Hochiki CHQ-WSB2/WL, CHQ-WSB2/RL, CHQ-WS2 Installation Instructions Manual

Page 1
2-3-0-1752/ISS1/JUNE14
HOCHIKI WALL SOUNDER & WALL SOUNDER BEACON INSTALLATION INSTRUCTIONS
Introduction
The CHQ-WS2 is a loop-powered addressable wall sounder. The CHQ-WSB2 is a loop-powered addressable wall sounder beacon. Both units are compatible with the standard red mounting base (YBO-R/3(RED)) and the red isolator base (YBO-R/SCI(RED)); the units have connections for both these types of base. Do not attempt to use any other base type with these units. Both sounders and bases are also available in WHITE (YBN-R/3(WHT) (see above).
Both the CHQ-WS2 and CHQ-WSB2 are Ingress Protection rated to IP21 for internal use, but can be made weatherproof when used in conjunction with the WS2-WPK Weather Proofing Kit, in which case they are Ingress Protection rated to IP65*1 but only when used in accordance with the WS2-WPK instructions (2-3-0-627).
Address Setting (with Hand Held Programmer)
The units will need to be manually addressed between 1 and 127. The sounder address can be set using the Hand Held programmer (TCH-B100) as the units both include the appropriate terminals to fit directly onto the Programmer. See the TCH-B100 instructions for further details of address setting. The address must be set before installation.
Tones and Volumes
Table 1 below shows the full range of sound outputs available from the CHQ-WS2 and CHQ-WSB2 together with the amount of current drawn when operated. The units are also capable of utilising a number of different EN54-3 Approved tones; these are listed in Table 2, page 3. The tone of the sounder and the volume level is selected
and controlled by the control panel, therefore check with the control panel manufacturer for options and default values available. The sounder and beacon elements of the CHQ-WSB2 can be controlled independently, check with the control panel manufacturer for compatibility.
Table 1
CHQ-WS2
(sounder activated)
CHQ-WSB2
(sounder & beacon activated)
Nominal Sound Output dB(A)*
2
Current Drawn mA
90
2.0
9.0
95
3.0
10.0
98
4.5
11.5
100
6.5
13.5
102
8.0
15.0
Supply Voltage Range 17-41 Vdc. Max. Power Consumption 287 mW @ 41 Vdc (beacon only)
*2 Refer to Application Notes AP084 and AP117 (available from our website) for complete EN54-3 A-weighted sound levels.
@ 1m distance.
Precautions
Ensure that the unit is installed in accordance with Local Standards or Regulations. Only use the specified Hochiki mounting bases (or WS2-WPK Weather Proofing Kit) with this wall sounder/wall
sounder beacon.
Only install in suitable environments, the following in particular should be avoided: -
Excessive ambient temperature.  Where excessive condensation or moisture is present (unless WS2-WPK is utilised).  Hazardous areas.
A high voltage tester must not be used with these units or either of the specified bases. Ensure that the unit is securely fixed to the mounting base (and WS2-WPK if utilised). For proper wiring supervision ensure that the cables are wired as shown in Fig 4.
Locking Mechanism
The units can be locked onto the relevant mounting base by removing a plastic lug on the underside of the sounder, refer to Fig. 1.
www.acornfiresecurity.com
www.acornfiresecurity.com
Page 2
2-3-0-1752/ISS1/JUNE14
*1 This product has only been approved to IP33 by LPCB
The unit can then only be removed from the base by using a special removal tool, TSE-SRT, which is available from Hochiki Europe (UK) Ltd.
Installation
Both the CHQ-WS2 wall sounder and the CHQ-WSB2 Wall Sounder Beacon are designed to be mounted directly onto the Red Standard Mounting Base (YBO-R/3(RED)) or the Red Short-Circuit Isolator Mounting Base (YBO-R/SCI(RED)) or YBN-R/3(WHT)-SCI in the same method as a Sensor (see Fig. 2). The terminals on the mounting base hold the units in place.
Remove tab carefully using a pair of pliers.
Fig. 1
Fix the mounting base to the required surface using appropriate fixings. For correct wiring of the each base type, refer to Fig. 4.
When installing either of these units in exterior locations use the WS2-WPK Weather Proofing Kit. The kit consists of a weatherproof back box and two gaskets, which must be used in conjunction with either mounting base to maintain the IP rating (see Fig. 3). For further information, refer to the WS2-WPK Weather Proofing Kit instructions (2-3-0-627).
Wiring
Please refer to Fig. 4 for wiring the Red Standard Mounting Base (YBO-R/3(RED)) and the Red Short-Circuit Isolator Mounting Base (YBO-R/SCI(RED)):
Fig. 2
Key: A: Loop (+) B: Loop (-) C: Cable Screen Fig. 4
Fig. 3
CHQ-WS2
0832-CPD-0455
09
EN54-3 Alarm Devices – Sounder EN54-23
CHQ-WS2(WHT)
CHQ-WS2(HFP)
CHQ-WSB2/WL
0832-CPR-F02562/14
14
EN54-3 Alarm Devices – Sounder EN54-23
Fire Alarm Devices – Visual Alarm Device (VAD)
CHQ-WSB2(WHT)/WL
CHQ-WSB2/WL-HFP
CHQ-WSB2(WHT)/WL-HFP
CHQ-WSB2/RL
0832-CPR-F0563/14
14
EN54-3 Alarm Devices – Sounder, EN54-23
Fire Alarm Devices – Visual Alarm Device (VAD)
CHQ-WSB2(WHT)/RL
CHQ-WSB2/RL-HFP
CHQ-WSB2(WHT)/RL-HFP
‘For information on essential characteristics please refer to the relevant Declaration of Performance available at www.hochikieurope.com’
CHQ-WS2 / CHQ-WSB2
CHQ-WS2 / CHQ-WSB2
YBO-R/3, YBO-R/SCI &
YBN-R/3(WHT)-SCI
(Refer to separate instructions no.
2-3-0-1499 for YBN-R/3(WHT)-SCI
wiring)
www.acornfiresecurity.com
www.acornfiresecurity.com
Page 3
2-3-0-1752/ISS1/JUNE14
CHQ-WS2 Operating Voltage 17 ~ 41 Vd.c.
Table 2
Tone Number
Tone Description
Graphic Representation
Tone Number
Tone Description
Graphic Representation
0
Sounder Off
19
800 Hz : 250 ms 970 Hz : 250 ms
1
925 Hz : 250 ms 628 Hz : 250 ms
20
2850 Hz Continuous
2
925 Hz Continuous
21
2400 Hz : 250 ms 2850 Hz : 250 ms
3
628 Hz Continuous
22
800 Hz : 500 ms 970 Hz : 500 ms
4
(French) 554 Hz : 100 ms 440 Hz : 400 ms
23
2850 Hz : 500 ms Off : 500 ms
5
(Swedish) 660 Hz : 150 ms Off : 150 ms
24
925 Hz : 250 ms Off : 1000 ms
6
925 Hz : 150 ms Off : 600 ms
25
970 Hz Continuous
7
670 Hz : 250 ms 845 Hz : 370 ms
26
660 Hz : 1800 ms Off: 1800 ms
8
Whoop 500 Hz - 1200 Hz 3000 ms Off : 500 ms
27
660 Hz : 6500 ms Off : 13000 ms
9
1200 Hz : 500 ms 500 Hz : 500 ms
28
660 Hz Continuous
10
970 Hz : 500 ms Off : 500 ms
29
554 Hz : 500 ms 440 Hz : 500 ms
11
Sweep 800 Hz - 970 Hz over 140 ms (7 Hz)
30
660 Hz : 500 ms Off : 500 ms
12
Sweep 800 Hz - 970 Hz over 1000 ms (1 Hz)
31
2850 Hz : 150 ms Off : 100 ms
13
Sweep 800 Hz - 970 Hz over 20 ms (50 Hz)
32
Sweep 2400 Hz – 2850 Hz over 20 ms (50 Hz)
14
Sweep 2400 Hz – 2850 Hz over 140 ms (7 Hz)
33
Sweep 800 Hz – 970 Hz over 500 ms (2 Hz)
15
Sweep 2400 Hz – 2850 Hz over 1000 ms (1 Hz)
34
988 Hz : 250 ms 645 Hz : 250 ms
16
Sweep 300 Hz – 1200 Hz over 1000 ms (1 Hz)
35
510 Hz : 250 ms 610 Hz : 250 ms
17
ISO8201 : 970 Hz : 500 ms
36
Sweep 800 Hz – 970 Hz over 110 ms (9 Hz)
18
ISO8201 : 2850 Hz : 500 ms
37
Sweep 800 Hz – 970 Hz over 330 ms (3 Hz)
www.acornfiresecurity.com
www.acornfiresecurity.com
Page 4
2-3-0-1752/ISS1/JUNE14
Tone Number
Tone Description
Graphic Representation
Tone Number
Tone Description
Graphic Representation
38
845 Hz Continuous
45
(German) Whoop 1200 Hz – 500 Hz : 1000ms Off : 10 ms
39
970 Hz : 1000 ms Off : 1000 ms
46
440 Hz : 600 ms Off : 600 ms
40
800 Hz : 150 ms 970 Hz : 150 ms
47
Whoop 500 Hz – 1200 Hz : 3750 ms Off : 250 ms
41
Sweep 2400 Hz – 2850 Hz over 110 ms (9 Hz)
48
ISO8201 925 Hz, 628 Hz : 250 ms Off 500 ms
42
Sweep 2400 Hz – 2850 Hz over 330 ms (3 Hz)
49
ISO8201 : Sweep 300 Hz – 1200 Hz : 500 ms Off : 500 ms
43
2850 Hz : 1000 ms Off : 1000 ms
50
ISO8201 : Sweep 1200 Hz – 300 Hz : 500 ms Off : 500 ms
44
2400 Hz : 150 ms 2850 Hz : 150 ms
51
Whoop 500-1200 3.5s/0.5s
CHQ-WSB2 Volume Compatibility
CHQ-WSB2 Beacon Light Coverage Characteristics
The CHQ-WSB2/RL and CHQ-WSB2/WL are “O” rated beacons designed in accordance with EN54-23, please refer to application note AP132 for the appropriate light output volumetric coverage diagrams for each type.
Flash frequency O Rated ~ 0.5Hz (Default), Compatibility Mode ~ 1Hz
YBO-BSB2 Setting
Corresponding CHQ-WSB2 Level
Sound Level dB(A)
Current mA
Sound Level dB(A)
Current mA*
Off
Quiescent
Off
Quiescent
50
0.8 → 90
2.0
55
0.8 → 90
2.0
60
0.8 → 90
2.0
70
0.8 → 90
2.0
78
1.5 → 90
2.0
80
2.0 → 90
2.0
85
3.0 → 95
3.0
88
4.5 → 98
4.5
90
6.5 → 100
6.5
93
8.0 → 102
8.0
94
10 → 102
8.0
95
11 → 102
8.0
98
16 → 102
8.0
If a control panel has not implemented the CHQ­WSB2 then it will be recognised as a YBO­BSB2. The table to the right shows the volume level set as a YBO-BSB2 and the corresponding level that is set on the CHQ-WSB2 by any panel configuration software that recognises the CHQ-WSB2 as a YBO­BSB2.
For example, if 55dB(A) is selected on the panel for a YBO-BSB2, the actual volume of the CHQ-WSB2 will set to 90dB(A).
* Note that this is sounder current only. If the Beacon is operating please add 7mA to
www.acornfiresecurity.com
www.acornfiresecurity.com
Loading...