- Discharge temperatures greater than charted
values indicate an undercharged system.
Refrigerant Charging Chart Legend for Cooling Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate
fl ooded conditions
- Rated Design Values. Suction Pressure will be lower than design value if indoor air
fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
- Discharge temperatures greater than charted
values indicate an undercharged system.
Refrigerant Charging Chart Legend for Cooling Mode of Operation
* Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate
fl ooded conditions
- Rated Design Values. Suction Pressure will be lower than design value if indoor air
fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
- Discharge temperatures greater than charted
values indicate an undercharged system.
Page 13
4
¢710554#¤
RED
1
2
3
4
5
6
7
8
9
9
WHITEWHITE
MOTOR
BLOWER
C
H
BROWN
CAPACITOR
COM
BROWN
BLACK
N.O. N.C.
8
L
6
7
GREEN
YELLOW
5
BLUE
4
RED
2
3
WHITE
1
BLACK
C
S
BLUE
R
ORANGE
YELLOW
OUTDOOR
FAN MOTOR
L1L2
T1T2
71055
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre
3. Ne convient pas aux installations de plus de 150 V a la terre.
R
XFMR-R
XFMR-C
RED
RED
FUSE
3 AMP
Legend
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 V to ground.
4. For replacement wires use conductors suitable for 105° C.
SPEEDUPG
C
Factory Wiring:
RELAY CONTROL BOARD
WHITE
BLACK
RED
240 COM
TRANSFORMER
COMPRESSOR
BLACK
RED
THERMOSTAT
CONTACTOR
GREEN
THERMOSTAT
YELLOW
THERMOSTAT
H
F
C
RED
S
ONLY)
SWITCH
(SELECT
MODELS
LOW PRESSURE
BROWN
ORANGE
DUAL
C
CAPACITOR
YELLOW
BLACK
R
COMPRESSOR
NOTES:
Field Wiring
Low Voltage
High Voltage
Figure 11. Wiring Diagram
710554
13
Page 14
WHITE
RED
123456789
123456789
Legend
Factory Wiring:
Field Wiring
Low Voltage
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre
3. Ne convient pas aux installations de plus de 150 V a la terre.
RED
¢710589P¤
BLUE
BLACK
TRANSFORMER
WHITE
WHITE
240 COM
RED
L1L2
T1T2
CONTACTOR
COMPRESSOR
BLACK
24V
SWITCH
LOW PRESSURE
(SELECT MODELS ONLY)
YELLOW
H
F
C
S
COMPRESSOR
RED
C
710589A (Replaces 7105890)
DUAL
CAPACITOR
BLACK
YELLOW
R
GREY
WHITE
High Voltage
GREEN/YELLOW
N
L
G
C
MOTOR
BLOWER
ORANGE
RED
NO
NC
LOAD
RELAY
COM
BLACK
C
R
S
MOTOR
OUTDOOR FAN
BLUE
RED
ORANGE
BLACK
14
Packaged Air Conditioner - Single Phase
See Installation Instructions for blower motor airflow settings.
5.
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 V to ground.
4. For replacement wires use conductors suitable for 105° C.
NOTES:
Figure 12. Wiring Diagram
FUSE
3 AMP
GREEN
THERMOSTAT
RED
RED
THERMOSTAT
BROWN
ORANGE
YELLOW
THERMOSTAT
710589A
Page 15
15
Page 16
INSTALLER
PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
708548A (Replaces 7085480)
O'Fallon, MO
¢708548L¤
708548A
Specifi cations and illustrations subject
to change without notice and without
incurring obligations.
Printed in U.S.A. (06/06)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.