HMS Industrial Networks Anybus BACnet to Modbus Gateway Installation Guide

HALMSTAD • CHICAGO • KARLSRUHE • TOKYO • BEIJING • MILANO • MULHOUSE • COVENTRY • PUNE • COPENHAGEN
HMS Industrial Networks Mailing address: Box 4126, 300 04 Halmstad, Sweden Visiting address: Stationsgatan 37, Halmstad, Sweden
Connecting Devices
TM
E-mail: info@hms-networks.com
Installation Guide
Anybus BACnet to Modbus
Gateway
Doc. SP1820
Rev. 1.00
3

Important User Information

This document provides installation instructions and other relevant information applicable to the Anybus BACnet to Modbus Gateway.

Liability

Every care has been taken in the preparation of this document. Please inform HMS Industrial Net­works AB of any inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial Networks AB, reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be considered as a commitment by HMS Industrial Net­works AB. HMS Industrial Networks AB assumes no responsibility for any errors that may appear in this document.
There are many applications of this product. Those responsible for the use of this product must ensure that all the necessary steps have been taken to verify that the applications meet all perfor­mance and safety requirements, including any applicable laws, regulations, codes or standards.
HMS Industrial Networks AB will, under no circumstances, assume liability or responsibility for any problems that may arise as a result from the use of undocumented features, timing, or func­tional side effects found outside the documented scope of this product. The effects caused by any direct or indirect use of such aspects of the product are undefined, and may include e.g. compati­bility issues and stability issues.
The examples and illustrations in this document are included solely for illustrative purposes. Be­cause of the many variables and requirements associated with any particular implementation, HMS Industrial Networks AB cannot assume responsibility for actual use based on these examples and illustrations.

Trademark Acknowledgements

Anybus ® is a registered trademark of HMS Industrial Networks AB. All other trademarks are the property of their respective holders.
Specifications are subject to change without notice. Other product names may be trademarks or registered trademarks of their respective companies. BACnet is a registered trademark of the American Society of Heating, Refrigeration, and Air-Conditioning Engineers, Inc. (ASHRAE).

Declaration of Conformity

Information about regulatory compliance can be found at: www.anybus.com
Anybus BACnet to Modbus Gateway Install Guide
Copyright© HMS Industrial Networks AB, September 2014
Anybus BACnet to Modbus Gateway Install Guide Doc. SP1820, Rev. 1.00
Anybus BACnet to Modbus Gateway Install Guide Doc. SP1820, Rev. 1.00
Table of Contents 5

Table of Contents

Important User Information . . . . . . . . . . . . . . . . . . . . . . . 3
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shipping Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ethernet Connector Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
RS-485 Connector Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
RS-485 Bias and Termination Jumpers (J5) . . . . . . . . . . . . . . . . . . . . . . . . . 11
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Limited Power Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Hardware & Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Modbus Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
RS-485 Bias and Termination
Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Further Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Anybus BACnet to Modbus Gateway Install Guide Doc. SP1820, Rev. 1.00
6

1. Overview

Modbus is a popular network interface commonly used with boiler controllers, variable speed drives, and metering applications, although many of these devices have no BACnet compliance. The Anybus BACnet to Modbus Gate­way is used to make Modbus devices appear as individual BACnet devices.
The gateway has one 10/100 Mbps Modbus TCP or BACnet/IP Ethernet port, and one opto-isolated Modbus RS-485 serial port for Modbus RTU or Modbus ASCII devices.
Up to 30 Modbus serial devices can share the unit’s Modbus port, and up to 1000 Modbus registers can be processed. The virtual routing feature in the Anybus BACnet to Modbus gateway allows each connected Modbus device to appear as an individual BACnet-compliant device.
A device profile is required for each Modbus device type. Common device pro­files are available from www.anybus.com. Device profiles can be customized.
Using web pages and a database of common Modbus device profiles, Modbus registers from Modbus Serial devices can be mapped to BACnet objects.
The Anybus BACnet to Modbus Gateway provides:
Gateway functionality between
Modbus Serial (RTU or ASCII) and BACnet/IP
Modbus TCP and BACnet/IP
Routing functionality between:
Modbus Serial (RTU and ASCII) and Modbus TCP
Flexible communication ports:
10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX
Opto-isolated serial port supports either 2-wire or 3-wire RS-485
Baud rates at 2.4–115.2 kbps
Convenient Installation
24 VAC/VDC powered
•DIN-rail mounting
Anybus BACnet to Modbus Gateway Install Guide Doc. SP1820, Rev. 1.00