Hoffman 99411400 Installation Instructions Manual

Page 1
Installation Instructions For
Large Grounding Kit
99411400
Keps Nut
Lockwasher
3/8 Hex Nut
1/4–20 Hex Nut
Grounding Label
Ground Wire (not included)
Hoffman Enclosures Inc.
2100 Hoffman Way
Anoka, MN 55303–1745
(763) 422–2211 Tel
www.hoffmanonline.com
1. Insert the 1/4–20x7/8 bolt through the hole in the panel as shown.
2. Secure bolt with keps nut. The keps nuts must penetrate into the paint to insure electrical continuity.
3. Attach the ground wire and secure with 1/4–20 hex nut as shown.
4. Install the lockwasher under one of the nuts securing the panel to insure grounding between the panel and the enclosure.
5. Attach grounding label included adjacent to the bolt as shown.
87568835E 2002 Hoffman Enclosures Inc.Rev. A 103402 P/N 93216001
Page 2
Installation Instructions For
Large Grounding Kit 99411400
1. Secure keps nut on each ground stud. The keps nuts must penetrate into the paint to insure electrical continuity.
2. Attach the ground wire and secure with the 1/4–20 hex nuts as shown.
3. Attach the grounding labels included adjacent to the studs as shown.
Grounding Label
Keps Nut
1/4–20 Hex Nut
Ground Wire (not included)
87568835E 2002 Hoffman Enclosures Inc.Rev. A 103402 P/N 93216001
Page 3
For Variable Depth Disconnect Devices
And For Flexible Cable Disconnect Devices
In Hoffman Bulletin A25
Wall Mounted Disconnect Enclosures
Rev. B 113357 P/N 99401665E 2005 Hoffman Enclosures Inc.®E 2005 Hoffman Enclosures Inc.
3Point Latching2Point Latching
87569072
Page 4
WARNING
The functions, fits, and clearances of the installation described hereon are calculated from information supplied by the manufac­tures of the equipment to be installed. Be certain to check the function, fits, and clearances of all equipment both before and after installation to assure that it operates properly and safely and meets all applicable codes, standards, and regulations.
In the event the completed installation does not function properly or fails to meet any such codes, standards, or regulations, do not attempt to make alterations or operate the equipment. Report such facts immediately to:
Customer Service Dept.
Hoffman Enclosures Inc.
2100 Hoffman Way
Anoka, MN 553031745
(763) 4222211
NOTICE
To maintain the environmental rating of this enclosure: install in any opening, only listed or recognized dis­connect devices, external mounting feet, or conduit hubs that have the same environmental rating as the enclosure. Install in compliance with the installation instructions of the device.
Installation Instruction Index
Brand of Disconnect
Type
See Pages
AllenBradley 1494V CutlerHammer C361/C371 General Electric STDA Square D 9422 CutlerHammer C371 Flex Shaftt General Electric SCH Siemens I−T−E Max Flext Square D 9422
Variable Depth Variable Depth Variable Depth Variable Depth Flexible Cable Flexible Cable Flexible Cable Flexible Cable
4,5 6,7
8,9 10,11 12,13 14,15 16,17 18,19
INSTALLATION STEPS
Step 1 Drill mounting holes in panel for specific disconnect device being installed. See installation instruc-
tion index above for appropriate panel drilling instructions. Additional holes may be required when using fused switches. See disconnect manufacturers instructions.
Step 2 Install operating handle on enclosure flange in holes provided. Follow disconnect manufacturers instructions.
Step 3 Install disconnect device on panel. Follow disconnect manufacturers instructions for installation and adjustment.
Step 4 Install door hardware on enclosure door. See table 3 on page 3 for selection of appropriate 2point or 3point door hardware. Follow disconnect manufactures instructions and Hoffman additional information to install door hardware. See disconnect manufactures instructions to adjust door hardware to properly in­terlock to disconnect operating handle.
2 87569072
Page 5
Correct position of upper roller assembly, rivet, and latch bar.
Rivet here
Rivet here
(To Open)
Latch bar post
Cover interlock bracket
Latch bar bracket
Latch bar
M4 or M9 Square D door hardware.
TABLE 3 DOOR HARDWARE REQUIRED
Disconnect
Brand
AllenBradley
Bulletin 1494V
Cutler Hammer
Type C361 Type C371
Type C371 Flex Shaft
General Electric
Type STDA
Type SCH
Square D
Class 9422
20” 24” 30” 36”
Enclosure Height
2Point
1494VL1
C361 KJ4
OR
C361 KJ6
TDV1
9423M4
OR
9423M9
42” 48” 60”
3Point
1494VL1 1494VL2
C361 KJ4
C361 KR
C361 KJ6
C361 KR
TDV1 TDV3
9423M4 9423M3
9423M9 9423M3
Additional
Mounting
Information
See Note 1
See Note 2
See Note 3
See Note 4
and
Fig. 6
M3 (3rd) roller assembly
Rivet here
Siemens
ITE
Max Flex
DKR2
DKR3
See Note 5
Sq. D Door Hardware
Figure 6
Note 1 Hoffman enclosures include a latch bar and have a door catch and studtype standoffs provided on the door. Therefore; AllenBradley door hardware items 19, 20, 21, 22, 24, 25, 26, and the AllenBradley door catch (shown in figure 4 of the AllenBradley instructions) can be omitted. The AllenBradley pivot plate (item 23) is to be installed on the studtype standoffs with the sleeve and locknut provided by Hoffman. Fasten the AllenBradley defeater actuator (item 30) to the latch bar. The latch bar has six (6) mounting holes. Use the top holes for eight (8) inch deep enclosures, middle holes for ten (10) inch deep enclosures, and the bottom holes for twelve (12), and sixteen (16) inch deep enclosures.
Note 2 Hoffman enclosures include a latch bar and have a door catch and stud type standoffs provided on the doors. Therefore the CutlerHammer door catch and some door hardware items will not be needed (CH items no. one (1) through six (6)). Install the CH defeater bracket (item 28) onto latch rod (furnished with enclosure). The latch rod has six (6) mounting holes. Use the top pair of holes for eight (8) inch deep enclosures, the middle holes for ten (10) inch deep enclosures, and the bottom holes for twelve (12) inch and sixteen (16) inch deep enclosures. Adjust door hardware as required.
Note 3 Hoffman enclosures include a latch bar and have a door catch and studtype standoffs provided on the door. Therefore, G.E. door hardware items 17, 18, 20, 21, and 22 can be omitted. Use optional mounting of upper latch (figure 1a on G.E. instructions) where upper latch roller contacts top of enclosure flange. The G.E. roller assembly (item 19) should be installed on the studtype standoffs with the locknut provided by Hoffman. Install the G.E. interlock bracket (item 23) ont the latch bar. The latch bar has six (6) mounting holes. Use the top holes for for eight (8) inch deep enclosures, middle holes for ten (10) inch deep enclosures, and the bottom holes for twelve (12), and sixteen (16) inch deep enclosures.
Note 4 Hoffman enclosures include a latch bar and have a door catch and studtype standoffs provided on the door. Therefore, Square D door hardware items 10, 13, 22, 23, 24, 25, and 26 can be omitted. The Square D latch arm (item 16) is to be installed on the studtype standoffs with the sleeve and locknut provided by Hoffman. Note: Assemble the upper Square D latching arm to the latch bar as shown in of Square D instructions. Also see Figure 6 (above) which shows correct assembly of door hardware. Fasten the Square D latch bar bracket (item 8) to the latch bar. The latch bar has six (6) mounting holes. Use the top holes for eight (6) inch deep enclosures, middle holes for ten (10) inch deep enclosures, and the bottom holes for twelve (12) and sixteen (16) inch deep enclosures.
Note 5 Hoffman enclosures include a latch bar and have a door catch and studtype standoffs provided on the door. Install the I−TE roller assembly on the studtype standoffs with the locknut provided by Hoffman. Fasten the I−T−E interlock defeater lever to the latch bar. The latch bar has six (6) mounting holes. Use the top holes for eight (8) inch deep enclosures, middle holes for ten (10) inch deep enclosures, and the bottom holes for twelve (12) and sixteen (16) inch deep enclosures.
87569072 3
E 2005 Hoffman Enclosures Inc.
Page 6
WallMounted Disconnect Enclosures
Installation Instructions for AllenBradley 1494V (variable depth) Disconnects
Figure 3
* E= 4.75 for 8.00” Deep E= 7.09 for 10.00” Deep E= 11.62 for 12.00” Deep E= 11.62 for 16.00” Deep
4 87569072
E 2005 Hoffman Enclosures Inc.
Page 7
Installation Instructions for AllenBradley 1494V (variable depth) Disconnects
159
A25
Wall M
d Di
t Encl
AllenBradley Bulletin
1494V Disconnect or
operator for Circuit
Breaker
*1494VDS30
(30 AMP)
*1494VDS60
(60 AMP)
*1494VDS100
(100A./series B)
*1494VDS200
(200 A./series B)
1494VM40 for 15150
AMP West.
1494VM50 for 15150
AMP West.
1494VM60 for 70400
AMP West.
WallMounted Disconnect Enclosures
TABLE 1
SubPanel Drilling
Enclosure Depth
8.00
H
H
1.41 3.75 8.28 1.97 2.44 4.33 3.94 1.44 − − − − − − − −
Do Not
Install
Do Not
Install
3.50 5.84 10.38 1.38 1.09 4.50 1.38 1.09 − − − − − − − −
Do Not
Install
Do Not
Install
10.00
3.75 8.28 1.97 2.44 4.33 3.94 1.44 − − − − − − − −
Do Not
Install
Do Not
Install
Do Not
Install
12.00
16.00 H
7.14 2.36 2.80 4.92 4.72 1.69 − − − − − − − −
10.94 1.38 1.25 7.25 1.38 1.25 .69 2.03 10.62
9.88 1.72 1.78 8.44 1.72 1.78 .86 1.16 10.75
J K L M N P Q R Hole Size
.
1032 UNF
.159
1032 UNF
.201
1/420 UNC
.136
832 UNF
.201
1/420 UNC
.201
1/420 UNC
* See AB Instructions For Locating Fuse Blocks.
NOTE: AllenBradley variable depth disconnects are provided with connecting rods that must be cut to length to fit the enclosure depth (from flange surface to subpanel surface). See table 2 and AllenBradley instructions.
TABLE 2
Bulletin Hoffman Disconnect Enclosure Description
Enclosure Depth
C
AllenBradley
D (1)
8.00 6.88
10.00 8.88
ounte
sconnec
osure
12.00 10.88
16.00 14.88
1) This enclosure depth dimension is used to calculate the length of AllenBradley connecting rod(s).
87569072 5
E 2005 Hoffman Enclosures Inc.
Page 8
WallMounted Disconnect Enclosures
Installation Instructions for CutlerHammer C361 and C371
Disconnects with Variable Depth Operating Mechanisms
* E= 4.75 for 8.00” Deep
Figure 3
Hole Pattern For Disconnect Switch Size
C361NC/C361SC 30 AMP
C361ND/C361SD 60 AMP
C361NE/C361SE 100 AMP
C361NF/C361SF 200 AMP
Hole Pattern For Circuit Breaker Frame Size
HMCP, FS, FH, EHD FDB, FD, HFD 150 AMP
HMCP, JS, JH, JL, JD, JDB, HJD, JDC 250 AMP
HMCP, HK, KS, KD, DK, KDB, HKD 400 AMP
LH, LS, LC 600 AMP
E= 7.09 for 10.00” Deep E= 11.62 for 12.00” Deep E= 11.62 for 16.00” Deep
6 87569072
E 2005 Hoffman Enclosures Inc.
Page 9
WallMounted Disconnect Enclosures
Do Not
Do Not
Install
D
Not
Install
A25
Wall M
d Di
t Encl
Installation Instructions for CutlerHammer C361 and C371
Disconnects with Variable Depth Operating Mechanisms
TABLE 1
SubPanel Drilling
Circuit Breaker or
Disconnect Switch
C361NC (30A) − − 1.68 4.03 8.56 2.47 4.00 7.13 − − − − − − − − − 1032 UNF
C361SC (30A) − − 1.68 4.03 8.56 2.47 4.00 9.75 − − − − − − − − −
C361ND (60A) − − 1.68 4.03 8.56 2.47 4.00 7.13 − − − − − − − − − 10−32 UNF
C361SD (60A) − − 1.68 4.03 8.56 2.47 4.00 9.75 − − − − − − − − − 10−32 UNF
C361NE (100A) − − 1.50 9.48 8.38 2.34 5.50 7.13 − − − − − − − − − 10−32 UNF
C361SE (100A) − − 1.50 3.84 8.38 2.34 5.50 11 .88 − − − − − − − − − 10−32 UNF
C361NF (200A) − −
C361SF (200A) − −
HMCP, FS, FH, EHD,
FDB, FD, HFD
JS, JH, JL 250A 6.22 10.75 3.13 7.25 1.38 .31 6.95 2.75
HMCP 250A 6.22 10.75 3.13 7.25 1.38 .31 6.95 2.75 1/4−20 UNC
KH, KS, DK, KDB, KD,
HKD, KDC
HMCP 400A
LH, LS, LC 600A
Frame
SizeH8” Deep
Do Not Do Not
Install
150A 3.91 6.26 10.79 2.62 4.50 1.38 − − − − − − − − 8−32 UNF
400A
Do Not
Install
H
10”
Deep
Install
o
Install
H
12”&16”
Deep
6.79 .81 8.50 15.50 − − − − − − − −
6.79 .81 8.50 15.50 − − − − − − − −
10.31 2.96 8.44 1.72 .31 6.95 3.18 1/420 UNC
10.31 2.96 8.44 1.72 .31 6.95 4.00 1/420 UNC
8.42 3.88 9.53 2.75 .23 10.05 4.32 1/420 UNC
J K L M N P Hole Size
1032 UNF
5/1618
5/1618
1032 UNF
UNC
UNC
NOTE: Cutler−Hammer variable depth disconnects are provided with connecting rods that must be cut to length to fit the enclosure depth (from flange surface to subpanel surface). See table 2 and CutlerHammer instructions.
TABLE 2
Bulletin Hoffman Disconnect Enclosure Description
Enclosure Depth
C
CutlerHammer
D (1)
8.00 6.88
10.00 8.88
ounte
sconnec
osure
12.00 10.88
16.00 14.88
1) This dimension is used to determine length to cut CutlerHammer connecting rods.
87569072 7
E 2005 Hoffman Enclosures Inc.
Page 10
WallMounted Disconnect Enclosures
Installation Instructions for General Electric Type STDA
Variable Depth Operating Mechanisms
* E= 4.75 for 8.00” Deep E= 7.09 for 10.00” Deep E= 11.62 for 12.00” Deep E= 11.62 for 16.00” Deep
Figure 3
8 87569072
E 2005 Hoffman Enclosures Inc.
Page 11
WallMounted Disconnect Enclosures
Install
A25
Wall M
d Di
t Encl
Installation Instructions for General Electric Type STDA
Variable Depth Operating Mechanisms
TABLE 1
SubPanel Drilling
G.E. Operating
Mechanism
TDOM1A QMRQMW 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
TDOM1JA QMRQMW 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
TDOM1B QMRQMW 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
TDOM1JB QMRQMW 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
TDOM2 QMRQMW 4 1/420
SDOM1A SE150 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
SDOM3 SF250 4 1/420
SDOM4 SG600 6 1/420
Frame Size
No. Of
Holes
Hole Size
H
8” Deep
Do Not
Install
Do Not
Install
Do Not
Install
H
10” Deep
Do Not
Install
4.38 8.91 1.69 2.75 10.88
Do Not
Install
H
12” & 16”
Deep
8.50 .69 7.00 7.25
6.91 1.34 3.35
J X Y
5.51 AND
12.20
SDOM1A TEB, TED 4 1/420 2.50 3.97 8.50 .75 3.00 6.75
SDOM1A
SDOM1AP
TDOM3 TFJ, TFK 4 1/420 3.97 8.50 1.69 2.75 10.88
TDOM4 JFRAME 4 1/420
TDOM5 TB4, TJH 4 1/420
TDOM6 K FRAME 4 1/420
TB1
TEC, TECL
4 1/420 2.50 3.97 8.50 .75 3.00 6.75
Do Not
Install
3.34 7.88 1.63 5.50 8.63
3.34 7.88 1.63 5.50 14.63
Do Not
Install
4.13 1.63 5.50 16.75
NOTE: General Electric variable depth disconnects are provided with connecting rods that must be cut to length to fit the enclosure depth (from flange surface to subpanel surface). See table 2 and General Electric instructions.
TABLE 2
Bulletin Hoffman Disconnect Enclosure Description
Enclosure Depth
C
G.E.
D (1)
8.00 6.88
10.00 8.88
ounte
sconnec
osure
12.00 10.88
16.00 14.88
1) This dimension is used to determine length to cut General Electric drive rod and stiffener rod (if used).
87569072 9
E 2005 Hoffman Enclosures Inc.
Page 12
WallMounted Disconnect Enclosures
Installation Instructions for Square D 9422
Variable Depth Operating Mechanisms
Figure 3
* E= 4.75 for 8.00” Deep E= 7.09 for 10.00” Deep E= 11.62 for 12.00” Deep E= 11.62 for 16.00” Deep
10 87569072
E 2005 Hoffman Enclosures Inc.
Page 13
WallMounted Disconnect Enclosures
Do Not
Do Not
A25
Wall M
d Di
t Encl
Installation Instructions for Square D 9422
Variable Depth Operating Mechanisms
TABLE 1
SubPanel Drilling
Square D
Operating
Mechanism
TCN, TCF 4 1,4,6,7 1024 2.25 4.59 9.13 .38 5.50 4.50
TDN, TDF 4 1,4,6,7 1024 2.25 4.59 9.13 .38 5.50 4.50
TEN, TEF 4 1,4,6,7 1024
TC 4 1,2,58 1024 2.50 4.41 8.94 .38 5.13 6.50
TD 4 1,2,47 1024 2.25 4.59 9.13 .47 5.19 5.25
TE 4 1,2,3,4 1/420
TF 4 1,2,3,4 5/1618
RG1 4 1,2,3,4 832 2.25 4.59 9.13 1.47 1.18 3.94
RN1 4 1,2,3,4 8−32 2.78 5.13 9.66 1.38 1.50 5.13
RP1 4 1,2,3,4 1024 2.78 5.13 9.66 1.56 1.50 7.13
RR−1
No. Of
Holes
4 1,2,3,4 1/420
4 1,2,3,4 .375 Dia.
Mtg. Hole
Position
Hole Size
H
8” Deep
Do Not
Install
Do Not
Install
Do Not Do Not
Install
H
10” Deep
4.59 9.13 .38 5.50 4.50
2.97 7.50 1.84 5.50 6.50
Do Not
Install
Install
H
12” & 16”
Deep
6.88 1.31 9.44 8.00
9.00 .19 6.63 6.56
7.63 2.50 2.00 9.25
J X Y
NOTE: Square D variable depth disconnects are provided with connecting rods that must be cut to length to fit the enclosure depth (from flange surface to subpanel surface). See table 2 and Square D instructions.
TABLE 2
Bulletin Hoffman Disconnect Enclosure Description
Enclosure Depth
C
Square “D”
D (1)
8.00 6.88
10.00 8.88
ounte
sconnec
osure
12.00 10.88
16.00 14.88
1) This dimension is used to determine length to cut Square D operating rods. Use .070 for “T” dimension.
87569072 11
E 2005 Hoffman Enclosures Inc.
Page 14
WallMounted Disconnect Enclosures
Installation Instructions for CutlerHammer C371
Flex Shaftt Flexible Cable Operating Mechanisms
Figure 3 CH
12 87569072
E 2005 Hoffman Enclosures Inc.
Page 15
WallMounted Disconnect Enclosures
A25
Wall M
d Di
t Encl
Installation Instructions for CutlerHammer C371
Flex Shaftt Flexible Cable Operating Mechanisms
TABLE 1
SubPanel Drilling
Circuit Breaker Frame
Size
F 8−32 1.375 4.500 1.38
J 1/4−20 1.375 7.250 1.38
K 1/420 1.719 8.438 1.88
Bulletin Hoffman Disconnect Enclosure Description Enclosure Depth H
Hole Size
ounte
sconnec
X Y C
TABLE 2
8.00 3.25
10.00 5.59
osure
12.00 10.13
16.00 10.13
min
Step1 Determine disconnect hole pattern from Figure 3 CH and the above tables. See disconnect manufacturers instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer to National Electrical Code Article 43010b for wire bend space required.
87569072 13
E 2005 Hoffman Enclosures Inc.
Page 16
WallMounted Disconnect Enclosures
Installation Instructions for General Electric SCH
Flexible Cable Operating Mechanisms
Figure 3 GE
14 87569072
E 2005 Hoffman Enclosures Inc.
Page 17
WallMounted Disconnect Enclosures
A25
Wall M
d Di
t Encl
Installation Instructions for General Electric SCH
Flexible Cable Operating Mechanisms
TABLE 1
SubPanel Drilling
Cable Mechanism Circuit Breaker No. of Holes Hole Size
SCOM1A E150 4 8−32 1.38 4.88 1.38
SCOM1EF
SCOM1G SG600 4 1224 1.81 7.75 1.84
SCOM1K SK1200 4 5/1618 2.75 14.25 2.75
SE150 4 1032 1.38 4.88 1.38
SF250 4 1224 1.38 7.75 1.38
TABLE 2
X Y C
min
Bulletin Hoffman Disconnect Enclosure Description
Enclosure Depth
C
H
8.00 3.25
10.00 5.59
ounte
sconnec
osure
12.00 10.13
16.00 10.13
Step1 Determine disconnect hole pattern from Figure 3 GE and the above tables. See disconnect manufacturers instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer to National Electrical Code Article 43010b for wire bend space required.
87569072 15
E 2005 Hoffman Enclosures Inc.
Page 18
Bulletin A25 Wall−Mounted Disconnect Enclosures
Installation Instructions for Siemens (I−T−E) Max Flext
Flexible Cable Operating Mechanisms
Figure 3 ITE
16 87569072
E 2005 Hoffman Enclosures Inc.
Page 19
WallMounted Disconnect Enclosures
A25
Wall M
d Di
t Encl
Installation Instructions for Siemens (I−T−E) Max Flext
Flexible Cable Operating Mechanisms
TABLE 1
SubPanel Drilling For Disconnect Switches
IT−E*
Mechanism
FHOS06036R 30 A SW. 4 & 3 2.00 1.69 5.10 2.88 1.50 .66 1.89
FHOS06036R 60 A SW. 4 & 3 2.00 1.69 5.10 2.88 1.50 .66 1.89
FHOS06036R 100 A SW. 4 & 3 2.00 .82 5.10 3.21 1.81 .66 3.00
FHOS20036R 200 A SW. 4 & 3 2.50 1.00 5.50 1.00 7.86 .62 5.44
IT−E* Mechanism No. of Holes Hole Size
FHOE036 4 8−32 1.00 5.00 1.00
FHOF036 4 1/420 1.50 7.50 1.50
FHOJ036 4 1/420 2.50 9.75 2.50
FHOLM036 4 1/420 2.50 9.75 2.50
Fits
Disconnect
Device
No. of Holes
A B C D E F
TABLE 1
SubPanel Drilling For Circuit Breakers
X Y C
min
G
min
* These mechanisms include 36” operating cables. If longer cables are needed, order I−T−E components separately.
TABLE 2
Location of Disconnect Operating Handle
Bulletin Hoffman Disconnect Enclosure Description Enclosure Depth H
8.00 3.25
10.00 5.59
ounte
sconnec
osure
12.00 10.13
16.00 10.13
Step1 Determine disconnect hole pattern from Figure 3 IT−E and the above tables. See disconnect manufacturers instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer to National Electrical Code Article 43010b for wire bend space required.
87569072 17
E 2005 Hoffman Enclosures Inc.
Page 20
WallMounted Disconnect Enclosures
Installation Instructions for Square D 9422
Flexible Cable Operating Mechanisms
Figure 3 SQ D
18 87569072
E 2005 Hoffman Enclosures Inc.
Page 21
WallMounted Disconnect Enclosures
CFT
A25
Wall M
d Di
t Encl
Installation Instructions for Square D 9422
Flexible Cable Operating Mechanisms
TABLE 1
SubPanel Drilling
Cable
Mechanism
CFT
CGJ GJL 4 1,2,3,4 8−32 1.18 3.94 2.50
CFA FAL, FHL 4 1,2,3,4 832 1.50 5.13 3.75
CKA KAL, KHL 4 1,2,3,4 1024 1.50 7.13 3.75
CLA** LAL, LHL
* See Square “D” instructions for range of “C” dimension which vary for 36”, 60” and 120” cable lengths.
** See Square “D” instructions for relationship between 1/420 and .375 diameter holes for LA circuit breaker.
Disconnect
Mechanism
TCN, TCF 4 1,4,6,7 1024 5.50 4.50 1.00
TDN, TDF 4 1,4,6,7 1024 5.50 4.50 1.00
TEN, TEF 4 1,4,6,7 1024 5.50 4.50 1.00
No. of Holes Hole Position Hole Size
4 1,2,3,4 1/420 6.63 6.56 2.25
4 1,2,3,4 .375 Dia. 2.00 9.25 − −
X Y C
min*
TABLE 2
Bulletin Hoffman Disconnect Enclosure Description Enclosure Depth H
8.00 3.25
10.00 5.59
ounte
sconnec
osure
12.00 10.13
16.00 10.13
Step1 Determine disconnect hole pattern from Figure 3 SQ. D and the above tables. See disconnect manufacturers instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer to National Electrical Code Article 43010b for wire bend space required.
87569072 19
E NIL Hoffman Enclosures Inc.
Page 22
Hoffman Enclosures Inc.
2100 Hoffm an Way Anoka, MN 553031745 (763) 4222211
www.hoffmanonline.com
Pentair Electroni c Packagi ng
170 Commerce Drive Warwick, RI 02886 (401) 7323770
www.pentair−ep.com
Mexico
Pentair Enclos ures, S. de R.L. de C.V. Federico T. de la Chica No. 8 Piso 4 A Circuito Comercial Plaza Satélite Ciudad Satélite, Naucalpan, México C.P. 53100 011−5255−53938263
Canada
Hoffman−Schroff 111 Grangeway Avenue, Suite 504 Scarborough, Ont ario M1H 3E9 (416) 2892770 1−8006682500 (Canada only)
Germany
Schroff GmbH Langenalber Str. 96−100 75334 Straubenhardt 49 (07082) 794−0
Great Brit ain
Schroff UK Ltd. Maylands Avenue Hemel Hempst ead, Hert s HP2 7DE 44 (01442) 240471
Sweden
Schroff Scandinavia AB Box 2003 12821 Skarpnäck 46 08683 61 00
France
Schroff Sas Z.I., 4 rue du Marais 67660 Betschdor f 33 03 88 90 64 90
Italy
Schroff srl Viale Milano, 119 21013 Gallarate (Varese) 39 0331 79 40 03
Singapore
Hoffman−Schroff Pt e. Ltd. #0168/71 German Centre 25 Internat ional Business Park Singapore 609916 65 5 6278 90
Japan
Schroff K.K. Nisso No. 13 Bldg. 4F 2−51 Shinyokohama KohokuKu, Yokohama shi Kanagawa 222−0033 81 (045) 47602 81
Finland
Schroff Scandinavia AB Peräsimentie 8 03100 Nummela 358 09 222 68 00
Norway
Schroff Scandinavia AB Bjoernerudveien 24 1266 Oslo 47 022 76 33 60
www.schroff.de
www.sc hroff.co.uk
www.sc hroff.se
www.sc hroff.fr
®
20 87569072
E 2005 Hoffman Enclosures Inc.
Page 23
®
Enclosure Alterations
Hoffman Enclosures Inc.
2100 Hoffman Way
Anoka, MN 55303−1745
(763) 4222211
Hoffman cannot assure the safety or effectiveness of any alterations or additions not made by Hoffman Enclosures Inc. However, the following information may be helpful. These instructions do not eliminate the need to consult with equipment manufacturers and to observe all regulatory agency procedures and safe practices to assure the proper electrical and mechanical function of Hoffman products in each particular application.
1. REPAINTING
See “Instructions for Repainting Hoffman Standard Paint Finishes”, part number
23155002.
4. PANEL INSTALLATION
When the interior panel is being installed, it may be necessary to bend one or more mounting studs slightly to permit the panel to fit in place. Simply position the panel on the studs
2. MOUNTING INSTRUCTIONS
a. Wall mounted enclosures have either an
internal mounting means or external mounting feet. Proper fasteners must be used in all mounting holes to secure the enclosure to the wall.
b. Floor mounted enclosures have floor
stands (legs) which include mounting plates. Proper fasteners must be used in all mounting holes to securely anchor the enclosure to the floor.
3. DOOR CLOSING ADJUSTMENTS
a. Single door (wall mounted)
If the surface on which the enclosure is mounted is not flat, the door may not open and close properly. Also, if heavy equipment is mounted on a large door, the door may sag slightly. If the top of the door strikes the lip which extends around the body opening, place metal shims behind the mounting foot which is located at the bottom of the enclosure and closest to the door hinge. Place the shims between the mounting foot and the wall or mounting surface. Be sure all mounting screws are tightened securely.
b. Two door (floor mounted)
The overlapping doors are factoryfitted to meet evenly at the top and bottom. If the floor under the enclosure is not level, the doors will not close evenly. In this case, place metal shims under the corners of the enclosure. The enclosure should be bolted in place with the doors closed to prevent tipping when installing shims. Shims under the right front corner will raise the right door. Shims under the left front
that line up properly and pry the other studs into position with a suitable screwdriver inserted through the panel holes.
5. REMOVING HINGE PINS FROM CONTINUOUS HINGES
This can be a difficult operation requiring one or more people. This procedure is best accomplished by using a small diameter punch to drive the hinge pin toward the bottom of the enclosure. Lay the wallmounted and floormounted or freestanding enclosure on its back side (see note 7 below). When the hinge pin protrudes about two inches below the bottom hinge barrel, bend the end of the pin 180° so it is shaped like the letter “J”. Use an electric or air powered vibrating hammer fitted with a tool which has a hole in the end to fit over the hinge pin, and drive the hinge pin out while opening and closing the door. To install the hinge pin, straighten the pin and drive it in with the vibrating hammer while opening and closing the door. Most hinge pins have one end chamfered, so be sure to start the chamfered end first when installing the pin.
6. PRINT POCKET
The print pocket on the door can be inverted or removed entirely.
7. LIFTING ENCLOSURES BY EYEBOLTS
To lift an enclosure which has eyebolts or mounting feet, be sure to use all the eyebolts and top mounting feet provided. Arrange the chains and cables with spreader bars so you are lifting straight up on the eyebolts or top mounting feet.
corner will raise the left door. It is important that the doors meet evenly to insure a proper seal against liquids and dust. Be sure all mounting bolts are tightened securely.
Rev. B 110539 P/N 99401677E 2004 Hoffman Enclosures Inc.
www.hoffmanonline.com
87569073
Page 24
ACCESSORIES AND HARDWARE
Hoffman cannot assure the safety or effectiveness of any alterations or additions not made by Hoffman Enclosures Inc.
Lock kits
and latch kits are available for field or factory installation on many types of Hoffman enclosures. Lock kits provide keylocking capabilities. Latch kits permit rapid access to enclosure interiors while retaining the oil tight and dust tight features.
Louver plate kits
provide ventilation in
enclosures where internal heat is a problem.
Floor stand kits for converting wall mounting enclosures to floor mounting are available for field or factory installation on single door NEMA 12 and NEMA 4 enclosures.
Drip shield kits are available for field or factory installation on single door and double door NEMA 12 enclosures.
Electrical interlocks provide a positive internal safety lockout on electrical enclosures while the enclosure contents are energized.
Swingout panel kits provide a means of mounting gauges, switches, pilot lights and other components near the front of the enclosure.
OTHER HOFFMAN PRODUCTS
S NEMA 1, NEMA 3R, NEMA 4, NEMA 4X,
NEMA 9, and NEMA 12 enclosures
S Oil tight JIC boxes and troughs.
S Oil tight wireway and layin wireway
S NEMA 1 wireway
S Oil tight pushbutton enclosures
S Cutout boxes, pull boxes, and transformer
cabinets
S Non−metallic enclosures
Safety Lockouts protect personnel and equipment by enabling multiple padlocks to be installed on a deenergized switch.
Touchup paint
is used to repair the finish of
enclosures and panels.
Window kits
are available for many types of
Hoffman enclosures.
Corrosion inhibitors protect interior components of enclosures, wireway, consoles, etc. from corrosion. There are no coatings, oils, or greases to apply.
Hole seals are used to seal extra conduit openings, pushbutton holes, cutouts, etc. against dust, dirt, oil, and water.
Terminal kit assemblies provide an easy method to mount terminal blocks in many types of Hoffman enclosures.
Folding Shelves can be used to support instruments and test equipment.
Pedestals are used to provide floor mounting at a working height for small to medium size enclosures.
S Aluminum enclosures and boxes
S Console cabinets
S Custombuilt enclosures of all types
S Instrument and electronic enclosures
S Environmental control products
S EMI/RFI shielded enclosures
S Wiring duct
S Modified Standard Enclosures
S Stainless steel enclosures and boxes
2 87569073
E 2004 Hoffman Enclosures Inc.
S CoDeveloped Enclosures
Loading...