Hochiki YBN-UA User Manual

Page 1
Hochiki YBN-UA Recess Base Adaptor
The YBN-UA is a Recess Base adaptor which allows detect or s /sensors from the CDX/ASX range to be flush mounted, this is particular ly s uited to where unobtrus iv e detection is required.
Compatibility
The YBN-UA will allow mos t types of mounting bas es to be fit ted, please f ind below a list of compatible base types.
Base Name Part No. Base Name Part No.
CDX Simp le Base without REM LED YBN-R/4 & 6 CDX SAV WIRE with REM. LED YBO-R/5PA &6PA CDX Sim ple Base with REM L ED YBO-R/5 CDX 12V Base YBO-R/12V CDX SAFELINE Base without REM LED YBN-R/4SK & 6SK ESCO & Mini-2000 YBO-R/5E CDX SAFELINE with REM LED YBO-R/5SK ASX Analogue Base YBN-R/3 CDX LIVE L INE with RE M L ED YBO-R/5ZD CDX Relay Base - Latchi n g YBO-R/6R CDX Relay Base - Non Latch ing YBO-R/6RN CDX Relay Base with Scho ttky Diode YBO-R/6RS
Each base type has been des igned in ac c or danc e with local standards and m ay not necessarily be suitable for use on any A lar m Control Panel. Check c om patibility with t he A lar m Control Panel manufacturer before installat ion.
Installation
To install the YBN-UA, a YYA-A fixing kit s hould be obtained this consists of the parts shown below.
Pressure clamp x 2 Screw fitting x 2
Screw x 2
Firstly a hole with a diameter of 115m m should be cut in the ceiling tile. The press ur e c lam ps should then be fitt ed to the YBN-UA in a v er tical position using the screw fitt ings and the fixing screws , refer to fig.1. T he nex t step is to pull the cables through and fi t the YBN-UA int o the hole in the ceiling and whilst looking through the Reces s A daptor cable hole, loosen t he s c r ews until the pressure c lamps lower into place refer to fig.2. Re-t ighten the bracket s c r ews until the pressure c lam ps are fixed in the horiz ontal position.
Fig 1 Fig 2
Once the YBN- UA has been s ec ur ed, the relevant mounting base needs to be f ix ed with the M4 x 16mm screws supplied. When fitting the base the locating “ LE D” m ar k on the base must be lined up wit h the locating “LED" m ar k on the YBN-UA, pleas e r efer to fig. 3. Once the base has been fitted the relev ant detector/ s ens or can then be attac hed, please refer t o fig.4.
2-3-0-377/ISS2/AUG03
Page 2
LED
Fig 3 Fig 4
Please find below a list of detectors /sensors and the height they will be from the ceiling when fitted to the relevant bases .
YBN STYLE BASES YBO STYLE BASES
ALG-E N/A N/A 26mm N/A N/A N/A N/A N/A N/A AIE-E N/A N/A 32mm N/A N/A N/A N/A N/A N/A
ASX
ATG-E N/A N/A 28mm N/A N/A N/A N/A N/A N/A ACA-E N/A N/A 26mm N/A N/A N/A N/A N/A N/A SLR-E & E3 26mm 26mm N/A 31mm 31mm 31mm 31mm 31mm 31mm SIJ-E 26mm 26mm N/A 31mm 31mm 31mm 31mm 31mm 31mm
CDX
DFJ Range 27mm 27mm N/A 32mm 32mm 32mm 32mm 32mm 32mm DCD Range 27mm 27mm N/A 32mm 32mm 32mm 32mm 32mm 32mm
R/4 & R/6
R/4SK & R/6SK
R/3
R/5,
R/6R,
R/6RN &
R/6RS
R/5SK R/5ZD
R/5PA &
R/6PA
R/5E R/12V
Specification
Operating Tem perature Range Humidity Range 10% to 95% RH Dimensions : Diamet er 140 mm Depth 46 mm Fixing Holes 48mm to 74mm Drilled Hole Size 115mm Weight 65g
-10 °C to +50 °C
Precautions
Ensure that t he bas e is ins talled in accordance with Loc al S tandards or Regulations. Check that the detector/s ens or is c om patible with the base t y pe. Only install in suit able env ir onm ents, the f ollowing s hould be av oided:-
Excessive ambient temperature.
Where excessiv e c ondensation or moist ur e is pr es ent.
Hazardous areas.
Do not use a high voltage tes ter on the base or det ec tor Ensure that t he bas e adaptor is securely fixed to the ceiling or other suitable surface. Ensure that t he bas e terminals are secur ely fastened.
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133 Facsimile: +44(0)1634 260132
Email: sales@hochikieurope.com
Web: www.hochikieurope.com
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description. Please check our web site for the latest version of this document.
2-3-0-377/ISS2/AUG03
Loading...