Hochiki SDP-3 Installation Instructions Manual

Hochiki Europe (UK) Limited Page 1 of 5 2-3-0-456/ISS6/JAN16
Hochiki SDP-3 Duct Probe
Installation Instructions
Hochiki's Duct Probe housing allows a standard photoelectric smoke detection device, either a conventional detector or an analogue sensor, to be mounted on the outside of an air duct for the purpose of monitoring the air within the duct. Air within the duct is drawn via a pipe into the duct probe's housing. This allows constant sampling with a standard, LPCB approved smoke detector and makes smoke detection within the duct simple, effective and easy to maintain.
Compatible Hochiki devices that can be used within the SDP-3 are:
ESP
Analogue Sensors
ACA (inc all variants), ACC (inc all variants) ALG (inc all variants), ALN (inc all variants) ALK (inc all variants)
CDX
Conventional Detectors
SLR (inc all variants) SLV (inc all variants)
Compatible Hochiki Bases that can be used within the SDP-3 are:
ESP
Analogue
YBN-R/3, YBN-R/3(SCI), YBO-R/SCI
CDX
Conventional
YBN-R/6, YBN-R/6SK, YBO-R/6R, YBO-R/6RN, YBO-R/6RS.
Mounting Position
The SDP-3 should be installed with the arrow on the cover corresponding to the direction of airflow in the duct.
The SDP-3 can be placed horizontally or vertically, on the top, side or bottom of the duct. Hochiki recommends that the unit is mounted away from heating, cooling or humidity devices following the same guidelines for flow monitors.
The SDP-3 smoke detector must be installed pointing towards the air flow direction.
A distance of 3 times the duct diameter should be left before a damper, filter or change of the duct direction, and 5 times the diameter after these devices.
NOTE: The word “diameter” has been used throughout. In the case of square-section ducts this should be read to mean width.
Hydraulic Diameters
Example of installations at sources of interference
Fan Damper Silencer Battery Air handling unit Duct Bend Duct Branching
Duct Narrowing
or Expansion
www.acornfiresecurity.com
www.acornfiresecurity.com
Hochiki Europe (UK) Limited Page 2 of 5 2-3-0-456/ISS6/JAN16
Installation Procedure
STEP 1 - Selecting Pipe Length
The supplied 600mm sampling pipe can only be used with ducts up to a maximum diameter of 600mm, but the pipe can be shortened if required (see STEP 2).
For ducts with a diameter greater than 600mm use the 1200mm sampling pipe cut to size but penetrating the whole width of the duct (see “Large Diameter Ducts” on Page 2).
For ducts with a diameter greater than 1200mm contact Hochiki Europe Customer Support for advice (psupport@hochikieurope.com).
STEP 2 - Adjusting Pipe Length
After measuring the diameter of the duct and deducing the length of pipe required, shorten the pipe if necessary.
The pipe should penetrate a minimum of 90% of the width of the duct.
Do not cut the end of the pipe with warning label.
Only cut between sampling holes.
Once cut to length, insert the end plug.
Large Diameter Ducts
• When using a sampling pipe within a duct
greater than 600mm diameter the pipe should penetrate the whole duct.
• Shorten the pipe to correct length if required
• Insert the end plug
• Fit the end plastic gasket
• Fit the sealing sleeve
STEP 3 – Insert Pipe into SDP-3
• Insert the pipe into the bottom of the SDP-3.
Secure the pipe with the locking
(7) Locking screw
(6)
www.acornfiresecurity.com
www.acornfiresecurity.com
Loading...
+ 3 hidden pages