HOCHIKI YBN-UA(WHT) RECESS BASE A DA PTOR
The YBN-UA(WHT) is a Recess Base adaptor which allows YBN-R/3(WHT) base and ALK-ASN analogue
sensor to be flush mounted, this is particularly suited to where unobtrusive detection is required.
Installation
To install the YBN-UA, a YYA-A fixing kit should be obtained this consists of the parts shown below.
Firstly a hole with a diameter of 115mm should be cut in the ceiling tile. The pressure clamps should then be
fitted to the YBN-UA in a vertical position using the screw fittings and the fixing screws, refer to fig.1. The next
step is to pull the cables through and fit the YBN-UA into the hole in the ceiling and whilst looking through the
Recess Adaptor cable hole, loosen the screws until the pressure clamps lower into place refer to fig.2. Retighten the bracket screws until the pressure clamps are fixed in the horizontal position.
Fig 1 Fig 2
Once the YBN-UA has been secured, the relevant mounting base needs to be fixed with the M4 x 16mm screws
supplied. When fitting the base the locating “LED” mark on the base must be lined up with the locating “LED"
mark on the YBN-UA, please refer to fig.3. Once the base has been fitted the relevant detector/sensor can then
be attached, please refer to fig.4.
Fig 3 Fig 4
Please find below a list of detectors/sensors and the height they will be from the ceiling when fitted to the
relevant bases.
Hochiki Australia Pty Ltd No.2-1-001/ISS1/FEB17
![](/html/ce/ce48/ce488a65acbda97dbe92222fd6cc97fccb203b73dbd9eddd8b63b02964e2f956/bg2.png)
Operating Temperature Range
Specification
Precautions
Ensure that the base is installed in accordance with Local Standards or Regulations.
Check that the detector/sensor is compatible with the base type.
Only install in suitable environments, the following should be avoided:-
Excessive ambient temperature.
Where excessive condensation or moisture is present.
Hazardous areas.
Do not use a high voltage tester on the base or detector
Ensure that the base adaptor is securely fixed to the ceiling or other suitable surface.
Ensure that the base terminals are securely fastened.