INBACDAL1280200
DALI to BACnet gateway
Order Code: INBACDAL1280200
Installation Sheet rev.1.1
HMS Industrial Networks S.L.U ©
! WARNING
Follow carefully this safety and installation instructions.
Improper work may lead to serious harmful for your health
and may also damage seriously the Intesis gateway and/or
any other equipment connected to it.
The Intesis gateway must be installed by accredited electrician or
similar technical personnel, following all the safety instructions given
here and in accordance always with the country legislation for
installation of electric equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct
solar radiation, water, high relative humidity or dust.
The Intesis gateway must only be installed in a restricted access
location.
In case of wall mount, fix firmly the Intesis device on a not vibrating
surface following the instructions next.
In case of DIN rail mount fix the Intesis device properly to the DIN rail
following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to
earth is recommended.
Disconnect always power of any wires before manipulating and
connecting them to the Intesis device.
A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rated is to be used.
Respect always the expected polarity of power and communication
cables when connecting them to the Intesis device.
Supply always a correct voltage to power the Intesis gateway, see
details of voltage range admitted by the device in the technical
characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type.
Dispose of Used Batteries according to the instructions. Battery
replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without
routing to the outside plant, all communication ports are considered for
indoor only and can be connected SELV circuits only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels
above 4 kV, precautions should be taken when the device is mounted
outside an enclosure. When working in an enclosure (ex. making
adjustments, setting switches etc.) typical anti-static precautions
should be observed before touching the unit.
Safety instructions in other languages can be found at:
https://intesis.com/docs/manuals/v6-safety
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the
Intesis gateway.
Disconnect power of any bus or communication cable before
connecting it to the Intesis device.
Mount the Intesis device on the wall or DIN rail following the instruction
given below, respecting the safety instructions given above.
Connect a NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply to the Intesis gateway, respect the polarity if DC
power or Line and Neutral if AC power. Apply always a voltage within
the range admitted by the Intesis gateway and of enough power (see
technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V6A.
Connect the communication cables to the Intesis device, see details on
the user's manual.
Power the Intesis gateway and the rest of devices connected to it.
NOTE: The device cannot be installed in air-handling space.
Wall Mount
1. Separate the fixing clips in the bottom of the box, pushing
them to the outside until hear the "click" which indicates that
now the clips are in position for wall mount, see in the figure
below.
2. Use the holes of the to fix the box in the wall using screws.
Use the template below for the wall wholes.
Clips in their original position Clips in position for wall mount
(for DIN rail mount)
DIN Rail Mount
With the clips of the box in their original position, insert first the box
in the upper edge of the DIN rail and later insert the box in the down
part of the rail, using a small screwdriver and following the steps in
the figure below.
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B
connector included) for communication between the gateway and the
configuration tool. See CONNECTIONS below and follow instructions
of user’s manual for more details.
The serial number is located at the rear of the gateway.
Record this information in the space provided below.
Refer to it whenever you contact upon your gateway
dealer or support team regarding this product.
Serial No.
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100mm
Color: Light Grey. RAL 7035
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Wall.
DIN rail EN60715 TH35.
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150mA
(HDD connection not allowed)
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC +/-10%
Button A: Check the user manual
Button B: Check the user manual
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
5 to 95%, no condensation
1 x DALI port (Plug-in screw terminal block orange 2 poles)
1500VDC isolation from other ports
DALI guaranteed power: 235mA
Voltage rating: 16VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
1 x DIP-Switch for serial EIA485 configuration:
Reserved for future use
1 x Serial EIA232 (SUB-D9 male connector)
Reserved for future use
1 x Serial EIA485 Plug-in screw terminal block (3 poles)
DALI guaranteed power: 235mA
Voltage rating: 16VDC
1500VDC isolation from other ports
(except PORT B: EIA232)
1 x DIP-Switch for serial EIA485 configuration:
Reserved for future use
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply. Respect polarity applied
of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table below). The power
supply can be connected to earth but only through the negative terminal, never through the positive terminal.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet CAT5
cable. If communicating through the LAN of the building, contact the network administrator and make sure traffic
on the port used is allowed through all the LAN path (check the gateway user manual for more information). With
factory settings, after powering up the gateway, DHCP will be enabled for 30 seconds. After that time, if no IP is
provided by a DHCP server, the default IP 192.168.100.246 will be set.
PortA / DALI #1
Connect the DALI bus to connectors A4 (+), A3 (-) of gateway’s PortA. The Intesis gateway provides
16VDC (+/-2%) DALI voltage to the bus.
PortB / DALI #2
Connect the DALI bus to connectors B2 (+), B1 (-) of gateway’s PortB. The Intesis gateway provides
16VDC (+/-2%) DALI voltage to the bus.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains el ectronic
parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation