HOMA TP Series User Manual

TP Series
Installation, Operation
Project: _________________________ Installation: ___________________
Pump Model: ____________ Serial Number: ____________
PN# TPIOM REV. 6/12
HOMA Pump Technology, Inc.
390 Birmingham Boulevard  Ansonia, CT 06401
TP Series
GENERAL INSTRUCTIONS:
This manual is intended to provide basic installation and start-up guidance. It is to be read and thoroughly studied prior to attempting to install or operate any of the equipment supplied.
Equipment damage, which occurs by not following these instructions will void the warranty.
SAFETY PRECAUTIONS:
Only trained, qualified personnel shall be utilized for installation and start-up.
The following is a general list of safety precautions that should be followed when installing, starting-up or servicing the pump.
The pump station owner or operator is ultimately responsible for ensuring that all equipment is installed, started up and operated in a safe manner.
Do not work alone.
Double check to make sure that all lifting
equipment is in good working order and that it has adequate lifting capacity for the weight that it will handle.
Wear safety helmet, goggles and protective shoes, or appropriate safety materials required.
Before working on the pump make sure that the power is disconnected and cannot be energized by others. Lockout and tag the control panel circuit breaker.
Do not stand under suspended loads!
Never enter or work within a wet well without
first checking to make sure sufficient oxygen is present and that there are no explosive or poisonous gases present.
All personnel, who work with sewage pumping equipment and systems shall be vaccinated against diseases that can occur. If there are any questions or doubts in this area it is strongly suggested that the local health agency be contacted.
For Hazardous Area Classifications, only use pumps with suitable Explosion Proof Rating.
Installation, Operation & Maintenance Manual
EQUIPMENT INVENTORY AND INSPECTION:
Upon arrival of pump shipment carefully unpack all components and compare with shipping and purchase order documents to ensure that the order is complete. Also inspect equipment for any damage that might have occurred in shipment. If
any problems are detected contact an authorized HOMA Pump Technology Representative immediately.
TRANSPORTATION AND STORAGE PROCEDURE:
Always lift the pump by its lifting bail or eye bolt. Never lift the pump by its power cable! Pumps should be stored in an upright position, taking extreme care to protect the power cable and control cables from crushing, nicks or tears which would permit water intrusion. Power cable ends must be protected from immersion in water as well as moisture intrusion. The cable will wick water into the pump if it is not protected properly. Power cable leads should be covered with shrink tubing or suitable sealing material during storage.
Short Term Storage: Short term storage is defined as any time less than six months. We recommend that pump and accessories be stored in its original shipping container in a dry, temperature controlled area. If climate controlled storage is not possible, all exposed parts should be inspected before storage and all surfaces that have the paint scratched, damaged or worn should be re-coated with air dry enamel paint. The pump should be stored in an upright position.
Long Term Storage: Any storage time exceeding six months is considered long term. In addition to the safeguards specified above, the impeller should be rotated once a month to prevent the mechanical seals from being damaged, and the pump should be inspected. The seal chamber oil should be drained and replaced prior to commissioning. The pump should be stored in an upright position.
Pg. 2
TP Series
ELECTRICAL INSTALLATION:
GENERAL GUIDELINES
All electrical work shall be carried out under the supervision of an authorized, licensed electrician.
The present state adopted edition of the National Electrical Code as well as all local codes and regulations shall be complied with.
VERIFICATION OF POWER SUPPLY
Prior to making any electrical connections or applying power to the pump, compare the power supply available at the pump station to the data on the unit's nameplate. Confirm that both voltage
and phase match between pump and control panel. The voltage supplied at the pump shall be
+5 / -10% of the nameplate value, frequency shall be + / - 1% of the nameplate value, the voltage phase balance shall be within 1% and the maximum corrected power factor shall be 1.0.
POWER LEAD WIRING
HOMA TP Series pumps may be provided with 1 or more cables, depending on motor horsepower and operating voltage. Power leads L1, L2, & L3 may be provided as single conductor, or as twin conductor. Twin conductor configuration may use leads from separate cables, or may use two conductors within one cable. Please refer to wiring diagram enclosed for specific connection details.
The pump must be connected electrically through a motor starter with proper circuit breaker protection in order to validate warranty. Do not splice cables.
THERMAL SWITCH WIRING :
Pumps are equipped with thermal switches embedded in the stator windings which are normally closed, automatically resetting switches. Switches will open when the internal temperature rises above the design temperature, and will close when the temperature returns to normal. Some non explosion proof, single phase TP pumps have internally connected thermals which shut the pump down in the event of over temperature condition and do not require any external connection. Explosion proof pumps and pumps with 7 lead cable have thermal switches which must be wired into the over temperature circuit of the control panel.
Installation, Operation & Maintenance Manual
Note: All sizes of Class 1, Div. 1 pumps for hazardous service will have externally wired thermal switches. Thermal switch leads must be connected to a current regulated control circuit in accordance with NEC.
Thermal switch leads must be connected to validate warranty.
Identify thermal switch leads marked T1 and T3 in the power or control cable. The resistance across these leads will be .5 Ohm. These leads must be connected to the thermal overload relay such as the HOMA Go switch seal fail / thermal relay (option) or other current regulated power supply / controller.
SEAL PROBE WIRING
The mechanical seal leak detector probe utilized in the pump is a conductive probe which is normally open. The intrusion of water into the seal chamber completes the electrical circuit. Control panel provisions will sense this circuit closure, and will provide indication or alarm functions depending on the panel design. Either single or dual wire systems may be provided. Single wire systems utilize one energizing conductor, and the pump casing and neutral lead as the ground or return portion of the circuit. The dual wire systems utilize two separate conductors for each leg of the circuit. With either system, the seal probe leads must be wired into a control circuit provided in the control panel. This control circuit must energize the probe with a regulated power source, and sense the closed circuit in event of water intrusion. Indication and alarm functions must also be provided in the control circuit. Please see control panel wiring diagram (by others) for seal probe connection points. IMPORTANT: For Hazardous Area
Classification Pumps, leak detector circuit must be in conformance with applicable NEC codes and regulations.
START / RUN CAPACITORS AND RELAYS:
All single phase motors require start and/or run capacitors to operate. Refer to the enclosed wiring diagrams. Capacitors and relays must be sized for the specific motor. Capacitors are sized based on ideal conditions. The run capacitor may need to be resized to match the available field voltage. Each cap kit shipped is supplied with a wiring diagram and start up procedure.
Pg. 3
TP Series
MECHANICAL INSTALLATION:
PUMPS WITH AUTOCOUPLING SYSTEMS
The HOMA Auto-Coupling is a quick removal system used in keeping personnel from having to enter the wet well. The pump mounts on a stationary base and operates completely or partially submerged (minimum 8” over volute) in the pumping media.
The HOMA Auto-Coupling kit consists of a base elbow, guide claw flange, and upper guide rail bracket. The kit also includes a profile seal and base anchor bolts.
TP Series pumps with horizontal threaded discharge, attach the guide claw flange to the pump discharge flange as follows:
1. Inspect threaded assemblies for damage.
2. Clean threaded portions of pump discharge flange and guide claw flange and locate set screw location.
3. Install profile seal (if not already installed at factory) into the guide claw with large diameter fitted into groove inside of claw.
4. Apply pipe sealant to the threads of the discharge.
When installing the pump onto a larger auto­coupling an increaser bushing will be included with the pump. Use a thread locking compound such as blue #242. Apply thread locking compound to the discharge threads. Thread the bushing onto the discharge and tighten.
5. Thread guide claw flange on to pump discharge fully. DISCHARGE THREADS ARE NOT NPT. DO NOT OVER TIGHTEN.
6. Tighten guide claw flange until the claw is in upright (horizontal) position.
7. Apply thread locker to the set screw included with the guide claw and tighten set screw.
For flanged discharge pumps, attach the guide claw with the fasteners and gasket provided. Flanges are raised face type, improper tightening will damage the flanges. Tighten the bolts in a crosswise fashion evenly and in steps. Do not tighten one side and then the other or the flanges will break.
Do not over tighten the bolts or the flanges will break.
For all pumps, properly locate the base and, with suitably sized anchor bolts, fasten it to the floor of the pump station. Make sure when locating and securing the anchor bolts that the base will align properly with the access cover at the top elevation of the station. Level the base before completely tightening the anchor bolts. If base is not level, proper sealing of the pump to base may not occur!
Place the guide rail pipes (supplied by others), cut to length into the rings of the base. The rails will be secured at the top of the pump station with the upper guide bar bracket and to extend down to the sump floor.
For stations exceeding 10 feet in depth intermediate guide bar brackets are recommended. One bracket is recommended for each additional 10 feet of station depth.
Install the upper guide bar bracket to maintain vertical orientation of the guide rails. Do not tighten mounting bolts completely at this point. Check that the guide system is properly installed in the vertical orientation by using levels and a plumb line. Then tighten upper guide anchor bolts. Connect the station riser piping to the outlet flange of the base.
INSTALLATION OF PUMPS WITH RING STANDS:
The ring stand design allows for simple, economical installation and can be transported from one installation to another.
For pump models without integral support feet, install the ring stand to the underside of the volute with the supplied fasteners. Apply a thread locking compound to threads before installing, such as blue #242 thread locking compound.
Pg. 4
Installation, Operation & Maintenance Manual
Loading...
+ 9 hidden pages