46
Advanced Room Controls (continued)
Airflow: The Normal setting allows the system to deliver as much
airflow as possible into a room. If you set a room to Quiet mode, the
system opens more ducts to reduce air pressure and, thus, air noise.
Note: The trade-off for Quiet mode is that the system may take longer
to bring a given room to temperature. In extreme climate conditions
the system may not achieve the desired temperature at all. In addition,
you should set as few rooms as absolutely needed to Quiet mode.
Anticipation: Suppose you set the lower limit to 68°F at 7:00
a.m. By default, Anticipation is enabled, which means that the
system calculates when to start heating in order to ensure the room
reaches 68°F by 7:00 a.m. As the name implies, the Anticipation
parameter allows the system to anticipate your temperature limits. The
system may start at different times each day due to outside temperature
factors and the current inside temperature.
Anticipation Disabled, on the other hand, causes the system to
begin conditioning a room at the start time indicated by your comfort
schedule. Disable anticipation if, for example, conditioning noise wakes
you up too early.
If you have a heat pump or multistage HVAC equipment,
Anticipation overrides the Activate aux. heat if temp.
differential is greater than setting. That is, auxiliary heat turns on
only if the temperature differential is greater than that specified at the
time conditioning would have started if Anticipation were not enabled.
Extra Heat and Extra Cool: These parameters define the
degree to which the system allows extra warm and extra cool air to
enter a room during a conditioning cycle. Remember that because of
airflow requirements, the system conditions multiple rooms during a
conditioning cycle (that is, these rooms are receiving extra conditioning)
even if only one room actually requires conditioning. The choices are:
• Less: Allows less-than-normal warm or cool air into this room,
which means that this room only receives extra air when it is
already very close to its heat or cool limit. (In general, the system
tends to want to allow extra air into rooms that are already near
their upper or lower limits.)
• Normal (default setting): Allows extra warm or cool air into this
room as needed. This is the default setting, and as much as possible
for system efficiency, leave rooms in this setting.
• More: Allows more-than-normal extra warm or cool air into this
room.
• In Range: Allows as much extra warm or cool air into this room
as necessary. This is the most flexible setting, and we recommend
Usage Details