FlexSmart™ TRMS Module (S-FS-TRMSA & S-FS-TRMSA-D) Manual 
The S-FS-TRMSA and S-FS-TRMSA-D are easy-to-configure, True-RMS input measurement 
modules. The S-FS-TRMSA is compatible with HOBO® H22 series data loggers. The S-FS-TRMSA-D 
is compatible with HOBO H22 loggers, U30 stations, and RX3000 stations. The “-D” variant has a 
modular connector for connecting to an available smart-sensor port. Both 2-channel modules 
have an input range of 512 millivolts RMS full-scale. Thus, they are fully compatible with 
industry-standard voltage and current transformers (PT and CT) which output 333 millivolts RMS 
full-scale. 
The modules feature extremely low-power operation, resulting in long battery life for 
unattended data logging applications. 
Note: Refer to the H22 logger, U30 or RX3000 station, and HOBOware® software manuals at 
www.onsetcomp.com/support/manuals for additional information on using and configuring the 
FlexSmart TRMS module. 
FlexSmart TRMS Module 
Models:  S-FS-TRMSA 
S-FS-TRMSA-D 
Included Items: 
• Detachable screw terminal  
connector 
• Imprintable label 
Specifications 
Input Channels  Two; AC-coupled 
Field Wiring  Two-wire via screw terminals on detachable connector, 16-24 AWG 
Input Range  5 to 512 mVRMS 
Minimum Input Voltage  5mVRMS; Input voltages < 5mV will be clipped to zero (see graph 
Maximum Input Voltage 
Input Frequency  50/60 Hz 
ccuracy  ±0.3% of reading +/- 0.5% of FSR 
ADC Resolution  15 bits 
AC Waveform  <4 Crest Factor 
Power Requirements 
Transfer Function 
Measurement Averaging Option Yes 
Replacement detachable connectors: Part of spares kit (A-FS-TRMSA4P-1) 
below) 
±1V referred to AC- terminals (pins 2 and 4) 
+3.3V @ 3mA active, 6μA sleep 
T
1
[]
VRMS
The CE Marking identifies this product as complying with all relevant 
directives in the European Union (EU). 
•=
T
0
()
2
dttV
10093-H MAN-S-FS-TRMSA 
Minimum Input Voltage Graph 

  FlexSmart TRMS Module (S-FS-TRMSA & S-FS-TRMSA-D) Manual 
Module Connections 
Potential Transformers (PT) and Current Transducers (CT) are 
connected to the module via a four-pin Phoenix-style 
detachable screw terminal connector. Once the PTs and/or CTs 
are connected, the module can then be configured using 
HOBOware software with the module installed on the HOBO 
H22 or U30 series logger or using HOBOlink® with the RX3000 
station. Note: There are limitations to the number of modules 
and smart sensors you can use with an RX3000 station. If you 
are using both TRMSA-D modules and smart sensors, then you 
are limited to a maximum of three TRMSA-D and any 
combination of smart sensors to reach a total of 13 data 
channels. For example, if there are three TRMSA-D modules in 
use with the RX3000 station (each module has two channels for 
a total of six in all), then this will leave seven additional data 
channels for smart sensors. Similarly, if there are two TRMSA-D 
modules in use with RX3000 station, then this will leave nine 
additional data channels for smart sensors. Refer to the smart 
sensor manuals at www.onsetcomp.com/support/manuals for 
the number of data channels used by a specific smart sensor. If 
you are not using smart sensors with the RX3000 station, then 
you are limited to a maximum of four TRMSA-D modules. 
Exceeding these guidelines may result in erroneous readings. 
The diagram below illustrates typical connections for a PT and 
CT. For module connection instructions specific to PTs and CTs 
purchased from Onset, refer to the documentation provided 
with each PT and CT. 
Note: For three-phase monitoring, each of the three modules 
should be wired so that similar parameters are connected to 
corresponding pin numbers. For example, voltage inputs pins 1 
and 2 on each module; current inputs pins 3 and 4 on each 
module.
Measurement Averaging 
This module supports measurement averaging. When 
measurement averaging is enabled, data is sampled more 
frequently than it is logged. The multiple samples are then 
averaged together and the average value is stored as the data 
for the interval. For example, if the logging interval is set at 10 
minutes and the sampling interval is set at 1 minute, each 
recorded data point will be the average of 10 measurements. 
Measurement averaging is useful for reducing noise in the data. 