Hochiki SLR--24C, SLR--24VC, SLR--24H, SLR--24HC, SLV-24V Installation Instructions Manual

...
Connect wiring to the bases as shown in the wiring diagrams that follow. Detectors and bases may be mixed on the same initiating loop as long as the number of two-wire powered detectors does not exceed the specifications of the control panel (see Figure 2 below)
SMOKE DETECTOR DATA
BUILT-IN
TEST FEATURE
30/ZONE
17.7-30.0 VDC
HD3
FIG. 2
BREAK WIRE RUN TO PROVIDE SUPERVISION
DO NOT LOOP WIRE UNDER TERMINALS.
CONNECT WIRING TO TERMINALS AS SHOWN.
HSC-BASE
NS4-BASE NS6-BASE
BASE
PHOTOELECTRIC
5V RIPPLE MAX.
FILTERED DC
160 A
45 A
150 mA
15-33.0 VDC
NSTT-A100
30/ZONE
HCP-1008E CONTROL PANEL
HEAT ELEMENT RATING
TYPE OF DETECTOR
SENSITIVITY TEST DEVICES
COMPATIBILITY IDENTIFIER
AVERAGE STANDBY CURRENT
MAX. SURGE CURRENT
MAX. ALARM CURRENT
VOLTAGE WAVEFORM
RATED VOLTAGE (4-WIRE)
WORKING VOLTAGE (2-WIRE)
DETECTORS
NOTE:
HD3
N/A
IONIZATION
200 A
5V RIPPLE MAX.
FILTERED DC
40 A
150 mA
17.7-30.0 VDC
15-33.0 VDC
SPECIFICATIONS
BUENA PARK, CA 90621-2268
7051 VILLAGE DRIVE SUITE 100
HOCHIKI AMERICA CORPORATION
CAUTION
INSTALLATION INSTRUCTIONS
BUILT-IN
TEST FEATURE
SLR-835/-835W/
PHOTOELECTRIC
8.0~35.0 VDC
8.0~35.0 VDC
*FILTERED DC
15% RIPPLE MAX.
150 mA
200 A
55 A @ 24VDC
38 A @ 12 VDC 70 A @ 35VDC
HD5
30/ZONE 30/ZONE
135/190°F
DCD-135/-135W/-135C
OF RISE HEAT
FIXED TEMP/RATE-
35 A
HD3
160 A
*
5V RIPPLE MAX.
FILTERED DC
TTA-1H
150 mA
17.7-30.0VDC
15.0-33.0VDC
DWG. # HA-06-060
*
CAUTION
BOX MOUNTING
NO
YES NO
3" OCT
YES
YES
NO
4" OCT
YES
NO YES
4" SQR
FIG. 1
(Pg.1 of 2, 06/16)
PART# 1700-09987
*
DETECTOR MODEL
DFE-190/-190W/DFE-190C
NON-CURRENT
NON-CURRENT
(57mA MAX)
37~45 mA @ 24V
(88.5mA @ 26.5VDC MAX)
(54 mA MAX.)
ALARM CURRENT
67~80 mA @ 24V
35~42 mA @ 24V
NOTE: BASES/DETECTORS WITH THE "W" SUFFIX ARE WHITE IN COLOR.
HSC-221L/-221LW
NS6-100,100W
NS4-100,100W
BASE MODEL
HSC-220L/-220LW
HSC-224L/-224LW
TEMPERATURE RATING MAX. ALARM CURRENT
DETECTOR TYPE
Pig Tail Lead
NS6-100
LISTED DEVICE
END OF LINE
190°F. 100 mA
FIXED TEMPERATURE
HB-63
FIXED TEMPERATURE
100 mA
135°F.
COMPATIBILITY
IDENTIFIER
HB-64
HB-62
LATCHING
INDICATION
YES
DFE HEAT DETECTORS
BASE STYLES
SPECIFICATIONS
NS6 SERIES
S1
HEAT DETECTOR DATA
(4 INCH BASE)
NS4 SERIES
HSC SERIES
S2
L2
L1
H1
H2
YES
YES
LIMITED
N/A
NO
LIMITED
N/A
NO
COMPATIBLE
CONTROL
PANEL
UL LISTED
SUPPLY
NEGATIVE
PANEL
POWER
HSC-220L
6
SIJ-24/-24C SLR-24/-24C/-24V/-24VC
OF CONNECTIONS.
-24VN/-24H/-24HC
-190/-190W/-190C -835C
55 A @ 24VDC
70 A @ 35VDC
38 A @ 12 VDC
200 A
150 mA
15% RIPPLE MAX.
FILTERED DC *
8.0~35.0 VDC
8.0~35.0 VDC
PHOTOELECTRIC
SLR-835H/-835HW
HD5
BUILT-IN
TEST FEATURE
30/ZONE
135°F
N/A
DFE-135/-135W/DFE-135C
15°F./MIN.
TEMPERATURE RATING MAX. ALARM CURRENT 100 mA
SPECIFICATIONS
DETECTOR TYPE
DETECTOR MODEL
HEAT DETECTOR DATA
DSC-EA HEAT DETECTORS
RATE OF RISE
DSC-EA/DSC-EAW
UL LISTED TEMPERATURE
6
L4
L3
56
3
4
1
2
S1
S2
H2 H1
L2
L1
L3L4
L2
L1
L3
L4
(EXCEPT NS6-100)
NS6-100
(EXCEPT NS4-100)
NS4-100
(4 INCH BASE)
1
2
6
5
3
4
6
NS6 SERIES
(EXCEPT NS6-100)
For testing and cleaning information, refer to Page 2 of these instructions and to Technical Bulletin HA-97 Conventional. Also refer to NFPA-72 Chapters 2 and 7 for Automatic Fire Detector installation guidelines, testing, and maintenance.
Use "3M" Weatherban # 606 non-flammable sealing compound to seal field wiring conduit openings in the mounting back box. Compliance with this request may reduce the occurrence of the "STACK EFFECT".
These instructions apply to all Hochiki America detector bases that utilize an NS detector with LEDs to indicate power, and alarm.
Install the bases in this instruction in accordance with applicable NFPA standards, local codes, and the authorities having jurisdiction. Failure to follow these instructions may result in failure of the detector to initiate an alarm condition. Hochiki America is not responsible for detectors that have been improperly installed, tested, or maintained.
* When using a four-wire
base full wave rectified
AC can be used.
When mounting detector on a wall, it must be between 4" and 12" from the ceiling.
PHOTOELECTRIC
SLV-24V/-24N
BUILT-IN
TEST FEATURE
30/ZONE
17.7-30.0 VDC
HD3
5V RIPPLE MAX.
FILTERED DC
45 A
150 mA
15-33.0 VDC
*
N/A
160 A
-24NW/SLV-24
Note: The SLR-24V, SLV-24V and SOC-24V are suitable for installation in air velocities up to 4000ft./min.
0°C ~ 37.8°C
(32°F ~ 100°F)
OPERATING TEMPERATURE
(14°F ~ 122°F)
-10°C ~ 50°C
NOTE: BASES/DETECTORS WITH THE "C" SUFFIX ARE CANADIAN.
PHOTOELECTRIC
SOC-24V/-24VN
30/ZONE
HD3
FILTERED DC
59 A
150 mA
*
N/A
160 A
8.0~35.0 VDC
8.0~35.0 VDC
15% RIPPLE MAX.
SOC-24VW
5
6
5
1 2
1 2
BUILT-IN
TEST FEATURE
the factory for servicing. Refer to Technical Bulletin HA-97 for cleaning information.
4) When the condition exists as stated in 2) the device needs to be cleaned or returned to
3) In the alarm state both LEDs are on Red continuously.
2) When the sensitivity drifts outside of its sensitivity limits, both LEDs flash Red
SLR -24/-835/SLV-24 AND SOC-24V SERIES SENSITIVITY TEST FEATURE
1) In normal condition both LEDs flash Green.
For go/no-go testing, a magnet will be required.
1. Hold the magnet just UNDER the word "TEST" as shown on Diagram A.
2. The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm Verification, it may take up to 30 seconds).
3. The detector's LEDs should be on Red continuously and any control panel indicating appliances should activate.
4. Silence the system and activate the control panel reset to reset smoke detector.
5. The smoke detector LEDs should flash Green.
TESTING THE SLR-835/SLR-24 AND THE SLV-24 SERIES INSTALLATION
FIG. 1
DWG. # HA-06-060
(Pg.2 of 2, 06/16)
DIAGRAM A
FIG. 2
Hold Magnet Here
TEST
Testing is performed with the Hochiki America Alarm Test Magnet
SIJ-24/-24C SENSITIVITY TEST PROCEDURE
POWER CONDITIONS MAY AFFECT SENSITIVITY. ALWAYS RESET POWER PRIOR TO
within specified sensitivity limits and may require service. See Tech Bulletin
3). Place magnet on detector as shown in Figure 2 (opposite side).
source and with normal applied power, place magnet as shown in Figure 1.
1). With detector wired to appropriate initiating circuit or current limited power
CONDUCT TESTING ONLY UNDER NORMAL STANDBY CONDITIONS. ABNORMAL OR LOW
produce an alarm when magnet is positioned as in Figure 2, detector is not
5). If detector does alarm when magnet is positioned as in Figure 1 or does not
2). Wait at least six seconds. Detector SHOULD not alarm and LED should not light.
TESTING OF NEXT UNIT.
4). Wait at least six seconds. Detector SHOULD alarm.
HA-97 for more information and for additional sensitivity test devices.
NOTE:
SIJ-24/-24C DETECTOR
TOP VIEW OF
(Part Number 0700-01110) shown below.
TEST DEVICE:
TEST PROCEDURE
TOP VIEW
SIDE VIEW
NS6-100
DEVICE
END OF LINE
LISTED
EXCEPT NS6-100
(EXCEPT NS4-100)
N/A47mA (75mA @ 18.0V MAX.)
HSC-4R12
LISTED DEVICE
END OF LINE
2
1
2-WIRE AUXILIARY RELAY BASE 4-WIRE 24V BASE
* - Requires External Current
Limiting To 150mA Max.
2
1
1
ID
HB-5
ALARM CURRENT
43mA (70mA @ 33.0V MAX.)
HB-4 HB-55
HB-4
HB-5 HB-3
HB-55 HB-73
HB-71 N/A
HB-72
1
49mA (62mA @ 30.0V MAX.)
46mA (77mA @ 33.0V MAX.) 150mA @ 15.0~33.0V MAX.
88mA (98mA @ 26.5V MAX.)
43mA (58mA @ 30.0V MAX.)
150mA @ 15.0~33.0V MAX.
46mA (77mA @ 33.0V MAX.)
93mA (136mA @ 33.0V MAX.)
43mA (70mA @ 33.0V MAX.)
43mA (58mA @ 30.0V MAX.)
93mA (136mA @ 33.0V MAX.)
HB-3
AND NS6 ARE IDENTICAL
- BASES WITH THE "W" SUFFIX ARE WHITE IN COLOR
NS6 SERIES
NOTE: - WIRING TERMINALS FOR THE NS4
BASE
NS6-224, 224W, 224C
HSC-221R/221RW/221RC
HSC-4R/-4RC
HSC-220R/220RW/220RC
NS6-221, 221W, 221C
*NS6-100, 100W, 100C
HSC-224R/224RW/224RC/RA/RST
*NS4-100, 100W, 100C
NS4-221, 221W, 221C
NS4-220, 220W, 220C
NS4-224, 224W, 224C
NS6-220, 220W, 220C
Resistor shown is for example only. Not all annunciators have in line resistance.
NS4 SERIES
UL LISTED
CONTROL
PANEL
PANEL POWER SUPPLY
NEGATIVE
UL LISTED
2-WIRE OPERATION
2-WIRE RELAY OPERATION
Annunciation device must be current limited to 20 mA @ 24VDC Maximum. Not limiting current could result in damage to the detector or cause a no alarm condition.
6 5
COM
N/C
4 3
N/O
N/O
HSC-(XXX)R (2-WIRE)
BLU GRN
GRY
YEL
PUR
ORN
HSC-224RA/RST VERSION ONLY
TERMINAL BLOCK USED ON
LISTED DEVICE
H1
ORN
YEL
H2
2 1
N/C
COM
END OF LINE
2 AND 4 WIRE BASE RELAYS SHOWN WITH
HSC-4R
POWER OFF.
CONTACTS
HSC-RELAY SERIES
LISTED RELAY
END OF LINE HA-EOLR-12 OR HA-EOLR-24
HSC-4R
PUR
CONTROL
PANEL
INITIATING
CIRCUIT
HSC-4R
UL LISTED
POWER SUPPLY
12VDC OR 24VDC
4-WIRE OPERATION
NOTE: The SLR-24/-24C/-24V/-24VC/-24VN/-24H/-24HC/-835/-835W/-835C/-835H/-835HW, SLV-24/-24V/-24N/-24NW and SOC-24V/-24VN/-24VW have a built-in automatic sensitivity test feature.
LED
LED
LED
Test tool (back side)
Test tool
SOC-24V/-24VN
Magnet
LED marking
DIAGRAM B
For go/no-go testing, original test tool will be required.
1. Hold the test tool on the detector like Diagram B.
2. The detector should alarm within 10 seconds (If control panel is programmed for Fire Alarm Verification, it may take up to 30 seconds).
3. The detector's LED should be on Red continuously and control panel indicating appliances should activate.
4. Silence the system and activate the control panel reset to reset smoke detector.
5. The smoke detector LED should flash Green.
TESTING THE SOC-24V/-24VN/-24VW
NOTE: In case of SOC-24V/-24VN/-24VW, only 1 LED
1
2
3
6
4
5
1
2
3
6
4
5
1
2
3
6
4
5
S1
S2
L2
L1
H1
H2
L4
L3
S1
S2
L2
L1
H1
H2
L4
L3
S1
S2
L2
L1
H1
H2
L4
L3
S1
S2
L2
L1
H1
H2
L4
L3
Loading...