INSTALLATION INSTRUCTIONS
USAGE INSTRUCTIONS
1. Remove the contents from the box.
2. Insert the controller into the panel. A square hole must be cut into the panel with dimensions
of 2-21/32 in. x 2-21/32 in. (67 mm x 67 mm). Page 8 includes a cut-out diagram.
3. Mount the controller to the panel by inserting the mounting brackets into the grooves on the
bottom and top of the controller. Fasten the brackets with the included screws.
4. View the contact diagram on the side of the controller (also on page 8).
5. Do NOT connect to a power source yet! Connect the black power cord to the contacts
#8 & #10 (110 V) or #8 & #9 (220V). It does not matter which color wire is connected to the
contacts. Screw in tight with a Phillips head screwdriver. (Note – If in the U.S. (or a country
that uses Type A or B plugs/sockets), connect the included plug adapter to the power cord).
6. If using a pump, valve, etc., connect a relay cord (not included) to contacts #13 and #14 for a
normally open position OR to contacts #12 and #13 for a normally closed position.
7. Connect the gray sensor cable by attaching the blue wire to contact #1, the red to #2, the
white to #3 and the black to #4.
8. Align the pins of the sensor to the cable and attach. Screw the tightening ring closed.
9. Insert the sensor electrode into a female ½” NPTF threaded tting. Attach to your water source.
10. To DISCONNECT the audible alarm, disconnect the blue wire from contacts #5 and #11.
11. To transmit the TDS data to a PLC via the 4-20mA output signal, connect a cable (not
included) from contacts #6 (positive) & 7 (negative) to a PLC or other device.
12. Plug the power cord into an electrical outlet. The controller does not have a power switch
and will automatically power on when the power is connected.
WARRANTY
ONE YEAR LIMITED WARRANTY
The PSC-154, including both the controller and sensor, is warranted by HM Digital, Inc.
("the Company") to the purchaser against defective materials and workmanship for
one (1) year from the date of purchase.
What is covered: Repair parts and labor, or replacement at the Company's option.
Transportation charges for repaired of new product to be returned to the purchaser.
What is not covered: Transportation charges for the defective product to be sent to
the Company. Any consequential damages, incidental damages, or incidental
expenses, including damages to property. This includes damages from abuse or
improper maintenance such as tampering, wear and tear, water damage, or any other
physical damage. The Company's products are not waterproof and should not be fully
submerged in water. Products with any evidence of such damage will not be repaired
or replaced. See additional note below.
How to obtain warranty performance: Attach to the product your name, address,
description of problem, phone number, and proof of date of purchase, package and
return to:
HM Digital, Inc.
ATTN: Returns
5819 Uplander Way
Culver City, CA 90230
U.S.A.
Implied Warranties: Any implied warranties, including implied warranties of
merchantability and tness for a particular purpose, are limited in duration to ve
years from date of purchase. Some states do not allow limitations on how long an
implied warranty lasts, so the above limitation may not apply to you. To the extent any
provision of this warranty is prohibited by federal and state law and cannot be
preempted, it shall not be applicable. This warranty gives you specic legal rights, and
you may also have other rights, which vary from state to state.
NOTE: Warranties are product-specic. Third-party products and products deemed by
HM Digital as "accessories" are not covered under warranty. Third-party products and
accessories include, but are not limited to, batteries, fuses, mounting brackets, plug
adaptors and ttings.
IMPORTANT: Double-check your contacts prior to connecting the controller to a
power source. Incorrect connections could result in shorting out the unit.
1. The controller will turn on when the power cord is plugged into an electrical outlet.
2. Open the cover on the front of the controller by gently pulling down.
3. To change the temperature mode, quickly press the ‘
oC/o
F’ button. This will toggle the
temperature between Fahrenheit and Celsius.
4. To change the measurement between TDS and EC, press and hold the MODE button. This will
toggle between ppm and μS.
5. To turn o the controller, unplug it from the electrical outlet.
Setting the Control Set Point
1. To set the control set point (to activate a device via the relay), press the SET button once. The
temperature reading will switch to a ashing “SET.”
2. Press the UP or DOWN buttons until the desired set point is reached. Pressing once will advance
the reading by a single digit. Holding down the button will advance the reading quickly.
3. Press the SET button again. This will save the set point to memory.
4. If the TDS/EC level reaches the saved set point, the controller will switch the contacts from the
normal position (either normally open or normally closed), thereby operating the pump,
solenoid valve, or other device attached to contacts #12 & 13 or #13 & 14.