HOMA A Series User Manual

Page 1
A Series
Installation, Operation
Project: _______________________ Installation: ____________________
Pump Model: ______________ Serial Number: ___________
AIOM REV. 6/12
HOMA Pump Technology, Inc.
390 Birmingham Boulevard  Ansonia, CT 06401
Page 2
A Series
GENERAL INSTRUCTIONS:
This manual is intended to provide basic installation and start-up guidance. It is to be read and thoroughly studied prior to attempting to install or operate any of the equipment supplied.
Equipment damage, which occurs by not following these instructions will void the warranty.
SAFETY PRECAUTIONS:
Only trained qualified personnel shall be utilized for installation and start-up.
The following is a general list of safety precautions that should be followed when installing, starting-up or servicing the pump.
The pump station owner or operator is ultimately responsible for ensuring that all equipment is installed, started up and operated in a safe manner.
Do not work alone.
Double check to make sure that all lifting
equipment is in good working order and that it has adequate lifting capacity for the weight that it will handle.
Wear safety helmet, goggles and protective shoes, or appropriate safety materials required.
Before working on the pump make sure that the power is disconnected and cannot be energized by others. Lockout and tag the control panel circuit breaker.
Do not stand under suspended loads!
Never enter or work within a wet well without
first checking to make sure sufficient oxygen is present and that there are no explosive or poisonous gases present.
All personnel, who work with sewage pumping equipment and systems shall be vaccinated against diseases that can occur. If there are any questions or doubts in this area it is strongly suggested that the local health agency be contacted.
For Hazardous Area Classifications, only use pumps with suitable Explosion Proof Rating.
Installation, Operation & Maintenance Manual
EQUIPMENT INVENTORY AND INSPECTION:
Upon arrival of pump shipment carefully unpack all components and compare with shipping and purchase order documents to ensure that the order is complete. Also inspect equipment for any damage that might have occurred in shipment. If any problems are detected contact
an authorized HOMA Pump Technology Representative immediately.
TRANSPORTATION AND STORAGE PROCEDURE:
Always lift the pump by its lifting bail or eye bolt.
Never lift the pump by its power cable! Damage to Sealing ring or cable may result.
Pumps should be stored in an upright position, taking extreme care to protect the power cable and control cables from crushing, nicks or tears which would permit water intrusion. Power cable ends must be protected from immersion in water as well as moisture intrusion. The cable will wick water into the pump if it is not protected properly. Power cable leads should be covered with shrink tubing or suitable sealing material during storage.
Short Term Storage: Short term storage is defined as any time less than six months. We recommend that pump and accessories be stored in its original shipping container in a dry, temperature controlled area. If climate controlled storage is not possible, all exposed parts should be inspected before storage and all surfaces that have the paint scratched, damaged or worn should be re-coated with air dry enamel paint. The pump should be stored in an upright position.
Long Term Storage: Any storage time exceeding six months is considered long term. In addition to the safeguards specified above, the impeller should be rotated once a month to prevent the mechanical seals and bearings from being damaged, and the pump should be inspected. The seal chamber oil should be drained and replaced prior to commissioning. The pump should be stored in an upright position.
Pg. 2
Page 3
A Series
ELECTRICAL INSTALLATION:
GENERAL GUIDELINES
All electrical work shall be carried out under the supervision of an authorized, licensed electrician.
The present state adopted edition of the National Electrical Code as well as all local codes and regulations shall be complied with.
VERIFICATION OF POWER SUPPLY
Prior to making any electrical connections or applying power to the pump, compare the power supply available at the pump station to the data on the unit's nameplate. Confirm that both
voltage and phase match between pump and control panel. The voltage supplied at the pump
shall be +5 / -10% of the nameplate value, frequency shall be + / - 1% of the nameplate value, the voltage phase balance shall be within 1% and the maximum corrected power factor shall be 1.0.
POWER LEAD WIRING
HOMA A Series pumps may be provided with 1 or more cables, depending on motor horsepower and operating voltage. Power leads L1, L2, & L3 may be provided as single conductor, or as multiple conductors. Multiple conductor configurations may use leads from separate cables, or may use two conductors within one cable. Please refer to enclosed wiring diagram for specific connection details. The pump must
be connected electrically through a motor starter with proper circuit breaker protection in order to validate warranty. Do not splice cables.
THERMAL SWITCH WIRING :
Pumps are equipped with thermal switches embedded in the stator windings which are normally closed, automatically resetting switches. Switches will open when the internal temperature rises above the design temperature, and will close when the temperature returns to normal. Thermal switches must be wired to a current regulated control circuit in accordance with the NEC. Identify thermal switch leads marked T1 and T3 in the power or control cable. The resistance across the leads will be .5 Ohms. Thermal leads must be connected to the thermal overload relay located in the control panel.
Thermal switch leads must be connected to validate warranty.
Note: All sizes of Class 1, Div. 1 pumps for hazardous service must have thermal switch leads connected to a current regulated control circuit in accordance with NEC.
SEAL PROBE WIRING
The mechanical seal leak detector probe utilized in the pump is a conductive probe which is normally open. The intrusion of water into the seal chamber completes the electrical circuit. Control panel provisions will sense this circuit closure, and will provide indication or alarm functions depending on the panel design. Either single or dual wire systems may be provided. Single wire systems utilize one energizing conductor, and the pump casing and neutral lead as the ground or return portion of the circuit. The dual wire systems utilize two separate conductors for each leg of the circuit. With either system, the seal probe leads must be wired into a control circuit provided in the control panel. This control circuit must energize the probe with a regulated power source, and sense the closed circuit in event of water intrusion. Indication and alarm functions must also be provided in the control circuit. Please see control panel wiring diagram for seal probe connection points. IMPORTANT: For Hazardous Area
Classification Pumps, leak detector circuit must be in conformance with applicable NEC codes and regulations.
START / RUN CAPACITORS AND RELAYS:
All single phase motors require start and run capacitors along with a start relay to operate. Refer to the enclosed wiring diagram. Capacitors and relays must be sized for the specific motor. Capacitors are sized based on reference voltage. The run capacitor may need to be resized to match the available field voltage. Each cap kit shipped is supplied with a wiring diagram and start up procedure.
Pg. 3
Installation, Operation & Maintenance Manual
Page 4
A Series
Variable Frequency Drives: Special considerations must be taken when operating pumps with variable frequency drives (inverters). The inverter circuit design,
horsepower required by pump, motor cooling system, power cable length, operating voltage, and anticipated turndown ratio must be fully evaluated during the design stage of the installation.
As a minimum, properly sized load reactors and filters must be installed between the inverter and the pump to protect the pump motor from damaging voltage spikes.
Warranty coverage will not be provided on any pump motor that is operated with a variable frequency drive, unless the load side of the inverter is properly isolated from the pump.
ADDITIONAL PUMP PROTECTIVE DEVICES
Several optional pump protection devices are available to protect submersible motors from damage, and may be provided in your pump.
Temperature Sensing RTD*: PT100 sensors are available in two critical locations on larger machines, the lower bearings and motor windings. N.C. Circuit - 108 ohm
Moisture Sensors:
seal chamber probe, additional sensors may be installed in the stator winding, motor cap, or junction box. These sensors may be either one of the following:
Moisture Detectors*: These are micro float switches designed to detect small amounts of liquid. These are available in the stator housing of 50hp and larger size pumps. N.C. Circuit - 268 ohm
Leakage Detectors*: These normally open, single or 2 wire probes are used to detect the presence of water in the pump. Single wire
probes use the pump ground to complete circuit.
* HOMA Go Switch or approved equivalent relay is required for sensor operation.
In addition to the standard
Installation, Operation & Maintenance Manual
MECHANICAL INSTALLATION:
PUMPS WITH AUTOCOUPLING SYSTEMS
The HOMA Auto-Coupling is a quick removal system used to prevent personnel from needing to enter the wet well.
The HOMA Auto-Coupling kit consists of a base, guide claw flange, upper guide rail bracket, profile seal and base anchor bolts. Refer to “Auto-Coupling Parts ID” technical page on website.
For all A Series pumps, attach the guide claw flange to the pump discharge flange with the fasteners and gaskets included with the auto­coupling kit. Use tightening torques indicated in the table on pg. 6. Do not over tighten! Install the profile gasket (if not already installed at the factory) into the guide claw with the large diameter fitted into the groove inside the claw. Refer to the attached instructional sheet for proper profile gasket installation.
Install suitable lifting chain of an adequate size and length to permit proper lowering and raising of the pump.
Properly locate the base, and with suitably sized anchor bolts, fasten it to the floor of the pump station. Make sure when locating and securing the anchor bolts that the base will align properly with the access cover at the top elevation of the station. Place the base in position, and level the base.
If the base is not level, proper sealing of the pump to base may not occur!
Pg. 4
Page 5
A Series
Place the guide rails (supplied by others), cut to length into the rings of the base. The rails will be secured at the top of the pump station with the upper guide bar bracket and extend down to the sump floor. Install the upper guide bar bracket to maintain vertical orientation of the guide rails.
For stations exceeding 10 feet in depth intermediate guide bar brackets are recommended. One bracket is recommended for each additional 10 feet of station depth.
Check that the guide system is properly installed in the vertical orientation by using levels and a plumb line. Fully tighten all anchors and mounting bolts. Connect the station riser piping to the outlet flange of the base.
Before lowering the pump, verify the direction of impeller rotation (refer to technical details section for procedure).
Make sure to use lifting equipment that has adequate capacity for the pump that will be handled. Before installing pump, check to be
certain the profile seal (rubber ring) is properly positioned in the guide claw flange. Then position pump so the guides on the discharge flange engage the rails. Slowly lower the pump along the guide rail. Once the pump reaches its bottom location it will automatically connect to the base.
It is recommended that the stationary base elbow be visible before lowering the unit. If this is not possible, ensure all debris is removed from wet well.
Important: Do not install more than one (1) check valve into any piping system or problems will occur.
Minimum Submergence
For optimal cooling, motor should be completely submerged at all times. In pump-down systems, level should not fall below one discharge diameter above the top of the volute. For continuous operation with a VFD, level should not be maintained below the top of the motor for sustained periods. For specific inquiries, please contact factory for assistance.
Installation, Operation & Maintenance Manual
INSTALLATION OF PUMPS WITH RING STANDS:
The ring stand design allows for a free standing, simple economical installation or to be transportable from one installation to another. It is intended to operate completely or partially submerged in the pumping liquid. Install the ring stand to the underside of the volute with the supplied fasteners provided. Apply thread locking compound such as blue #242 and tighten the bolts using the torque table indicated in the table. Do not over tighten! Install suitable lifting device of an adequate length to ensure proper lowering and raising capabilities. Lower the pump into the area where it is required. Properly position power cable and chain so they stay above pump and cannot enter the pump suction.
INSTALLATION OF PUMPS FOR DRY PIT APPLICATIONS:
Foundation and Piping Requirements:
General The following recommendations are basic guidelines which are intended to outline basic requirements in the design of the dry pit station. It is essential that a licensed professional engineer be retained by the owner to design the station and all support structures.
Foundations Foundations may consist of any structure heavy enough to provide permanent rigid support for the pump and inlet elbow stand. HI standards demand at least 5 times the weight of the pump. Concrete foundations built up from the solid ground are the most commonly used. The concrete floor shall be level. The space required by the inlet stand and the location of the foundation anchor bolts are shown on the outline dimension drawing. Foundation bolts are to be embedded in the concrete.
Pg. 5
Page 6
A Series
Suction Piping
Suction piping should be at least as large as the pump inlet elbow suction. If reducers are utilized they should be of the eccentric, conical type and must be installed with the level side up. Suction piping should be run as straight as possible with a recommended 10 suction diameter distance before pump inlet. Rough sections in pipe suction line can cause turbulence and result in severe vibration of the pump. Pipe reducers should not be installed adjacent to pump inlet All pipe flange joints should be gasketed to prevent air from entering the pipe. High points that may collect vapor are to be avoided. Isolation valves such as gate valves can be installed in order to facilitate the removal of the pump for maintenance. Any valve installed in the suction line should be installed with the stems horizontal. The location of the suction piping termination point inside of the wet pit must be installed such that sufficient submergence is obtained to prevent vortexing. Invert location and multiple suction points can cause hydraulic instability to an operating pump. Avoid high velocity or turbulence at suction pipe inlet.
Discharge Piping
A check valve and isolation valve shall be installed in the discharge line. The check valve should be installed between the pump discharge flange and the isolation valve. If pipe increasers are used on the discharge line, they should be placed between the check valve and the pump. The inlet elbow stand allows the pump to be installed in a stationary position in a dry pit. Place the inlet stand in position and tighten the anchor nuts.
Lower the pump onto the top flange of the
inlet stand. DO NOT ALLOW SLACK ON THE
LIFTING CABLE UNTIL THE PUMP IS BOLTED DOWN. Make sure the flange bolt
holes align with the mounting holes on the underside of the volute. Secure the pump to the mounting flange with the fasteners that are specified in the accessory fastener selection table below.
Installation, Operation & Maintenance Manual
Bolts
PUMP MODEL Anchors
3” A SERIES
AUTOCOUPLING
4” A-SERIES
AUTOCOUPLING
3” & 4” A-SERIES
RING STAND
3” & 4” A- SERIES
DRY SUMP
6” A-SERIES
AUTOCOUPLING
6" A-SERIES
RING STAND
6" A-SERIES
DRY SUMP (1 Piece)
6" A-SERIES
DRY SUMP
(N/PMotor)
6" A-SERIES
DRY SUMP (F Motor)
8” A-SERIES
AUTOCOUPLING
8" A-SERIES
RING STAND
8" A-SERIES
DRY SUMP (2 Piece)
Notes:
1. For pumps larger than 8” please consult factory.
2. Flange bolts must be tightened in cross pattern to avoid damage to the raise face flanges.
3. Standard Flange Bolts are 316SS
4. Standard Anchors are Plated Steel
5. Autocoupling systems include qty 4 M12 anchors for the upper bracket. Torque to 38 ft#.
6. Anchor bolt holes should be drilled to the actual diameter of the anchor (M12 anchor requires 12mm diameter hole).
8 M16X60mm 108 ft/ # 4 M16 74 ft/ #
8 M16X60mm 108 ft/ # 4 M16 74 ft/ #
4 M16x25mm 108 ft/#
8 M16x40mm 108 ft/# 4 M16 74 ft/#
8 M20x70mm 150 ft/# 4 M16 74 ft/#
4 M20x40mm 150 ft/#
8 M20x45mm 150 ft/# 4 M16 74 ft/#
8 M20x65mm 150 ft/# 4 M16 74 ft/#
8 M20x70mm 150 ft/# 4 M16 74 ft/#
8 M20x70mm 150 ft/# 4 M20 150 ft/#
4 M20x30mm 150 ft/#
8 M20x75mm 150 ft/# 4 M20 150 ft/#
SIZE TORQUE
Pg. 6
Page 7
A Series
Installation / Startup Troubleshooting:
Only authorized service personnel who are trained professionals shall troubleshoot and repair pumps that are experiencing operational or performance difficulties.
All HOMA pumps are factory tested, yet startup difficulties can occur with any mechanical equipment. Please note that our technical support staff stands ready to assist you with any problem or difficulty you might encounter with our equipment.
The following is a tabulation of common start-up problems and possible causes.
Symptom
Possible Causes
Pump will not start
1, 2, 3, 4, 27, 28, 29, 31, 32
Little or zero discharge
5, 6, 7, 8, 16, 30, 32
Insufficient discharge flow/pressure 5, 6, 9, 10, 11, 12, 26, 30
Excessive power consumption
6, 9, 13, 28, 30
Excessive current draw
6, 13, 14, 15, 19, 26, 30
Excessive pump vibration/noise
12, 15, 16, 25, 26, 28, 31
Pump runs & motor protection trips 17, 18, 19, 20, 21, 28
Pump runs manually, but not automatically 22, 23, 24
Pump runs hot 7, 19, 25, 26, 28
Installation, Operation & Maintenance Manual
Listing of Possible Causes:
1. Incorrect or no power supplied to motor.
2. Power cable cut.
3. Short to ground in cable or motor winding.
4. Control panel circuit breaker open.
5. Actual system head is higher than calculated or specified.
6. Incorrect impeller rotation direction.
7. Sump liquid level is below pump's minimum submergence requirement.
8. Closed discharge valve or jammed check valve.
9. Wear ring worn. (If Applicable).
10. Vortex at pump's suction.
11. Discharge valve partially closed.
12. Insufficient NPSHA (Dry Pit Application).
13. Actual system head is lower than specified resulting in over pumping condition.
14. Voltage supply to motor is lower than required by motor.
15. Damaged bearings.
16. High system head causing pump to operate at extremely reduced capacity.
17. Object stuck inside impeller.
18. Motor not receiving proper voltage on all three phases.
19. Phase/currents unbalanced or too high.
20. Insulation between phases and earth ground, <1M-ohm.
21. Density of the pumping media too high.
22. Defective level sensor.
23. Hand/Off/Auto switch not in Auto Position.
24. Defective H/O/A switch, relay or contactor coil.
25. Air Captured in Cooling Jacket.
26. Pump not properly seated on Auto Coupling.
27. Water intrusion through junction box.
28. VFD or Soft Start not functioning properly.
29. Run capacitor size too large (1ph).
30. Start capacitor size too small (1ph).
31. Profile seal not sealing or missing.
32. Start relay or capacitor damaged (1ph).
Please note that some possible causes may not relate to your particular model.
If you need additional help, please contact your local distributor or e-mail service@ homapump.com
Pg. 7
Page 8
A Series
MAINTENANCE
Regular maintenance will help ensure longer pump life and more reliable operation. It is recommended that pumps in intermittent operation be inspected twice a year and pumps in continuous operation be inspected every 1,000 hours. The following is a listing of required inspection and maintenance items.
If any of the problems described in the following list exists stop operating the pump to avoid damage or personal injury.
1. CABLE ENTRY
Make sure that the cable entry flange and strain relief clamp are tight. If the cable entry is showing signs of leakage remove cable from entry, remove grommet, cut a piece of cable off so that the grommet seats on a new portion of the cable, replace grommet, and reinstall cable assembly, into the top of the motor.
Note: Explosion Proof cables are sealed with a Factory Mutual Approved potting compound. Please consult factory for instruction.
2. CABLES
Inspect the cable for cuts, scrapes or sharp bends. If the outer jacket is damaged, replace the cable. Splices of the power or control cable within the wet well area are not acceptable.
3. MOTOR INSULATION RESISTANCE
Megger the insulation between the phases; and between any phase and ground. Resistance values should be greater than 1 M ohm. If abnormal readings are obtained, contact authorized service center immediately.
4. EXTERNAL PARTS ON PUMP
Make sure that all screws, bolts and nuts are tight. Check the condition of pump lifting eyes and replace if damaged or worn, Replace any external part that appears worn or damaged.
Installation, Operation & Maintenance Manual
5. SEAL CHAMBER OIL
Note: Use extreme care when removing the seal chamber plug, as the chamber may become pressurized if seal failure has occurred. Seal
chamber oil should be checked for signs of water intrusion, or other impurities any time the pump is removed from wet well. To check the condition of the oil, remove the oil fill plug. Drain the chamber volume into a transparent container. Visually check sample for impurities or emulsification (oil may appear cream-like if a small amount of water is present). If significant water intrusion has occurred, remove and replace lower mechanical seal. Unless obvious mechanical damage has occurred to the lower seal, it is good practice to replace the upper and lower mechanical seals as a set. Refill seal chamber with fresh oil to the bottom of fill plug port (when pump is in vertical position) and replace oil fill plug.
6. IMPELLER
Periodically inspect impeller by turning pump on its side, remove suction strainer nuts and strainer to expose impeller and relocate position of adjusting plate (suction cover) as needed. Replace the impeller if it is damaged or worn.
SPARE PARTS
In order to obtain spare parts identify the required parts by looking at the enclosed cross sectional drawing and listing, and contact authorized HOMA PUMP TECHNOLOGY representative with your order. Authentic Homa Pump Technology parts shall be used to maintain warranty.
Note: Explosion Proof pumps must be identified as such, and the pump serial number must be referenced for proper parts identification.
RECOMMENDED TOOLS AND SUPPLIES
In addition to ordinary maintenance and lifting devices, ensure that complete set of metric Allen wrenches, impeller puller, Loctite 242 (Blue), and Anti-seize compound are on hand.
Pg. 8
Page 9
A Series
Wire Markings of Power & Control Cables
Wire Marker Wire Connection Normal Value Power Cable (s)
L3 Power Supply See Enclosed Wiring Diagram L2 Power Supply See Enclosed Wiring Diagram L1 Power Supply See Enclosed Wiring Diagram Yellow/Green - Ground
Control Cable (s)
T1 Thermal Switch N.C. .4 ohm T2 or T3 Thermal Switch N.C. .4 ohm K1 Thermistor (optional) N.C. 268 ohm K2 Thermistor (optional) N.C. 268 ohm P1 Lower Bearing Temp. PT100 N.C. 108 ohm P2 Lower Bearing Temp. PT100 N.C. 108 ohm P3 Lower Bearing Temp. PT100 N.C. 108 ohm P4 Lower Bearing Temp. PT100 N.C. 108 ohm S1* Oil Chamber Seal Probe 1 or 2 wire probe N.O. S2 Oil Chamber Seal Probe 2 wire probe N.O. S3 Connection Chamber Seal Probe 2 wire probe N.O. S4 Connection Chamber Seal Probe 2 wire probe N.O. S5* Stator Housing Leak Detector 1 wire probe N.O. S7 Stator Housing Leak Detector Level Switch N.C. .7 ohm S8 Stator Housing Leak Detector Level Switch N.C. .7 ohm Yellow/Green –Ground - *Must be used to complete 1 wire probe circuits!
Note: Pump may have single or multiple power or control cables. Verify all wire connections are correct before applying power to any circuit. Improper power supply can permanently damage certain control devices.
All control or monitoring devices must be connected to a suitable power supply and sensing device. Homa can provide an optional Go Switch for any of these control or monitoring devices. Consult your local Homa distributor
Pg. 9
Installation, Operation & Maintenance Manual
Page 10
A Series
PROFILE SEAL INSTALLATION
When installing a profile seal, one side of the seal has a larger diameter ridge on the
outside edge. This side goes to the inside of the guide claw as seen below.
Press the seal into its seat starting on one side and work the rest of the seal into the
same position. When finished, it should look as below.
When properly installed, the profile seal will stay in place when pulled straight outwards.
It is recommended that 3M Weather Stripping be applied to the surface touching the
claw if possible for added adhesion.
REMEMBER:
Pg. 10
the larger diameter always goes to the inside.
Installation, Operation & Maintenance Manual
Page 11
A Series
Single Phase Pump Start-Up Procedure
Run Capacitor sizing can vary depending on the incoming supply voltage provided. HOMA Single Phase pumps are provided with Start and Run Capacitor(s) sized for 220-230V under load. Frequently, the available line voltage is considerably different than indicated, and the Run capacitor(s) may need to be resized to match the available field voltage. The following procedure will allow you to verify proper operation of your single phase pump, and/or make necessary changes to your capacitors to correct for your power supply.
After verifying wiring is in accordance with your pump requirements, start pump and record the following readings from each of the (3) pump cable leads.
Current under load: U1 _________
Should be (highest reading) (middle reading) (lowest reading) Lead U1 (common) should have the highest current reading. Lead Z2 (start) should have the lowest
reading. If Z2 current draw is greater than the current draw of either U1 or U2, a smaller size Run capacitor (lower
microfarad rating) is required to correct the condition. Example: If a 60 µf Run capacitor was supplied, change to a 50 µf Run capacitor and check current readings. Typically, only one step down in capacitor size is required, but in certain instances 2 steps may be required.
Amps
,> U2 __________
Amps
,> Z2 __________
Amps
( ) The standard capacitor kit provided includes: ____________µf start capacitor ____________µf run capacitor. ( ) Additional run capacitors have been included for use in tuning the pump to match available line
voltages for optimum performance. ___________µf run capacitor
___________µf run capacitor ___________µf run capacitor
This form is provided for your use in optimizing the performance and service life of your single phase pumps, and is applicable to most Capacitor Start/Capacitor Run motors. Please contact our Technical Service Department @ (203)-736-8890 with any questions or if you require any additional information or assistance.
Installation, Operation & Maintenance Manual
Pg. 11
Page 12
A Series
N Motor Capacitor Sizing Chart
Pump Model Start Capacitor Run Capacitor Cap Kits AMX334-434/1-142/2.9N 80µf @ 330V 40µf @ 370V 8857010 AMX334-434/1-155/4N 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-178/4N 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-184/5N 150µf @ 330V 80µf @ 370V 8857040 AMX334-434/1-193/5N 150µf @ 330V 80µf @ 370V 8857040 AMX334-434/1-193/7N 150µf @ 330V 100µf @ 370V† 8857045 AMX334-434/1-206/7N 150µf @ 330V 100µf @ 370V† 8857045
AMX334-434/1-206/10N 250µf @ 330V** 120µf @ 370V* 8857055
AMX334-434/1-218/10N 250µf @ 330V** 120µf @ 370V* 8857055
AMX334-434/1-228/10N 250µf @ 330V** 120µf @ 370V* 8857055
(2) 50µf run capacitors in parallel are required.
*Consult factory for A Frame motors with centrifugal switch.
* (2) 60µf run capacitors in parallel are required.
** (1) 150µf & 100µf start capacitor in parallel required.
External Seal Probe Wiring
Seal Probes must be connected to a Homa Go Switch or suitable controller to operate.
Pg.12
Installation, Operation & Maintenance Manual
Page 13
A Series
C, D & T Motor Capacitor Sizing Chart
Pump Model Start Capacitor Run Capacitor Cap Kits AMX334-434/1-1422/C/C 80µf @ 330V 40µf @ 370V 8807010 AMX334-434/1-142/2.5D 80µf @ 330V 50µf @ 370V 8857060 AMX334-434/1-142/2.9T/C 60µf @ 330V 40µf @ 370V 8857065 AMX334-434/1-155/3.6D 80µf @ 330V 50µf @ 370V 8857060 AMX334-434/1-155/4.3T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-155/5.1T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-178/3.6D 80µf @ 330V 50µf @ 370V 8857060 AMX334-434/1-178/4.3T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-178/5.1T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-184/5.1T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-193/5.1T/C 100µf @ 330V 50µf @ 370V 8857035 AMX334-434/1-193/6.7T/C 120µf @ 330V 60µf @ 370V 8857070 AMX334-434/1-206/6.7T/C 120µf @ 330V 60µf @ 370V 8857070
AMX334-434/1-206/9.7T/C 150µf @ 330V 80µf @ 370V 8857075
AMX334-434/1-218/9.7T/C 150µf @ 330V 80µf @ 370V 8857075 AMX334-434/1-228/9.7T/C 150µf @ 330V 80µf @ 370V 8857075 AMX334-434/1-228/11.4T/C 250µf @ 330V** 120µf @ 370V* 8857080 AMX334-434/1-235/11.4T/C 250µf @ 330V** 120µf @ 370V* 8857080 AMX334-434/1-250/11.4T/C 250µf @ 330V** 120µf @ 370V* 8857080
*Consult factory for A Frame motors with centrifugal switch.
* (2) 60µf run capacitors in parallel are required.
** (1) 150µf & 100µf start capacitor in parallel required.
External Seal Probe Wiring
Seal Probes must be connected to a Homa Go Switch or suitable controller to operate.
Installation, Operation & Maintenance Manual
Pg.13
Page 14
A Series
START-UP REPORT
To validate warranty, please answer the following questions during start-up as completely and as accurately as
possible and mail this form to:
HOMA PUMP TECHNOLOGY INC.
390 BIRMINGHAM BOULEVARD
ANSONIA, CT 06401
ATTN: SERVICE MANAGER
Receipt of completed report will initiate operational warranty.
Reports that are not returned can delay or void warranty.
1.) Pump User's Name: _____________________________________________________________
Site Location: __________________________________________________________________
Site Contract: __________________________________________________________________
Unit Supplied By: _______________________________________________________________
2.) HOMA Pumps Model__________________________________ Serial No._____________________
Voltage____________ Phase_________________ Hertz________________ Horsepower________
Method Used to Check Rotation (viewed from bottom) __________________________________
Does Impeller Turn Freely By Hand: YES________ NO _________
3.) Condition of Equipment: EXCELLENT_____________ GOOD ____________ AVERAGE___________
Condition of Cable Jacket : EXCELLENT___________GOOD ____________ AVERAGE___________
Resistance of Cable and Pump Motor (measured at pump control)
1 Phase: U1 – U2 _________ Ohms; U1 - Z2 ________ Ohms; U2 – Z2 _________ Ohms; T1 – T2 ________Ohms
3 Phase: U - V_____________ Ohms; V - W ____________Ohms; U -W _________Ohms, T1 – T2 ________ Ohms
Resistance of Ground Circuit Between Control Panel and Outside of Pump __________Ohms
MEG Ohm Check of Insulation:
U to Ground _______________ V to Ground _______________ W to Ground____________
4.) Condition of Equipment at Start-Up: Dry __________ Wet _____________ Muddy_________
Was Equipment Stored:_______________ Length of Storage ________________________
Describe Station Layout ___________________________________________________________
5.) Liquid Level Controls: Model_____________________________ Type ______________________
Is Control Installed Away From Turbulence?____________________________________________
Operation Check: (IF FLOAT SWITCHES SUPPLIED).
Tip lowest float (stop float), all pumps should remain off.
Tip second float (and stop float), one pump comes on.
Tip third float (and stop float), both pumps on (alarm on simplex).
Tip fourth float (and stop float), high level alarm on (omit on simplex).
6.) Electrical Readings:
Single Phase:
Voltage Supply at Panel Line Connection, Pump Off, L1- L2 _______ L1-Ground ______ L2-Ground _________
Voltage Supply at Panel Line Connection, Pump On, L1- L2 ________ L1-Ground _______ L2-Ground ________
Amperage: Load Connection, Pump On, U1________________ U2 _______________ Z2 _________
Resistance Across Thermal Switch leads T1-T2 _______ ohms
Three Phase:
Voltage Supply at Panel Line Connection, Pump Off, L1-L2_________ L2-L3 _______ L3-L1 ______
Voltage Supply at Panel Line Connection, Pump On, L1-L2_________ L2-L3 _______ L3-L1 ______
Amperage Load Connection, Pump On, L1_____________ L2_____________ L3_______________
Resistance Across Thermal Switch leads T1-T2 _______ ohms
Pg. 14
Installation, Operation & Maintenance Manual
Page 15
A Series
7.) S
tarting Devices Are pumps being started DOL, or with Soft Start device. Indicate manufacturer of Soft Starter. ___________ Are any vibrations evident while pump is being controller by the soft starter? __________________________ Are pumps being operated with VFD (Variable Frequency Drive)? _______ Please indicate brand and model VFD: _________________________________________________________ Are load reactors being used between VFD output and pump? ______ Please indicate size _______________ What ramp up and decel time is the VFD set for? Accel __________ seconds, Decel: _________ seconds What is the minimum frequency the pump can operate at in this system? ______Hz. Is low speed limit set?_______
8.) Final Check: Are Thermal Switches properly wired? _______What Over-temperature Relay is being used? ____________ Is Pump Seated On Discharge Properly? ______________ Check For Leaks? __________________ Does Check Valve Operate Properly? ________________________________________________ Flow: Does Station Appear To Operate At Proper Rate ___________________________________ Vibration Level: Measured _____________________ Observed_____________________________ Has the cooling jacket been vented? _________ Is a permanent cooling jacket vent installed? _______
COMMENTS: _____________________________________________________________________
9.) Equipment Difficulties During Start-Up:_________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________
10.) I Certify this Report to be accurate. Authorized Homa Service Representative:
___________________________________________________________ Phone #____________________ (Signature)
DATE_______________________ Pump Station Owner/ Operator ___________________________________________________________ Phone # ____________________
(Signature) DATE _______________________
Pg. 15
Installation, Operation & Maintenance Manual
Page 16
A Series
230 #
A Series Technical Details
The following is offered as a general guide to values and capacities commonly used.
Resistance Readings (ohms) Pump Weight
230V 230V 460V
HP / RPM
2.5HP-1750 D 2.2 5.0 1.5 5.0
2.8HP-1160 T N/A 2.7 5.0 230 #
2.9HP-1750 N 2.2 5.0 3.1 11.0 230 #
2.9HP-1750 T 1.6 4.4 3.1 11.0 230 #
3.5HP-1750 D N/A 1.9 5.5 230 #
3.8HP-1160 T N/A 1.5 2.5 240 #
4.3HP-1750 N 1.5 3.0 1.5 4.2 240 #
4.3HP-1750 T 1.5 4.2 240 #
5.1HP-1750 T 1.1 2.6 N/A N/A 250 #
5.5HP-1750 N 0.9 1.9 1.3 3.7 250 #
5.5HP-1750 T N/A 1.3 3.7 250 #
6.2HP-1160 T N/A 1.3 3.7 250 #
6.7HP-1750 T 0.7 1.9 N/A N/A 260 #
7.5HP-1750 N 0.8 1.5 0.9 2.6 260 #
7.5HP-1750 T N/A 1.2 3.0 260 #
8.3HP-1160 T N/A 0.9 2.6 260 #
9.7HP-1750 T 0.5 1.4 N/A N/A 260 #
9.8HP-1160 P N/A 0.7 2.2 290 # 10HP-1750 N 0.3 0.9 0.6 1.9 290 # 10HP-1750 T N/A 0.6 1.9 290 #
11.4HP-1750 T 0.4 0.8 N/A N/A 290 # 13HP-1750 P N/A 0.5 1.8 350 #
15.3HP-1160 P N/A 0.5 1.1 350 # 20HP-1750 P N/A 0.5 1.1 400 #
21.5HP-1160 P N/A 0.5 1.1 400 # 29HP-1750 P N/A 0.4 0.7 500 #
*Values should be as indicated between any 2 power leads. Note: Resistance values include 30’cable, and should be within +/- 10% of above value.
Above 30 HP, resistance values between 230 and 460 volt machines vary by less than 0.1 ohm. Consult factory with specific requirements.
Impeller Bolt Torque: 10MM- 26FT#, 12MM-45FT#, 16MM-108FT#, 20MM- 210FT# Impeller to Bottom Plate Clearance: (ASC) .020” minimum clearance. Pump Rotation Right hand (CW) looking down from top of motor, CCW looking at bottom of pump. Seal Probes: N motor pumps use a 12mm seal probe P motor pumps use 20mm seal probe.
Single wire probes are for non classified areas, and 2 wire probes are for Hazardous areas.
1 Phase 3 Phase * 3 Phase *
U1 - U2 / U1 - Z2 U-V-W U-V-W
Approx. (Lbs.)
Pg.16
Installation, Operation & Maintenance Manual
Page 17
A Series
A Series Technical Details
Seal Chamber Oil: White Mineral Oil (Chevron Lubricating Oil FM 32, 46, 68)
Seal Oil Volume
ALL N FRAME MOTORS 2.5L ALL T FRAME MOTORS 2.5L ALL P FRAME MOTORS 3.7L CURRENT D MOTORS________0.9L F, G & H FRAME SEAL OIL VOLUTE VARY BY HP, PLEASE CONSULT FACTORY WITH SPECIFIC PUMP MODEL.
Seal Oil Level
With pump lying on its side and oil port at 12:00, measure from the top of housing with gasket in place, to the oil level.
A Series T, N & P motors: 1 1/2” from top of housing to oil level
Minimum Distance between 2 pumps 3” Discharge 4” Discharge 6” Discharge 8” & Larger
AK Min N/A Min 10” Min 13” Please consult AV Min 8” Min 10” Min 13” factory for lay- AMX Min 8” Min 10” Min 13” out information
Pg. 17
Installation, Operation & Maintenance Manual
Loading...