HMS 4RO, 6RTD, 8DIO, DAIO, 8AIV User Manual

...
Page 1
Netbiter®IO Extender
4RO | 6RTD | 8DIO | DAIO | 8AIV | 8AIIS
USER MANUAL
HMSI-27-228 3.1 ENGLISH
Page 2
Important User Information
Liability
Every care has been taken in the preparation of this document. Please inform HMS Industrial Networks AB of any inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial Networks AB, reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be considered as a commit­ment by HMS Industrial Networks AB. HMS Industrial Networks AB assumes no responsibility for any errors that may appear in this document.
There are many applications of this product. Those responsible for the use of this device must ensure that all the necessary steps have been taken to verify that the applications meet all performance and safety requirements in­cluding any applicable laws, regulations, codes, and standards.
HMS Industrial Networks AB will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features, timing, or functional side effects found outside the documented scope of this product. The effects caused by any direct or indirect use of such aspects of the product are undefined, and may include e.g. compatibility issues and stability issues.
The examples and illustrations in this document are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks AB cannot as­sume responsibility for actual use based on these examples and illustrations.
Intellectual Property Rights
HMS Industrial Networks AB has intellectual property rights relating to technology embodied in the product de­scribed in this document. These intellectual property rights may include patents and pending patent applications in the USA and other countries.
eWON
®
, Netbiter®, and Netbiter Argos®are registered trademarks of HMS Industrial Networks AB. All other trade-
marks mentioned in this document are the property of their respective holders.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 3
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Table of Contents
Page
1 Preface ............................................................................................................................... 3
1.1 About This Document .....................................................................................................3
1.2 Document history...........................................................................................................3
1.3 Document Conventions ..................................................................................................4
2 Overview............................................................................................................................ 5
2.1 Introduction ...................................................................................................................5
2.2 Data acquisition .............................................................................................................5
2.3 Selection Guide .............................................................................................................5
3 General/Common Characteristics .............................................................................. 6
3.1 Dimensions ...................................................................................................................6
3.2 Common Specifications ..................................................................................................6
3.3 EMC Considerations ......................................................................................................7
3.4 Network Termination ......................................................................................................7
3.5 DIP Switches.................................................................................................................7
3.6 Modbus Node ID Setting.................................................................................................8
3.7 Communication Settings.................................................................................................9
4 IOX-4RO – Relay Outputs............................................................................................ 10
4.1 Description ..................................................................................................................10
4.2 Technical Specifications ............................................................................................... 10
4.3 Status Indicators.......................................................................................................... 10
4.4 Wiring ......................................................................................................................... 11
4.5 DIP Switch Settings...................................................................................................... 12
4.6 Data Registers............................................................................................................. 12
5 IOX-6RTD – RTD Inputs ...............................................................................................13
5.1 Description ..................................................................................................................13
5.2 Technical Specifications ............................................................................................... 13
5.3 Wiring ......................................................................................................................... 14
5.4 Status Indicators.......................................................................................................... 15
5.5 DIP Switch Settings...................................................................................................... 15
5.6 Data Registers............................................................................................................. 16
Page 4
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Table of Contents
6 IOX-8DIO – Digital Inputs/Outputs............................................................................ 17
6.1 Description ..................................................................................................................17
6.2 Technical Specifications ............................................................................................... 17
6.3 Wiring ......................................................................................................................... 18
6.4 Status Indicators.......................................................................................................... 19
6.5 DIP Switch Settings...................................................................................................... 19
6.6 Jumper Settings...........................................................................................................20
6.7 Data Registers ............................................................................................................ 21
7 IOX-DAIO – Digital and Analog Inputs/Outputs.....................................................23
7.1 Description ..................................................................................................................23
7.2 Technical Specifications ............................................................................................... 25
7.3 Status Indicators.......................................................................................................... 26
7.4 Wiring ......................................................................................................................... 27
7.5 DIP Switch Settings...................................................................................................... 27
7.6 Jumper Settings...........................................................................................................28
7.7 Data Registers............................................................................................................. 29
8 IOX-8AIV – Analog Voltage Inputs ............................................................................ 30
8.1 Description ..................................................................................................................30
8.2 Technical Specifications ............................................................................................... 30
8.3 Status Indicators.......................................................................................................... 30
8.4 Wiring ......................................................................................................................... 31
8.5 DIP Switch Settings...................................................................................................... 32
8.6 Data Registers............................................................................................................. 32
9 IOX-8AIIS – Isolated Analog Current Inputs...........................................................34
9.1 Description ..................................................................................................................34
9.2 Technical Specifications ............................................................................................... 34
9.3 Status Indicators.......................................................................................................... 34
9.4 Wiring ......................................................................................................................... 35
9.5 DIP Switch Settings...................................................................................................... 36
9.6 Data Registers............................................................................................................. 36
A Regulatory Compliance ...............................................................................................39
Page 5
Preface 3 (40)
1 Preface
1.1 About This Document
This manual describes how to install and configure Netbiter IO Extender modules.
For additional documentation and software downloads, FAQs, troubleshooting guides and tech­nical support, please visit www.netbiter.com/support.
1.2 Document history
Version Date Description
2.00 Sep 2015 Multiple corrections and updates, new layout
3.0 2016-10-11 Rebranded and updated compliance info
3.1 2017-10-25 Minor corrections
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 6
Preface 4 (40)
1.3 Document Conventions
Ordered lists are used for instructions that must be carried out in sequence:
1. First do this
2. Then do this
Unordered (bulleted) lists are used for:
Itemized information
Instructions that can be carried out in any order
...and for action-result type instructions:
► This action...
leads to this result
Bold typeface indicates interactive parts such as connectors and switches on the hardware, or menus and buttons in a graphical user interface.
Monospaced text is used to indicate program code and other kinds of data input/output such as configuration scripts.
This is a cross-reference within this document: Document Conventions, p. 4
This is an external link (URL): www.hms-networks.com
This is additional information which may facilitate installation and/or operation.
This instruction must be followed to avoid a risk of reduced functionality and/or damage to the equipment, or to avoid a network security risk.
Caution
This instruction must be followed to avoid a risk of personal injury.
WARNING
This instruction must be followed to avoid a risk of death or serious injury.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 7
Overview 5 (40)
2 Overview
2.1 Introduction
The Netbiter I/O Extender series provides a solution for distributed I/O requirements. The I/O system consists of stand-alone digital and analog input/output modules connected together on a RS-485 two-wire multi-drop network.
The modules communicate using the Modbus RTU protocol. The 32-bit ARM CPU in the mod­ule provides high speed data processing and fast communication turnaround times. Multiple baud rates are selectable, from 2400 to 115200 baud.
All I/O modules fit directly onto an industry standard DIN rail. All modules have a minimum isola­tion of 1000 VAC rms between the field and logic.
The modules are equipped with status LEDs to indicate the status of the inputs and outputs. This visual indication assists with fault finding and diagnostics.
2.2 Data acquisition
The primary use of the Netbiter I/O Extender modules is for data acquisition in combination with a Netbiter EC or WS gateway. The Netbiter gateway acts as a Modbus master which retrieves and sends data from the Netbiter I/O Extender modules.
120 Ω
Termination
120 Ω
Termination
RS-485 network
Netbiter EC or WS (Modbus Master)
Netbiter IOX Extenders (Modbus Slaves)
QUERY
REPLY
Fig. 1 Overview
2.3 Selection Guide
Module Type
IOX-4RO 4 relay outputs
IOX-8DIO 8 digital inputs / 8 digital outputs
IOX-6RTD 6 RTD inputs – PT100, Ni120, PT1000, Ni1000, Ni1000LG & Ohms
IOX-DAIO 2 RTD inputs, 2 analog inputs 0(4)-20mA or 0(2)-10V
1 analog output 0(4)-20mA or 0(2)-10V 4 digital inputs, 2 digital outputs
IOX-8AIV 8 analog inputs, 0(2)-10V
IOX-8AIIS 8 fully isolated analog inputs, 0(4)-20mA
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 8
General/Common Characteristics 6 (40)
3 General/Common Characteristics
3.1 Dimensions
The module clips directly onto an industry standard DIN rail (EN 50022).
Field wiring is on the front of the module via a plug-in connector.
Module power and RS-485 communications wiring are on a separate plug-in connector on the bottom side of the housing.
Allow at least 25 mm in front of and below the module to accommodate the wiring.
Ensure that the space above and below the module is sufficient to provide adequate ventilation.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
1C
1NC
2NC
2C
2NC
2NC
3C
3NC
3NC
4C
4NC
4NC
P R T
1234
Fig. 2 Netbiter I/O Extender enclosure
3.2 Common Specifications
Operating temperature -10 °C to +50 °C
Storage temperature -40 °C to +85 °C
Humidity 5–95 % RH, non-condensing
This product contains parts that can be damaged by electrostatic discharge (ESD). Use ESD protective measures to avoid equipment damage.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 9
General/Common Characteristics 7 (40)
3.3 EMC Considerations
The I/O modules will usually be installed in an enclosure along with other devices that generate electromagnetic radiation, such as relays and contactors, transformers, motor controllers, etc. Electromagnetic radiation can induce electrical noise in both power and signal lines. Direct radi­ation into the module can also have a negative effect on the system.
Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent interference. Protective steps include control cabinet grounding, module grounding, cable shield grounding, protective elements for electromagnetic switching devices, correct wiring, as well as the consideration of cable types and their cross sections.
Use screened twisted pair RS-485 cable with the screen grounded at one point.
Use screened I/O, T/C, and RTD cables, with the screens grounded at one point as close as possible to the I/O module.
3.4 Network Termination
Transmission line effects often present a problem on data communication networks. These problems include reflections and signal attenuation.
If it should be necessary to eliminate reflections from the ends of the cable, the cable can be ter­minated with a resistor across the line equal to its characteristic impedance. Both ends should be terminated, as propagation is bi-directional. In the case of an RS-485 twisted pair cable, this termination is typically 120 Ohms.
3.5 DIP Switches
1ON2 3 4 5 6 7 8 9 0
Fig. 3 DIP switches
DIP Switch Functions
Switch Function
1–7 Modbus Node ID
See Modbus Node ID Setting, p. 8
8
Module specific settings.
9
0 Baud rate: OFF = 9600, ON = programmed
See Communication Settings, p. 9
The status of the DIP switches is stored in register 30100.
MSB DIP Switch Status Register LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30100
0 9 8 7 6 5 4 3 2 1
DIP Switches
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 10
General/Common Characteristics 8 (40)
3.6 Modbus Node ID Setting
Switches 1 to 7 are used to set the Modbus Node ID as shown in this table.
All modules will respond to a default Node ID of 254.
Fig. 4 Node ID DIP switch chart
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 11
General/Common Characteristics 9 (40)
3.7 Communication Settings
The data in the modules is stored in 16-bit registers. These registers are accessed over the net­work using the Modbus RTU communication protocol.
DIP Switch 0 setting OFF (Default) ON (Programmed Baud Setting)
Baud rate 9600 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data bits 8 8
Parity None None, Even, Odd
Stop bits 1 1, 2
3.7.1 Communication Settings Registers
Modbus Register
Register Name
Low Limit
High Limit
Ac­cess
Comments
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200, 38400,57600,11520
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W (x10ms)
The baud rate value is programmed directly into the baud rate register. The only exception is the 115200 baud rate, where the value 11520 is used.
The reply delay is a time delay between the Modbus message being received to the reply being sent. In some applications where a modem or radio is used in the RS-485 network, it may be necessary to add a reply delay due to turnaround delays in the equipment.
Time (x 10 ms)
Rx Query
Tx Reply
Reply Delay
Fig. 5 Reply delay
Reply delay works only when DIP switch 0 is set to ON.
3.7.2 Supported Modbus Functions
Function Code Modbus Function Comment
1 Read Coil Status Digital inputs/outputs
2 Read Input Status Digital inputs/outputs
3 Read Holding Registers Analog inputs/outputs
4 Read Input Registers Analog inputs/outputs
5
Write Single Coil Digital outputs
6 Write Single Register Analog outputs
15 Write Multiple Coils Digital outputs
16 Write Multiple Registers Analog outputs
The Modbus message length must be limited to 100 consecutive read or write registers. If more registers are required, a new poll group must be added.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 12
IOX-4RO – Relay Outputs 10 (40)
4 IOX-4RO – Relay Outputs
4.1 Description
The IOX-4RO module has 4 normally open/closed relay outputs. This module may be used for a higher drive capability, or when isolation between outputs is required.
When switch 9 is OFF, the module is configured as a Modbus slave and the outputs are written to by the Modbus master (PC/PLC/HMI). Each output on the module can be individually switched ON or OFF, or all outputs can be set up at the same time by writing a single number to the output register that represents the status of all outputs.
An output watchdog timer can be configured to switch off all outputs if there has been no com­munication with the module for up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state.
4.2 Technical Specifications
Power supply Logic supply voltage 24 VDC
Logic supply current 42 mA
Relay outputs Output points 4
Maximum current 0.5 A @ 220 VAC / 1 A @ 28 VDC
Isolation 1000 Vrms between field and logic
1000 Vrms between outputs
Temperature Operating temperature. -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
4.3 Status Indicators
1 2 3 4
P R T
RS-485 Rx RS-485 TxPower
Outputs 1 – 4
Fig. 6 IOX-4RO Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Outputs 1–4 OFF when the output is off, ON when the output is on.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 13
IOX-4RO – Relay Outputs 11 (40)
4.4 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
Pin Connection
24 VDC @ 42 mA
RS-485
-
+
A B
Fig. 7 IOX-4RO power and RS-485 wiring
Relay 1 Common
Relay 1 Normally Open
Relay 1 Normally Closed
Relay 2 Common
Relay 2 Normally Open
Relay 2 Normally Closed
Relay 3 Common
Relay 3 Normally Open
Relay 3 Normally Closed
Relay 4 Common
Relay 4 Normally Open
Relay 4 Normally Closed
+24 VDC / 220 VAC
0 VDC / 220 VAC
RELAY
+
-
Fig. 8 IOX-4RO relay wiring example
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 14
IOX-4RO – Relay Outputs 12 (40)
4.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8
-
Not used
9 MODE Slave (OFF)
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
4.6 Data Registers
MODULE TYPE = 113
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
00001 Relay Output 1 0 1 R/W
Status of Digital Outputs.
00002 Relay Output 2 0 1 R/W
00003 Relay Output 3 0 1 R/W
00004 Relay Output 4 0 1 R/W
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 113
40002 Digital Outputs N/A N/A R/W Digital Outputs in bits. 4(msb) - 1(lsb).
30100 DIP Switch 0 65535 R Status of DIP switch on front panel
40101 Watchdog Timer 0 255 R/W Timer in seconds.
0 = disabled. 1–255 = enabled.
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600,19200, 38400, 57600,
115200 (115200 is entered as 11520)
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable (x10 ms)
4.6.1 Relay Output Register
The relay outputs can be read/written in a single register as follows:
MSB IOX-4RO Relay Outputs LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 40002
— — —
4 3 2 1
Relay Output Number
4.6.2 Output Watchdog Timer
The watchdog timer is used to switch off all outputs in the event of a communications failure. When register 40101 is set to zero, the watchdog timer is disabled.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 15
IOX-6RTD – RTD Inputs 13 (40)
5 IOX-6RTD – RTD Inputs
5.1 Description
The IOX-6RTD is a 6 RTD input module that can accommodate 2 or 3-wire RTD sensors. The RTD inputs are isolated from the logic.
The RTD resistance is read by the module circuitry, linearised and converted to degrees Cel­sius. No ranging is required, as the module covers the full range of the RTD, as indicated in the RTD table. The value read from the Modbus register is the actual temperature with 0.1 °C reso­lution. i.e., a value of 3451 corresponds to a temperature of 345.1 °C.
The RTD type is set up by writing a value to the RTD Type register. The value is obtained from the table below. For example, to select PT100 RTD, the value “1” must be written to the RTD Type register. All 6 RTD inputs adopt the same RTD type.
DIP switch 9 is used to select upscale or downscale burnout for break detection. A value of 32768 is used to indicate upscale burnout and a value of -32767 indicates downscale burnout.
As there is no inter-channel isolation, isolated RTD:s must be used in order to prevent ground loops and read errors.
5.2 Technical Specifications
Power supply Logic supply voltage 12–24 VDC
Logic supply current 87 mA @ 12 V / 45 mA @ 24 V
RTD inputs Input points 6
RTD configuration 2- or 3-wire
Resolution 0.1 °C
Drift 100 ppm/°C typical
Line resistance effect < 0.1 °C balanced
Max. line resistance 100 Ohms
Isolation 1500 Vrms between field and logic
RTD type Number Type Range Accuracy
1 Pt100 -200 to +850 °C ±0.3 °C IEC
751:1983
2 Ni120 -80 to +320 °C ±0.3 °C
3 Pt1000 -200 to +850 °C ±0.3 °C
4 Ni1000 (DIN) -200 to +850 °C ±0.3 °C
5 Ni1000
(Landis+Gyr)
-200 to +850 °C ±0.3 °C
6 Ohms 10–400 Ω ±0.05 %
7
Ohms 100–4000 Ω ±0.05 %
Temperature Operating temperature -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 16
IOX-6RTD – RTD Inputs 14 (40)
5.3 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
12 VDC @ 87 mA
Pin Connection
24 VDC @ 45 mA
RS-485
-
+
A B
Fig. 9 IOX-6RTD power and RS-485 wiring
Input 1a
1bInput
Input 1c
2aInput
Input 2b
2cInput
Input 3a
3bInput Input 3c
4aInput Input 4b
4cInput
Input 5a
5bInput Input 5c
6aInput
RTD
3 Wire
Input 6b
6cInput
RTD
2 Wire
Fig. 10 IOX-6RTD input wiring example
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 17
IOX-6RTD – RTD Inputs 15 (40)
5.4 Status Indicators
1 2 3 4 5 6
P R T
Inputs 1 – 6
RS-485 Rx RS-485 TxPower
Fig. 11 IOX-6RTD Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Inputs 1–6 ON when the RTD is open circuit, OFF when the RTD is connected.
5.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8
-
Not used
9 BREAK RTD break. When switched OFF, the RTD value will be -32767 when the RTD
is faulty. When set to ON, the RTD value will be 32768.
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 18
IOX-6RTD – RTD Inputs 16 (40)
5.6 Data Registers
MODULE TYPE = 109
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 109
30002 RTD Input 1 R
For ranges,see Technical Specifications,
p. 13.
30003 RTD Input 2 R
30004 RTD Input 3 R
30005 RTD Input 4 R
30006 RTD Input 5 R
30007 RTD Input 6 R
30008 Input Status 0 65535 R bit1 = 0 (OK)
bit1 = 1 (Error or open circuit)
30100 DIP Switch 0 65535 R Status of DIP switch on front panel
40101 RTD Type 1 7
R/W See Technical Specifications, p. 13.
40102 Line Frequency 50 60 R/W Line frequency
40103 Units Type 1 2 R/W 1 = °C, 2 = °F
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200,
38400,57600,115200
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
5.6.1 RTD Input Status
There is one status bit associated with each RTD input. These bits are used to indicate if the in­put is open circuit or over range, and if so the error bit will be set.
Bit 1 – Error Bit 2 – Not used Condition Status LED
0 0 Input working OK LED OFF
1 0 Open circuit/Over range LED ON
DIP Switch Status Register (30100)
MSB IOX-6RTD Input Status LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30008
RTD6 Error
RTD5Error
RTD4 Error
RTD3 Error
RTD2 Error
RTD1 Error
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 19
IOX-8DIO – Digital Inputs/Outputs 17 (40)
6 IOX-8DIO – Digital Inputs/Outputs
6.1 Description
The IOX-8DIO module has 8 digital inputs and 8 digital outputs. The inputs are isolated from the logic by bi-directional opto-couplers. The common is connected internally to either the +V or -V field power supply terminals, using a jumper inside the housing.
The inputs have internal counters associated with them. These are 32-bit counters allowing a count value in the range 0-4294967295. This value can be cleared by writing a zero to the asso­ciated registers, or it can be preset to any other value using the same method.
The count values will be lost if power is disconnected.
The format of the registers allows the status of the inputs to be read either as single bits, or all at once as a single register on the Modbus network.
The 8 digital outputs are of the type open collector (NPN). These may be used to drive lamps or external relays when more drive capability is required. The outputs are isolated from the logic and they share a common negative terminal.
When switch 9 is OFF, the module is configured as a Modbus slave and the outputs are written to by the Modbus master (PC/PLC/HMI). Each output on the module can be individually switched ON or OFF, or all outputs can be set up at the same time by writing a single number to the output register that represents the status of all outputs.
6.2 Technical Specifications
Power supply Logic supply voltage 12–24 VDC
Logic supply current 33 mA @ 12 V / 19 mA @ 24 V
Field supply voltage 12–24 VDC
Field supply current 6 mA @ 12 V / 6 mA | 24 V
Digital inputs Input points 8
Input voltage range 12–24 VDC
Input current per input 5 mA @ 12 V / 11 mA @ 24 V
Isolation 1500 Vrms between field and logic
Digital outputs Output points 8
Maximum voltage 36 VDC
Maximum current 100 mA per output
VCEon 1.1 V (max)
Isolation 1500 Vrms between field and logic
Counters Inputs 1 to 16
Resolution 32 bits
Frequency 1 KHz (max)
Pulse width 500 µs (min)
Temperature Operating temperature -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
Inputs 1 to 8 are used both as digital inputs and counter inputs.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 20
IOX-8DIO – Digital Inputs/Outputs 18 (40)
6.3 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
12 VDC @ 33 mA
Pin Connection
24 VDC @ 19 mA
RS-485
-
+
A B
Fig. 12 IOX-8DIO power and RS-485 wiring
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Output 1
+12–24 VDC
or
0 VDC
+12–24 VDC
0 VDC
+V
0V
+12–24 VDC
RELAY
+
-
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
( Set internal jumper )
Fig. 13 IOX-8DIO input/output wiring example
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 21
IOX-8DIO – Digital Inputs/Outputs 19 (40)
6.4 Status Indicators
I1 I2 I3 I4
I7 I8I5 I6
O1 O2 O3 O4
O7 O8O5 O6
P R T
Inputs 1 – 8
Outputs 1 – 8
RS-485 Rx RS-485 TxPower
Fig. 14 IOX-8DIO Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Inputs 1–8 OFF when the input is off, ON when the input is on.
Outputs 1–8 OFF when the output is off, ON when the output is on.
6.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8
INVERT
ON = status of the inputs is inverted in the Modbus status register (30002)
9 MODE OFF (Slave)
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 22
IOX-8DIO – Digital Inputs/Outputs 20 (40)
6.6 Jumper Settings
The digital inputs can be configured as NPN or PNP by changing the position of jumper LK1.
LK1 jumper setting
Position Function
NPN (default) Digital inputs operated by switching to -V (0 V)
PNP Digital inputs operated by switching to +V (+12 V to +24 V)
LK1
LK1
PNP NPN
PNP NPNPNP NPN
Fig. 15 LK1 jumper setting
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 23
IOX-8DIO – Digital Inputs/Outputs 21 (40)
6.7 Data Registers
MODULE TYPE = 102
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
10001 Digital Input 1 0 1 R
Status of digital inputs
10002 Digital Input 2 0 1 R
10003 Digital Input 3 0 1 R
10004 Digital Input 4 0 1 R
10005 Digital Input 5 0 1 R
10006 Digital Input 6 0 1 R
10007 Digital Input 7 0 1 R
10008 Digital Input 8 0 1 R
00017 Digital Output 1 0 1 R/W
Status of digital outputs
00018 Digital Output 2 0 1 R/W
00019 Digital Output 3 0 1 R/W
00020 Digital Output 4 0 1 R/W
00021 Digital Output 5 0 1 R/W
00022 Digital Output 6 0 1 R/W
00023 Digital Output 7 0 1 R/W
00024 Digital Output 8 0 1 R/W
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 102
30002 Digital Inputs N/A N/A R Digital inputs in lower 8 bits. 8-1.
40003 Digital Outputs N/A N/A R/W Digital outputs in lower 8 bits. 8-1.
40004 Counter 1 MSB 0 65535 R/W
Counter MSB and LSB combine to give a 32-bit counter with range 0-4294967295.
40005 Counter 1 LSB 0 65535 R/W
40006 Counter 2 MSB 0 65535 R/W
40007 Counter 2 LSB 0 65535 R/W
40008 Counter 3 MSB 0 65535 R/W
40009 Counter 3 LSB 0 65535 R/W
40010 Counter 4 LSB 0 65535 R/W
40011 Counter 4 LSB 0 65535 R/W
40012 Counter 5 MSB 0 65535 R/W
40013 Counter 5 LSB 0 65535 R/W
40014 Counter 6 MSB 0 65535 R/W
40015 Counter 6 LSB 0 65535 R/W
40016 Counter 7 MSB 0 65535 R/W
40017 Counter 7 LSB 0 65535 R/W
40018 Counter 8 MSB 0 65535 R/W
40019 Counter 8 LSB 0 65535 R/W
30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel
40101 Watchdog Timer 0 255 R/W Timer in seconds. 0 = disabled. 1–255 =
enabled.
40105 Counter Mode 0 2 R/W 0 = Disable, 1 = Up Counting, 2 = Up/
Down Count
40106 Input Filter 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200,
38400,57600,115200
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 24
IOX-8DIO – Digital Inputs/Outputs 22 (40)
6.7.1 Digital Input Register
The digital inputs can be read in a single register as follows:
MSB IOX-8DIO Digital Inputs LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30002
8 7 6 5 4 3 2 1
Digital Input Number
6.7.2 Digital Output Register
The digital outputs can be read/written in a single register as follows:
MSB IOX-8DIO Digital Outputs LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 40003
8 7 6 5 4 3 2 1
Digital Output Number
6.7.3 Counter Registers
Counters are stored in two 16-bit registers: the High Register and the Low Register. To get the actual 32-bit count value, the registers must be combined as follows:
Counter High Value Register 40003
Counter Low Value Register 40004
Counter Value (Counter High Value x 65535) + Counter Low Value
6.7.4 Output Watchdog Timer
The watchdog timer is used to switch off all outputs in the event of a communications failure. When register 40101 is set to zero, the watchdog timer is disabled.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 25
IOX-DAIO – Digital and Analog Inputs/Outputs 23 (40)
7 IOX-DAIO – Digital and Analog Inputs/Outputs
7.1 Description
The IOX-DAIO module is a multi-purpose combination of inputs and outputs. It can accommo­date the following:
2- or 3-wire RTD sensors
Current (0–20 mA) inputs
Voltage (0–10 V) inputs
Current (0–20 mA) output
Voltage (0–10 V) output
Digital inputs
Digital outputs
7.1.1 RTD Inputs
The RTD resistance is read by the module circuitry, linearised and converted to degrees Cel­sius. No ranging is required, as the module covers the full range of the RTD, as indicated in the RTD table. The value read from the Modbus register is the actual temperature with 0.1 °C reso­lution. i.e., a value of 3451 corresponds to a temperature of 345.1 °C.
The RTD type is set up by writing a value to the RTD Type register. The value is obtained from the table below. For example, to select PT100 RTD, the value “1” must be written to the RTD Type register. All 6 RTD inputs adopt the same RTD type.
A value of -32767 indicates downscale burnout.
As there is no inter-channel isolation, isolated RTD:s must be used in order to prevent ground loops and read errors.
7.1.2 Analog Inputs
The Analog Inputs can be configured by internal jumpers as current inputs (0–20 mA), or as voltage inputs (0–10 V). An input within these ranges represents an output value range of 0– 4095 (12 bits) in the corresponding Modbus register.
7.1.3 Analog Output
The single analog output can be configured by internal jumpers for a current output (0–20 mA), or a voltage output (0–10 V).
The resolution is 12 bits, so writing a value to the Modbus register of 0–4095 would give an out­put current of 0–20 mA. A value of 819 ± 1LSB will give a current output of 4 mA.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 26
IOX-DAIO – Digital and Analog Inputs/Outputs 24 (40)
7.1.4 Digital Inputs
There are 4 digital inputs on the module. These share a common terminal and can be config­ured for common positive or common negative.
The inputs have counters associated with them, which operate in three modes:
Mode 0 All counters are disabled.
Mode 1 All counters are 32-bit counters allowing a count value 0–4294967295. The count
value can be cleared by writing a zero to the associated registers, or they can be preset to any other value using the same method.
Mode 2 The inputs are connected as up/down counters. Input 1 will count counter 1 up,
while input 2 counts counter 1 down.
The count values will be lost if power is disconnected.
The format of the registers allows the status of the inputs to be read either as single bits, or all at once as a single register on the Modbus network.
7.1.5 Digital Outputs
The 2 digital outputs are of the type open collector (NPN). These may be used to drive lamps or external relays when more drive capability is required. The outputs are isolated from the logic and they share a common negative terminal.
The outputs are written to by a Modbus master device, such as a PC / PLC / HMI. Each output on the module can be individually switched ON or OFF, or all outputs can be set up at the same time by writing a single number to the output register that represents the status of all outputs.
An output watchdog timer can be configured to switch off all outputs if there has been no com­munication with the module for up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 27
IOX-DAIO – Digital and Analog Inputs/Outputs 25 (40)
7.2 Technical Specifications
Power supply Logic supply voltage 12–24 VDC
Logic supply current 115 mA @ 12 V / 58 mA @ 24 V
Field supply voltage 24 VDC
Field supply current 25 mA
RTD inputs Input points 2
RTD configuration 2- or 3-wire
Resolution 0.1 °C
Drift 100 ppm/°C typical
Line resistance effect < 0.1 °C balanced
Max. line resistance 100 Ω
Isolation 1500 Vrms between field and logic
RTD type Number Type Range Accuracy
1 Pt100 -200 to +850 °C ±0.3 °C IEC
751:1983
2 Ni120 -80 to +320 °C ±0.3 °C
3 Pt1000 -200 to +850 °C ±0.3 °C
4 Ni1000 (DIN) -200 to +850 °C ±0.3 °C
5 Ni1000
(Landis+Gyr)
-200 to +850 °C ±0.3 °C
6 Ohms 10–400 Ω ±0.05 %
7
Ohms 100–4000 Ω ±0.05 %
Current inputs Input points 2
Input current 0–20 mA
Input resistance 250 Ω
Input type Range Resolution
1 0–4095 12 bits
2 0–20 mA 1 µA
3 +/- 20 mA 1 µA
Drift 100 ppm/°C
Accuracy 0.2 % of span
Isolation 1000 Vrms between field and logic
Voltage inputs Input points 2
Input voltage 0–1 VDC or 0–10 VDC
Input resistance 190 kΩ
Input type Range Resolution
4 0–4095 12 bits
5 0–10 V 1 mV
6 +/-10 V 1 mV
7 0–1 V 0.1 mV
8 +/-1 V 0.1 mV
Drift 100 ppm/°C
Accuracy 0.2 % of span
Isolation 1000 Vrms between field and logic
Current outputs Output points 1
Output current 0–20 mA
Output type Range Resolution
1 0–4095 12 bits
Drift 100 ppm/°C
Accuracy 0.05 % of span
Compliance 500 Ω max. @ 12 VDC
1000 Ω max. @ 24 VDC
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 28
IOX-DAIO – Digital and Analog Inputs/Outputs 26 (40)
Voltage outputs Output points 2
Output voltage 0 (2)–10 V
Output type Range Resolution
2 0–4095 12 bits
Drift 100 ppm/°C
Accuracy 0.05 % of span
Compliance 200 Ω min. load
Digital inputs Input points 4
Input voltage range 10–26 VDC
Input current per input 4 mA @ 12 V / 8 mA @ 24 V
Isolation 1500 Vrms between field and logic
Digital outputs Output points 2
Maximum voltage 36 VDC
Maximum current 100 mA per output
VCEon 1.1 V (max)
Isolation 1500 Vrms between field and logic
Counters Inputs 1 to 4
Resolution 32 bits
Frequency 50 Hz (max)
Pulse width 20 ms (min)
Temperature Operating temperature -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
7.3 Status Indicators
I1 I2 I3 I4
I7 I8I5 I6
O1 O2 O3 O4
O7 O8O5 O6
Inputs 1 – 8
Outputs 1 – 8
RS-485 Rx RS-485 TxPower
P R T
Fig. 16 IOX-DAIO Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Input/Output status LEDs are not available in the IOX-DAIO module.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 29
IOX-DAIO – Digital and Analog Inputs/Outputs 27 (40)
7.4 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
12 VDC @ 115 mA
Pin Connection
24 VDC @ 58 mA
RS-485
-
+
A B
Fig. 17 IOX-DAIO power and RS-485 wiring
RTD Input 1a
RTD 1bInput
RTD Input 2a
RTD 2cInput
Common/0V
Analog 1Input
Analog Input 2
Analog Out 1put Common/0V
Digital 1Input Digital Input 2
Digital 3Input
Digital Input 4
Digital CommonInput Digital Output 1
Digital Output 2
RTD
3 Wire
+V
Common/0V
+24 VDC
0 VDC
+24 VDC
0 VDC
0 VDC
+24 VDC
or
+24 VDC
RELAY
+
-
+24 VDC
+
Two Wire Transmitter
0(4)–20 mA
-
Analog Load
0–20 mA
or
0–10 V
+
-
0 VDC
Fig. 18 IOX-DAIO input/output wiring example
7.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8
Not used
9
Not used
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 30
IOX-DAIO – Digital and Analog Inputs/Outputs 28 (40)
7.6 Jumper Settings
The two analog inputs and single analog output can be configured for current or voltage by changing the position of jumpers J7–J11.
J7 (AI1) J8 (AI2)
Current input
Voltage input
Fig. 19 Analog inputs jumper setting
J9
J10J11
Current output
Voltage output
I V
I V
Fig. 20 Analog output jumper setting
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 31
IOX-DAIO – Digital and Analog Inputs/Outputs 29 (40)
7.7 Data Registers
MODULE TYPE = 112
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
10001 Digital Input 1 0 1 R
Status of Digital Inputs
10002 Digital Input 2 0 1 R
10003 Digital Input 3 0 1 R
10004 Digital Input 4 0 1 R
00017 Digital Output 1 0 1 R/W
Status of Digital Outputs
00018 Digital Output 2 0 1 R/W
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 102
30002 Digital Inputs N/A N/A R Digital inputs in lower 8 bits. 8-1.
40003 Digital Outputs N/A N/A R/W Digital outputs in lower 8 bits. 8-1.
40004 RTD Input 1
R
For ranges, see Technical Specifications,
p. 25.
40005 RTD Input 2
R
40006 Analog Input 1 0 4095 R
40007 Analog Input 2 0 4095 R
40008 Analog Output 0 4095 R/W
40009 Counter 1 MSB 0 65535 R/W
Counter MSB and LSB combine to give a 32-bit counter with range 0-4294967295.
40010 Counter 1 LSB 0 65535 R/W
40011 Counter 2 MSB 0 65535 R/W
40012 Counter 2 LSB 0 65535 R/W
40013 Counter 3 MSB 0 65535 R/W
40014 Counter 3 LSB 0 65535 R/W
40015 Counter 4 MSB 0 65535 R/W
40016 Counter 4 LSB 0 65535 R/W
30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel
40101 Watchdog Timer 0 255 R/W Timer in seconds. 0 = disabled. 1–255 =
enabled.
40102 Counter Mode 0 2 R/W 0 = Disable, 1 = Up Counting,
2 = Up/Down Count
40103 Input Filter 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
40104 RTD 1 Type 1 7
R/W
See Technical Specifications, p. 25
40105 RTD 2 Type 1 7
R/W
40106 AI 1 Type 1 8 R/W
40107 AI 2 Type 1 8 R/W
40108 AO Type 1 2 R/W 1 = 0–20 mA, 2 = 0–10 V
40109 Line Frequency 50 60 R/W Line frequency
40110 Units Type 1 2 R/W 1 = °C, 2 = °F
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200,
38400,57600,115200
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 32
IOX-8AIV – Analog Voltage Inputs 30 (40)
8 IOX-8AIV – Analog Voltage Inputs
8.1 Description
The IOX-8AIV module has 8 analog voltage inputs. The inputs are isolated from the logic and share a common negative terminal.
An input voltage of 0–10 V corresponds to an output of 0–4095 (12 bits) in the Modbus register. If the OFFSET switch is switched on, 0–4095 represents 2–10 V.
If the jumper on the analog board is removed, the input range will be 0–5 V, or 1–5 V if the OFF­SET switch is on.
8.2 Technical Specifications
Power supply Logic supply voltage 12–24 VDC
Logic supply current 27 mA @ 12 V / 16 mA @ 24 V
Field supply voltage 12–24 VDC
Field supply current 8 mA @ 12 V / 15 mA @ 24 V
Voltage inputs Input points 8
Input voltage 0(2)–10 VDC or 0(1)–5 VDC
Input resistance 20 kΩ
Resolution 12 bits
Drift 50 ppm/°C
Accuracy 0.2 % of span
Isolation 1500 Vrms between field and logic
Temperature Operating temperature -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
8.3 Status Indicators
I1 I2 I3 I4
I7 I8I5 I6
Inputs 1 – 8
RS-485 Rx RS-485 TxPower
P R T
Fig. 21 IOX-8AIV Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Inputs 1–8 OFF when the input is off, ON when the input is on.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 33
IOX-8AIV – Analog Voltage Inputs 31 (40)
8.4 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
- 12 VDC @ 27 mA
Pin Connection
+ 24 VDC @ 16 mA
+ Comms
- RS-485
Fig. 22 IOX-8AIV power and RS-485 wiring
Input 1
Common
Input 2
Common
Input 3
Common
Input 4
Common
+12–24 VDC
0 VDC
+V
0V/Common
Input 5
Common Input 6
Common
Input 7
Common Input 8 Common
+24 VDC
+
Voltage Source
0(2)–10 VDC
-
Sensor
Fig. 23 IOX-8AIV input wiring example
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 34
IOX-8AIV – Analog Voltage Inputs 32 (40)
8.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8
Not used
9 OFFSET ON = inputs are scaled to accept a 2 V offset.
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
8.6 Data Registers
MODULE TYPE = 104
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 102
30002 Analog Input 1 0 4095 R
Analog inputs in lower 12 bits.
30003 Analog Input 2 0 4095 R
30004 Analog Input 3 0 4095 R
30005 Analog Input 4 0 4095 R
30006 Analog Input 5 0 4095 R
30007 Analog Input 6 0 4095 R
30008 Analog Input 7 0 4095 R
30009 Analog Input 8 0 4095 R
30010 Input Status 0 65535 R bit 2 = 0 (open circuit or <2)
bit 2 = 1 (over range) bit 1 = 0 (OK) bit 1 = 1 (error)
30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200,
38400,57600,115200
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
8.6.1 Analog Input Registers
The analog inputs are read as a 12 bit value in the registers as follows:
MSB IOX-8AIVAnalog Inputs LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 300xx
x x x x x x x x x x x x
Analog Input: 12 bit value (0–4095)
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 35
IOX-8AIV – Analog Voltage Inputs 33 (40)
8.6.2 Analog Input Status
There are two status bits associated with each analog input. These bits are used to indicate if the input is zero or open circuit, in the working range 0–4095, or over range. If the input is open circuit or over range, the error bit will be set. When the error bit is set, the range bit is zero if the input is open circuit, and is set if the input is over range.
Bit 1 – Error Bit 2 – Range Condition Status LED
0 Any Input working OK Off
1 0 Open circuit or zero On
1 1 Over range Flashing
MSB IOX-8AIV Analog Input Status LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30010
AI 8 Range
AI 8 Error
AI 7 Range
AI 7 Error
AI 6 Range
AI 6 Error
AI 5 Range
AI 5 Error
AI 4 Range
AI 4 Error
AI 3 Range
AI 3 Error
AI 2 Range
AI 2 Error
AI 1 Range
AI 1 Error
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 36
IOX-8AIIS – Isolated Analog Current Inputs 34 (40)
9 IOX-8AIIS – Isolated Analog Current Inputs
9.1 Description
The 8 current inputs in the IOX-8AIIS module are fully isolated from input to logic, and between inputs. This module is ideal for monitoring current loops that are isolated from each other and which cannot be connected to a common point of reference.
An input current of 0–20 mA corresponds to an output of 0–4095 (12 bits) in the Modbus regis­ter. If the OFFSET switch is switched on, 0–4095 represents 4–20 mA.
The module can also be configured for a 0–20 mA input range or a +/- 20 mA input.
9.2 Technical Specifications
Power supply Logic supply voltage 12–24 VDC
Logic supply current 58 mA @ 12 V / 31 mA @ 24 V
Current inputs Input points 8
Input current 0(4)–20 20 mA
Input type Range Resolution
1 0–4095 12 bits
2 0–20 mA 1 µA
3 +/- 20 mA 1 µA
Drift 100 ppm/°C
Isolation 1000 Vrms between field and logic
350 V peak between each input
Temperature Operating temperature -10 °C to + 50 °C
Storage temperature -40 °C to + 85 °C
Connectors Logic power and comms. 4-pin connector on underside of unit
Outputs 18-way screw connector on front
9.3 Status Indicators
I1 I2 I3 I4
I7 I8I5 I6
Inputs 1 – 8
RS-485 Rx RS-485 TxPower
P R T
Fig. 24 IOX-8AIIS Status Indicators
Power Indicates that the CPU is running.
RS-485 Rx Flashes to indicate that the unit has received a valid Modbus message.
RS-485 Tx Flashes to indicate that the unit has sent a Modbus message.
Inputs 1–8 OFF when the input is off, ON when the input is on.
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 37
IOX-8AIIS – Isolated Analog Current Inputs 35 (40)
9.4 Wiring
Do not reverse the power/communications connections as this may damage the unit.
1
3
4
2
12 VDC @ 58 mA
Pin Connection
24 VDC @ 31 mA
RS-485
-
+
A B
Fig. 25 IOX-8AIIS power and RS-485 wiring
Input 1
Common 1
Input 2
Common 2
Input 3
Common 3
Input 4
Common 4
0 VDC
+24 VDC
+
Input 5
Common 5
Input 6
Common 6
Input 7
Common 7
Input 8
Common 8
Two Wire Transmitter
0(4)–20 mA
+24 VDC
+
Current Source
0(4)–20 mA
-
Sensor
-
Fig. 26 IOX-8AIIS input wiring example
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 38
IOX-8AIIS – Isolated Analog Current Inputs 36 (40)
9.5 DIP Switch Settings
Switch Function Description
1–7 NODE ID Modbus Node ID — See Modbus Node ID Setting, p. 8
8 OFFSET ON = inputs are scaled to accept a 4 mA offset.
9 OUT OF RANGE Out of range is given when the input is too negative or too positive.
OFF = the analog value will be loaded with -32767 when out of range. ON = the analog value will be loaded with 32768 when out of range.
0 BAUD RATE OFF = 9600, ON = programmed. See Communication Settings, p. 9.
9.6 Data Registers
MODULE TYPE = 104
Modbus Register
Register Name Low
Limit
High Limit
Access Comments
30001 S/W Version /
Module Type
N/A N/A R High Byte = Software Version
Low byte = 102
30002 Analog Input 1 0 4095 R
Analog inputs in lower 12 bits.
30003 Analog Input 2 0 4095 R
30004 Analog Input 3 0 4095 R
30005 Analog Input 4 0 4095 R
30006 Analog Input 5 0 4095 R
30007 Analog Input 6 0 4095 R
30008 Analog Input 7 0 4095 R
30009 Analog Input 8 0 4095 R
30010 Input Status 0 65535 R bit 2 = 0 (open circuit or <2)
bit 2 = 1 (over range) bit 1 = 0 (OK) bit 1 = 1 (error)
30100 DIP Switch 0 65535 R Status of DIP Switch on Front Panel
40101 Analog Input
Type
0 5
R/W See Technical Specifications, p. 34.
40121 Baud Rate 2400 11520 R/W 2400, 4800, 9600, 19200,
38400,57600,115200
40122 Parity 0 2 R/W 0 = none, 1 = even, 2 = odd
40123 Stop Bits 1 2 R/W 1 = 1 stop bit, 2 = 2 stop bits
40124 Reply Delay 0 65535 R/W 0 = Disable, >0 = Enable. (x10 ms)
9.6.1 Analog Input Registers
The analog inputs are read as a 12 bit value in the registers as follows:
MSB IOX-8AIIS Analog Inputs LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 300xx
x x x x x x x x x x x x
Analog Input: 12 bit value (0–4095)
Netbiter
®
IO Extender User Manual HMSI-27-228 3.1
Page 39
IOX-8AIIS – Isolated Analog Current Inputs 37 (40)
9.6.2 Analog Input Status
There are two status bits associated with each analog input. These bits are used to indicate if the input is zero or open circuit, in the working range 0–4095, or over range. If the input is open circuit or over range, the error bit will be set. When the error bit is set, the range bit is zero if the input is open circuit, and is set if the input is over range.
Bit 1 – Error Bit 2 – Range Condition Status LED
0 Any Input working OK Off
1 0 Open circuit or zero On
1 1 Over range Flashing
MSB IOX-8AIIS Analog Input Status LSB
Address
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
32768 16384 8192 4096 2048 1024 512 256 128 64 32 16 8 4 2 1 30010
AI 8 Range
AI 8 Error
AI 7 Range
AI 7 Error
AI 6 Range
AI 6 Error
AI 5 Range
AI 5 Error
AI 4 Range
AI 4 Error
AI 3 Range
AI 3 Error
AI 2 Range
AI 2 Error
AI 1 Range
AI 1 Error
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 40
This page intentionally left blank
Page 41
Appendix A: Regulatory Compliance 39 (40)
A Regulatory Compliance
This product is in compliance with applicable EU directives. The Declaration of Conformity is available at www.netbiter.com/support.
Netbiter®IO Extender User Manual HMSI-27-228 3.1
Page 42
last page
© 2017 HMS Industrial Networks AB
Box 4126 300 04 Halmstad, Sweden
info@hms.se HMSI-27-228 3.1.5925 / 2017-10-25
Loading...