PLANT CONTROL MODULE
INSTALLATION INSTRUCTIONS
Products covered: CHQ-PCM(SCI), CHQ-PCM/DIN(SCI)
The CHQ-PCM(SCI) is a loop powered output module with four independent change-over relay outputs, with N/O and N/C
volt free contacts. These outputs can be driven separately under the control of the fire alarm panel and can be used for
the control of devices such as dampers or for plant and equipment shutdown. Four inputs are provided for local fire and
fault monitoring and these are fully monitored for open and short circuit, which if required, can be enabled or disabled in
pairs using a two-way DIL switch. Note:- The state of the relay contacts will be indeterminate until the unit is
powered.
Components
Standard "Smart-Fix" Modules are supplied as two individual components (see Fig 1 & 2). DIN versions are supplied as
one unit (see Fig 3).
Fig 1
"Smart-Fix" CHQ Module (Back Plate inc PCB Component)
(Note: configuration of Wiring Terminal blocks differs between
models)
Setting the Loop Address
The analogue address of the Module is set using the first 7
switches of the 8-bit DIL switch, which in the case of the
Standard CHQ is located through the cut-out section on the
top of the PCB cover. On the DIN version, this switch is
located on the edge of the PCB behind the clear door (see
Fig 3).
The switches are numbered 1 to 8 (left to right):
CHQ
MODULE
DIN
MODULE
The switches should be set using a small-tipped
screwdriver or similar.
Refer to the Address Chart (Fig 5) on page 3 for a quick
reference on addresses.
Switch 8 is not used and must be switched to “OFF”.
SWITCH UP ON
SWITCH DOWN OFF
SWITCH UP OFF
SWITCH DOWN ON
Fig 2
CHQ-LID Transparent Module Lid
(Supplied with four screws and acrylic retaining washers)
Fig 3
DIN Rail Mountable CHQ Module
2-3-0-1156/ISS2/OCT11

Connection Details
The module has been designed for easy installation
and contains two connector blocks for termination of
the field wiring; refer to Fig. 4 (right) for correct
connection details.
A – EOL Monitoring Resistor, 10 KΩ
B – Operational Resistor, 470 Ω
(volt-free contact)
Setting the Fault Monitoring
The general purpose inputs on the
CHQ-PCM(SCI) are fully monitored for open and
short circuit, however, if the monitoring facility is not
required then they can be disabled by the two-way
DIL switch, refer to the table below:
CHQ MODULE
DIN MODULE
SWITCH 1 DOWN INPUTS 1 & 2 MONITORED
SWITCH 1 UP INPUTS 1 & 2 NOT MONITORED
SWITCH 2 DOWN INPUTS 3 & 4 MONITORED
SWITCH 2 UP INPUTS 3 & 4 NOT MONITORED
SWITCH 1 DOWN INPUTS 1 & 2 NOT MONITORED
SWITCH 1 UP INPUTS 1 & 2 MONITORED
SWITCH 2 DOWN INPUTS 3 & 4 NOT MONITORED
SWITCH 2 UP INPUTS 3 & 4 MONITORED
Fig 4
In Non-Monitored mode*,
the unit ignores open or
short-circuit condition –
but still requires 470 Ω to
activate.
2-3-0-1156/ISS2/OCT11

Specification
Order codes
CHQ-PCM(SCI) (module)
CHQ-PCM/DIN(SCI) (DIN module)
Transmission method Digital communication using ESP
Operating voltage 17 - 41 Vdc
Loop
Quiescent current
Current consumption whilst polling
300
22 mA
A
20 %
Relay contact rating 30 Vdc max, 1 A (resistive load)
Input E.O.L resistor
Input threshold level
Isolator
Weight (g)
Dimensions (mm)
Colour and enclosure material
Fire alarm control panel compatibility is required for both variants of this product. See AP0127 for short-circuit isolator specifications.
Switch current (switch closed) 1 A
Leakage current (switch open) 3 mA (max)
CHQ Module
DIN Module 150 L119 x W108 x H24 (CHQ DIN Module)
10 k
ON=470
5%, 0.25 W
, Short cct <50 , Open cct >100 K
332 L157 x W127 x H35 (CHQ Module with lid),
567 H79 (CHQ Module with lid and CHQ-BACKBOX)
CHQ Module & CHQ-BACKBOX white ABS, DIN Module green ABS
Note:- All EOL and operational resistors are supplied with the unit – DO NOT DISCARD!
Installation – "Smart-Fix" Version
Set analogue address before installation (see page 1).
The fixing surface should be dry and stable.
Hold the back plate up against the fixing surface and
mark the position of the four corner fixing holes.
Determine which cut-out sections along the top and
bottom edges of the module require removing to
accommodate the cables being used.
Remove cut-outs by scoring with a sharp knife before
breaking off with pliers or snips.
Mount the back plate using appropriate fixings (not
supplied) for the fixing surface.
Terminate and connect field wiring as per the wiring
diagrams on pages 2 & 3 (and the terminal block
indications on the product label).
The transparent lid (CHQ-LID) is supplied with four screws
and eight retaining washers.
Push the screws through one of the retaining washers
and then through the holes in the lid from front to
back, pushing another retaining washer onto the end
inside the lid.
Screw the lid onto the back plate; do not over tighten
the screws as this could damage the unit.
NOTE: A white plastic version of the lid is available (sold
separately – CHQ-LID(WHT)).
Fig 5
Installation with Back Box
For installations requiring glanded cables, a module back box (CHQ-BACKBOX) is available (sold separately). This is
mounted on the fixing surface; the CHQ Module is then fitted to the top of the back box and the CHQ-LID is added creating
a sealed enclosure. For further details refer to the CHQ-BACKBOX Instructions (2-3-0-800). For CHQ-PCM installations
utilising heavy-duty cabling (for example, 1.5mm
plate and CHQ-ADAPTOR is recommended.
any glands used (not supplied) conform to IP67, if such ingress protection is required.
2
solid conductor) the use of the SMB-1 Box with the SMB-ADAPTOR
For further details refer to the SMB-ADAPTOR Instructions (2-3-0-1502).
Ensure
2-3-0-1156/ISS2/OCT11

Installation – DIN Version
Set analogue address before installation (see above) and write loop address in space provided on door label.
DIN modules should be mounted in an SMB-2 or SMB-3 enclosure in conjunction with an NS 35 mounting rail with
the loop connections at the bottom of the unit. Use glands that conform to IP65 if such ingress protection is required.
Terminate and connect field wiring as per the wiring diagram on page 2 (and the terminal block indications on the
product label).
Suitable anti-static precautions must be taken when handling these products.
Status LEDs
A green LED flashes each time the unit is polled by the fire alarm control panel.
An amber LED is continually illuminated when unit detects short-circuit fault.
CHQ-PCM(SCI) 0832-CPD-1679 11
EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules
Protocol
specified in
TI/006
CHQ-PCM/DIN(SCI) 0832-CPD-1680 11
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133
Facsimile: +44(0)1634 260132
Email: sales@hochikieurope.com
Web: www.hochikieurope.com
Hochiki Europe (UK) Ltd. reserves the right to alter the specification
of its products from time to time without notice. Although every
effort has been made to ensure the accuracy of the information
contained within this document it is not warranted or represented by
Hochiki Europe (UK) Ltd. to be a complete and up-to-date
description. Please check our web site for the latest version of this
document.