INSTALLATION INSTRUCTIONS FOR DCP-CZM CONVENTIONAL ZONE MODULE
The (DCP-CZM) Conventional Zone module is mounted as
WIRING
NOTE: All wiring must conform to local codes,
ordinances and regulations.
1) Install module wiring in accordance with the job drawings and appropriate wiring diagram (see Fig.3).
2) Secure the module to a U.L. listed electrical box (supplied by installer), as shown in Figure 2.
shown in Figure 2 on page 1 of this instruction.
HOCHIKI AMERICA CORPORATION 7051 VILLAGE DRIVE, SUITE 100 BUENA PARK, CA 90621-2268
PROGRAMMING PLUG AND CONNECTOR
EXPLODED VIEW OF ADDRESS
FIGURE 1.
NON-POLARIZED
PLUG IS
TO PROGRAMMER
NOTE: Please reference the 2 wire detector compatibility matrix on
the proceding page for a complete list of devices approved for use
with the "DCP-CZM"
The information contained in this installation instruction is to be used as quick reference guide. For detailed system
information, refer to the panel's installation manual.
CAUTION !
Install the modules in this instruction in accordance with applicable NFPA standards, local codes, and the authorities having jurisdiction. Failure to follow these instructions may result in failure of the system to operate as intended. Hochiki America is not responsible for modules that have been improperly installed, tested, or maintained.
To ensure proper operation connect this module to a compatible Fire Control Panel only. Refer to panel instructions for proper connection and compatibility.
If this module will be installed in an existing operation system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the module
An average of 6.75mA (communication current)
per loop of SLC devices, must be factored into the panel battery backup calculations.
PART# 1700-10170
(PG 1 OF 2, 05/17)
HA-06-101
DWG. #
μ
This instruction applies to the Conventional Zone Module (DCP-CZM), which is to be connected to a Signal Line Circuit (SLC). The module allows the analog panel to interface and monitor dry contacts such as pull stations and two-wire conventional smoke detectors. The "DCP-CZM" is addressed through the communication line of the system and transmits the status of one zone of devices to the panel. Status conditions are reported as normal, open or alarm. It supervises the external power supply as well as the entire zone of devices.
NOTE:
NOTE:
Maximum Ripple Voltage 2VDC P-P
Page 2
FIGURE 3.
NFPA STYLE B WIRING DIAGRAM
TB1
TB2
EB
DCP-CZM
24V-
24V+
SC
S
OUT-
IN+
OUT+
IN-
JP2
TB2
FIGURE 3.
S
SC
24V+
24V-
EB
IN-
OUT+
IN+
OUT-
SER. NO. 210300001
DCP-CZM
SC
24- 24V+
S
TB1
JP2
DETECTORS
MAX. 25 CONVENTIONAL
DETECTORS
MAX. 25 CONVENTIONAL
PART# 1700-10170
(PG 2 OF 2, 05/17)
HA-06-101
DWG. #
CLASS A
CLASS B
1-2: CLASS B
HA's Sales department for proper procedure for claims and return of merchandise. This warranty is in lieu of all other warranties
specifications in any way. HA will not be responsible for any dismantling, reassembling or re-installation charges. Please contact
abused, improperly installed, altered or otherwise misused or damaged or exposed to conditions outside the products
delivery. All warranties are void and HA is not obligated to repair or replace equipment which has been repaired by others,
and to be free from defects in materials and workmanship under normal use and service for a period of one (1) year from date of
Hochiki America (HA) warrants its digital communication modules to be in conformance with it's own plans and specifications
expressed or implied.
One Year Limited Warranty
EXPLODED VIEW
EXPLODED VIEW
NOTE: ENSURE JUMPER IS IN CORRECT POSITION FOR WIRING CONFIGURATION. (POSITION 3-4)
FOR WIRING CONFIGURATION. (POSITION 1-2)
NOTE: ENSURE JUMPER IS IN CORRECT POSITION
3-4: CLASS A
NEXT DEVICE
NEXT DEVICE
24- 24V+
+
SC
S
-
SCS
U.L. LISTED
COMPATIBLE
FIRE CONTROL
PANEL
S
COMPATIBLE
FIRE CONTROL
PANEL
SC
U.L. LISTED
NFPA STYLE D WIRING DIAGRAM
OPTIONAL BRANCH CIRCUIT TO NEXT INTERFACE MODULE. MODULE SUPERVISES SUPPLY VOLTAGE AND DETECTOR LOOP.
OPTIONAL BRANCH CIRCUIT TO NEXT INTERFACE MODULE. MODULE SUPERVISES SUPPLY
VOLTAGE AND DETECTOR LOOP.
ALL WIRING IS SUPERVISED AND POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME MODULE.
TB1/TB2 ARE SUPERVISED AND POWER LIMITED.
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, SECURITY DEVICES OR LINE TYPE HEAT CABLES ON THE SAME MODULE.
-
+
0400-03190
PART NUMBER
E.O.L. DEVICE 4.7K
HOCHIKI AMERICA CORP.
E.O.L. DEVICE 4.7K
0400-03190
PART NUMBER
INSTALL ONLY DETECTORS LISTED AS UL COMPATIBLE WITH THE CONVENTIONAL ZONE MODULE (CZM) AS REFERENCED IN THE CHART BELOW.
Hochiki America Corporation
Hochiki America Corporation
MODULE
CONVENTIONAL ZONE
NOTE: Only the same size wire
from 12 to 22 AWG may be connected terminal block TB1 when more than one conductor is being connected under each terminal. Maximum of 2 conductor per terminal.
Detector Model
SLR-835BH-2/-2W
DCD-135/-190
Detector
Identifier
Detector Type
HD-6
HD-3
Heat Fixed Temp/Rate of Rise
Base
w/thermal (baseless)
Photoelectric (8-35V)
Base Model
Detectors
Max
N/A
HB-5
N/A
25
25
SLR-835B-2/-2W
HD-6
Photoelectric (8-35V) (baseless)
N/A
N/A
25
NS4-224, NS6-224
HD-3SLR-24H Photoelectric w/heat
NS4/NS6-220/-224
HB-3/HB-5 25
SLR-24V Photoelectric SLR-835/-835W HD-3
Photoelectric (8-35V)
NS4/NS6-220/-220W/-224/-224W
25
Indetifier
SLR-835H/-835HW
HD-5
Photoelectric (8-35V)
w/thermal
NS4/NS6-224/-224W/-220/-220W
25
SLV-24/-24N/-24V HD-3
Photoelectric
NS4-224, NS6-224
HB-5
25
NS4-224W, NS6-224W
UL LISTED 1481 24VDC REGULATED POWER SUPPLY,
LISTED FOR FIRE
PROTECTION
WITH BATTERY BACKUP.
UL LISTED 1481 24VDC REGULATED POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.
DCD-135/-190
HD-3
Heat Fixed Temp/Rate of Rise
HB-3 25
NS4-220, NS6-220
SLV-24/-24N/-24V HD-3
Photoelectric
NS4-220, NS6-220
HB-3
25
NS4-220W, NS6-220W
For Dry Indoor Use Only
For Proper Mounting/Installation See
HA-06-101 05/17
Compatibility Identifier: A
POWER LIMITED
SER. NO. 210300001
For Dry Indoor Use Only
For Proper Mounting/Installation See
HA-06-101 05/17
Compatibility Identifier: A
POWER LIMITED
MODULE
CONVENTIONAL ZONE
Compatible Linear Heat Detection Cable for use with the CZM:
Proline Protection Systems TH 105
Proline Protection Systems TH 68 Fixed Temp. line type heat detector cable 155 F (68 C) 8,000ft. (2,438m)
Proline Protection Systems TH 88
Manufacturer Model Description Maximum Lenght
Fixed Temp. line type heat detector cable 190 F (88 C)
Fixed Temp. line type heat detector cable 221 F (105 C)
8,000ft. (2,438m)
8,000ft. (2,438m)
INSTALLATION WIRING SHALL NOT EXCEED 50 OHMS (12-22 AWG) WHEN USING CONVENTIONAL DETECTORS
Compatible Two Wire Detectors for use with the CZM with zone identifier A:
SEE UL CERTIFICATE FOR COMPLETE LIST
HD-3
Photoelectric (8-35V)
25
SOC-24V/-24VN /-24VW
NS4/NS6-100,NS4/NS6-220/-221/-224, HSC-220R/-224R
HD-3
NS4/NS6-220/-224
HB-3/HB-5 25 HB-3/HB-5
HB-3/HB-5
HB-55/HB-3/HB-4 /HB-5/HB-72/HB-73
Loading...