HOMA GRP Series User Manual

GRP Series
Installation, Operation
Project: _________________________ Installation: ___________________
Pump Model: ____________ Serial Number: ___________
PN# GRPIOM REV. 6/12
HOMA Pump Technology, Inc.
390 Birmingham Boulevard  Ansonia, CT 06401
GRP Series
GENERAL INSTRUCTIONS:
This manual is intended to provide basic installation and start-up guidance. It is to be read and thoroughly studied prior to attempting to install or operate any of the equipment supplied. Equipment
damage, which occurs by not following these instructions will void the warranty.
SAFETY PRECAUTIONS:
Only trained qualified personnel shall be utilized for installation and start-up.
The following is a general list of safety precautions that should be followed when installing, starting-up or servicing the pump. The pump station owner
or operator is ultimately responsible for ensuring that all equipment is installed, started up and operated in a safe manner.
Do not work alone.
Double check to make sure that all lifting
equipment is in good working order and that it has adequate lifting capacity for the weight that it will handle.
Wear safety helmet, goggles and protective shoes, or appropriate safety materials required.
Before working on the pump make sure that power is disconnected and cannot be energized by others. Lockout and tag the control panel circuit breaker.
Do not stand under suspended loads!
Never enter or work within a wet well without
first checking to make sure sufficient oxygen is present and that there are no explosive or poisonous gases present.
All personnel, who work with sewage pumping equipment and systems shall be vaccinated against diseases that can occur, If there are any questions or doubts in this area it is strongly suggested that the local health agency be contacted.
For Hazardous Area Classifications, only use pumps with suitable Explosion Proof Rating.
EQUIPMENT INVENTORY AND INSPECTION:
Upon arrival of pump shipment carefully unpack all components and compare with shipping and purchase order documents to ensure that the order is complete. Also inspect equipment for any damage that might have occurred in shipment. If
any problems are detected contact an authorized HOMA Pump Technology Representative immediately.
TRANSPORTATION AND STORAGE PROCEDURE:
Always lift the pump by its lifting bail or eye. Never lift the pump by its power cable! Pumps should be stored in an upright position, taking extreme care to protect the power cable and control cables from crushing, nicks, or tears which would permit water intrusion. Power cable ends must be protected from immersion in water as well as moisture intrusion. The cable will wick water into the pump if it is not protected properly. Power cable leads should be covered with shrink tubing or suitable sealing material.
Short Term Storage: Short term storage is defined as any time less than six months. We recommend that pump and accessories be stored in their original shipping container in a dry, temperature controlled area. If climate controlled storage is not possible, all exposed parts should be inspected before storage and all surfaces that have the paint scratched, damaged or worn should be re-coated with suitable paint. When possible it is best to store the pump in an upright position.
Long Term Storage: Any storage time exceeding six months is considered long term. In addition to the safeguards specified above, the impeller should be rotated once a month to prevent the mechanical seals and bearings from being damaged, and the pump should be inspected. The oil in the mechanical seal chamber should be drained and replaced prior to commissioning.
Pg.2
Installation, Operation & Maintenance Manual
GRP Series
ELECTRICAL INSTALLATION:
GENERAL GUIDELINES
All electrical work shall be carried out under the supervision of an authorized, licensed electrician.
The present state adopted edition of the National Electrical Code as well as all local codes and regulations shall be complied with.
VERIFICATION OF POWER SUPPLY
Prior to making any electrical connections or applying power to the pump, compare the power supply available at the pump station to the data on the unit's nameplate. Confirm that both voltage and phase match between pump and control panel. The voltage supplied at the pump shall be +5 / -10% of the nameplate value, frequency shall be + / - 1% of the nameplate value, the voltage phase balance shall be within 1% and the maximum corrected power factor shall be 1.0.
POWER LEAD WIRING
HOMA GRP Series pumps may be provided with 1 or more cables, depending on motor horsepower and operating voltage. Power leads L1, L2, & L3 may be provided as single conductor, or as twin conductor. Twin conductor configuration may use leads from two separate cables, or may use two conductors within one cable. Please refer to enclosed wiring diagram for specific connection details. The pump must be connected electrically
through a motor starter with proper circuit breaker protection in order to validate warranty. Do not splice cables.
THERMAL SWITCH WIRING :
Pumps are equipped with thermal switches which are normally closed, automatically resetting switches. Switches will open when the internal temperature rises above the design temperature, and will close when the temperature returns to normal. Non Explosion proof GRP 10/1 to 21/1 single phase pumps have internally connected thermals which shut pump down in the event of over temperature condition, and do not require any external connection. Explosion proof pumps and pumps with 7 lead cable have thermal switches which must be wired into the over temperature circuit of the control panel.
Note: All sizes of Class 1, Div. 1 pumps for hazardous service will have externally wired thermal switches. Thermal switch leads must
be connected to a current regulated control circuit in accordance with the NEC.
Thermal switch leads must be connected to validate warranty.
Identify thermal switch leads marked T1 and T3 in the power or control cable. The resistance across these leads will be .5 Ohm. These leads must be connected to the thermal overload relay such as the HOMA Go switch seal fail / thermal relay (option) or other current regulated power supply / controller.
SEAL PROBE WIRING
The mechanical seal leak detector probe utilized in the pump is a conductive probe which is normally open. The intrusion of water into the seal chamber completes the electrical circuit. Control panel provisions will sense this circuit closure, and will provide indication or alarm functions depending on the panel design. Either single or dual wire systems may be provided. Single wire systems utilize one energizing conductor, and the pump casing and neutral lead as the ground or return portion of the circuit. The dual wire systems utilize two separate conductors for each leg of the circuit. With either system, the seal probe leads must be wired into a control circuit provided in the control panel. This control circuit must energize the probe with a regulated power source, and sense the closed circuit in event of water intrusion. Indication and alarm functions must also be provided in the control circuit. Please see control panel wiring diagram (by others) for seal probe connection points. IMPORTANT: For Hazardous Area
Classification Pumps, leak detector circuit must be in conformance with applicable NEC codes and regulations.
START / RUN CAPACITORS AND RELAYS:
All single phase motors require start and/or run capacitors to operate. Refer to the enclosed wiring schematic. Capacitors and relays must be sized for
the specific motor.
Capacitors are sized based on reference voltage. The Run capacitor may need to be resized to match the available field voltage. Each cap kit shipped is supplied with a wiring diagram and start­up procedure.
Pg.3
Installation, Operation & Maintenance Manual
GRP Series
MECHANICAL INSTALLATION:
PUMPS WITH AUTOCOUPLING SYSTEMS
The HOMA Auto-Coupling is a quick removal system used to prevent personnel from needing to enter the wet well.
The HOMA Auto-Coupling kit includes a base elbow, guide claw flange and upper guide rail bracket. The kit also includes a profile seal and base anchor bolts. Refer to “Auto-Coupling Parts ID” technical page on website.
For GRP 10 - 50 Series
threaded discharge, attach the guide claw flange to the pump discharge flange as follows:
1. Inspect threaded assemblies for damage.
2. Clean threaded portions of pump discharge
flange and guide claw flange and locate set screw location.
3. Install profile seal (if not already installed at
factory) into the guide claw with large diameter fitted into groove inside of claw.
4. Apply pipe sealant to the threads of the
discharge.
5. Thread guide claw flange onto pump discharge
fully. DISCHARGE THREADS ARE NOT NPT.
DO NOT OVER TIGHTEN.
6. Tighten guide claw flange until the claw is in
upright (horizontal) position.
7. Apply thread locker to the set screw included
with the guide claw and tighten set screw.
For GRP 12 and 19 Series
1¼” threaded discharge (note: this assembly can be ordered with or without integral check valve), attach the pump discharge flange as follows:
1. Inspect threaded assemblies for damage.
2. Clean threaded portions of pump discharge
flange, nipple and riser pipe.
3. Apply pipe sealant to the male threads.
4. Thread guide claw riser pipe (either style) onto
the pump discharge with the provided 11/4” close nipple. Tighten the assembly until the opening in riser pipe points away from pump and is parallel with the cable entry.
pumps with horizontal 2”
pumps with vertical,
Installation, Operation & Maintenance Manual
5. Bolt the guide claw flange with rubber gasket to the riser pipe using the SS nuts and bolts provided.
6. Install profile seal (if not already installed at factory) into the guide claw with large diameter fitted into groove inside of claw.
7. For check valve version install second gasket, drop in check ball, and fasten the cover with nuts and bolts provided.
Important: Do not install more then one (1)
check valve into any pump discharge piping system or problems will occur.
For GRP 59 to 118 Series pumps
guide claw flange to the pump discharge flange with the fasteners and gasket included with the auto-coupling kit. Tighten the bolts to the proper torque. Install profile seal (if not already installed at factory) into the guide claw with large diameter fitted into groove inside of claw.
For all pumps, properly locate the base and, with suitably sized anchor bolts, fasten it to the floor of the pump station. Make sure when locating and securing the anchor bolts that the base will align properly with the access cover at the top elevation of the station. Level the base before completely tightening the anchor bolts. If base is not level, proper sealing of the pump to base may not occur!
Place the guide rail pipes (supplied by others), cut to length into the rings of the base. The rails will be secured at the top of the pump station with the upper guide bar bracket and will extend down to the sump floor.
For stations exceeding 10 feet in depth, inter­mediate guide bar brackets are recommended. One bracket is recommended for each additional 10 feet of station depth.
Install the upper guide bar bracket to maintain vertical orientation of the guide rails. Do not tighten mounting bolts completely at this point. Check that the guide system is properly installed in the vertical orientation by using levels and a plumb line. Then tighten upper guide anchor bolts. Connect the station riser piping to the outlet flange of the base.
Pg.4
, attach the
Loading...
+ 9 hidden pages