Hitecsa ECV-SP 1001, ECV-SP 1502, ECV-SP 1602, ECV-SP 2003, ECV-SP 2303 Installation, Operation And Maintenance Manual

Models 1001 1502 1602 2003 2303
01.18 207691 Rev101
ECV-SP
EVAPORATOR UNITS – TAILOR-MADE SOLUTIONS FOR VRF OUTDOOR UNITS
Thank you for trusting in Hitecsa Products. Our company has been offering the market an extended range of specialized units for air conditioning and cooling installations for over 35 years. Our approach is based on efficiency, adaptability, usability and practical solutions. This has been the hallmark of our product catalogue.
The versatility of our factory allows us to contribute solutions, almost tailored to each project’s specifications, in search of a solution to every problem that arises in design and implementation of air conditioning installations.
From all of us at Hiplus Aire Acondicionado, once again, thank you very much.
3
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
INDEX
INTRODUCTION ................................................................................................................................................ 5
CONTENTS ................................................................................................................................................... 5
REGULATIONS AND CERTIFICATIONS ......................................................................................................... 6
SAFETY PRECAUTIONS .................................................................................................................................. 7
TECHNICAL SPECIFICATIONS ........................................................................................................................ 8
OPTIONAL EC MOTOR ................................................................................................................................ 9
TRANSPORT & RECEPTION .......................................................................................................................... 10
INSPECTION AT RECEPTION ................................................................................................................... 10
RIGGING ..................................................................................................................................................... 10
STORAGE ................................................................................................................................................... 10
INSTALLATION ............................................................................................................................................... 11
INSTALLATION LOCATION ........................................................................................................................ 11
UNIT SETTLEMENT .................................................................................................................................... 11
SERVICE AREA .......................................................................................................................................... 11
WATER DRAIN ............................................................................................................................................ 11
AIR DUCTS.................................................................................................................................................. 12
DIMENSIONS .............................................................................................................................................. 13
Centrifugal fan ................................................................................................................................... 13
Radial fan .......................................................................................................................................... 15
REFRIGERATION CONNECTIONS ........................................................................................................... 17
Guide for a proper installation of the refrigeration connections ............................................... 17
OPERATION .................................................................................................................................................... 18
BEFORE START UP ................................................................................................................................... 18
START UP ................................................................................................................................................... 18
INDOOR FAN TRANSMISSION ADJUSTMENT ......................................................................................... 19
OPERATING LIMITS ........................................................................................................................................ 20
MAINTENANCE ............................................................................................................................................... 20
CONSERVATION AND CLEANING ............................................................................................................ 20
FAILURES ................................................................................................................................................... 20
FAN DOES NOT START................................................................................................................... 20
LUBRICANT ................................................................................................................................................ 21
REFRIGERANT CHARGE ........................................................................................................................... 21
ECV-SP
4
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
FAN WITH EC MOTOR (OPTIONAL) .............................................................................................................. 22
SAFETY INSTRUCTIONS ........................................................................................................................... 22
Intended use ...................................................................................................................................... 22
Improper use ..................................................................................................................................... 22
Explanations of symbols ................................................................................................................... 23
Product safety ................................................................................................................................... 23
Requirements placed on the personnel / due diligence .................................................................... 23
Working on device ............................................................................................................................. 23
Modifications / interventions in the device ........................................................................................ 25
DIAGNOSIS / FAULTS ................................................................................................................................ 26
Trouble shooting ................................................................................................................................ 26
Status Out with flash code ................................................................................................................ 27
Rotation caused by an air flow in false direction ............................................................................... 28
MAINTENANCE AND REPAIRS ................................................................................................................. 28
CLEANING .................................................................................................................................................. 29
APPENDIX: SAFETY DATA R-410A .............................................................................................................. 30
ECV-SP
5
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
INTRODUCTION
CONTENTS
Purpose of this Manual
This manual and any other instructive document attached as refrigeration lines design, electrical diagrams, etc. have been written to allow a correct installation, commissioning and maintenance of the unit. Therefore it is essential to read the instructions with due attention. Verify that all the necessary information for the correct installation of the system is included in the manuals supplied with this unit and/or the rest of the indoor units, accessories, etc. Otherwise, the manufacturer declines any responsibility for any damage to persons, animals or things, as a result of improper use of the unit and/or failure to observe these instructions.
Preservation Manual
This manual and the electric diagram of the unit must be retained and remain available to the operator for any further consultation.
Updating the Data
The continuous improvement in design and performance to which we are committed gives us the right to modify the specifications of our products without prior notice.
Electrical Network
Check that the electrical network features are in accordance to data shown in the data nameplate of the unit.
Local Safety Regulations
Observe and analyze all possible causes of accidents that may arise in the place or places of installation of the units, check means and tools to use, etc. It is not possible to anticipate each and every one of the potential circumstances of danger in this manual. Respect the valid local security standards during installation.
Principles of Security on Installation
The unit is designed and built in a way that does not pose a risk to the health and safety of people. Appropriate solutions for the project have been adopted to eliminate the possible causes of risk in the installation.
Packaging and Replacement of Equipment
The material of the package (plastic bags, insulating materials, nails, etc.) is a potential source of danger. Consequently, it should be kept out of the reach of children and properly recycled according to the valid local safety regulations. This product should not be mixed with household waste at the end of its life. Due to the refrigerant, oil and other components contained in this product, it must be dismantled by professional installers in accordance with current regulations.
Utilization
The unit will be used only for the reason it has been conceived. Any other use does not imply any kind of compromise or link for the manufacturer.
Incorrect Operation
In case of breakdowns or operation faults, turn off unit.
6
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
INTRODUCTION
CONTENTS
Periodic Inspections and Maintenance
Carry out periodic inspections to detect possible damaged or broken pieces. If they are not repaired it could cause damage to people or stuff. Before executing any maintenance operation, cut off the unit power supply.
All operations should be carried out in accordance with local safety regulations.
Repairs
The reparations should be always and exclusively realized for trained personal authorized by the manufacturer using original spares. The safeties of the unit could be affected due to the failure to comply with these warnings.
Modifications
The manufacturer will not respond to the warranty and to the possible damages of the unit in case of electrical and/or mechanical modifications. The unauthorized manipulation, reparation or modification of the unit will automatically invalidate the warranty.
Refrigerant
This product is hermetically sealed and contains R-410A which is a HFC fluorinated greenhouse gas.
REGULATIONS AND CERTIFICATIONS
ISO 9001:2008 CERTIFICATION: HIPLUS AIRE ACONDICIONADO S.L., trying always to find the maximum satisfaction
of costumers, has obtained the ISO 9001:2008 Quality System referred to its production activity. This will result in a continuous determination to improve quality and reliability of all our products; commercial activities, design, raw materials, production and after-sales service, are the means to reach our goal.
CE MARKING: Our machines have got the CE mark, in conformity with the essential requirements of the applicable EC directives and their last modifications as well as with the national legislation of each country.
EUROVENT CERTIFICATION: HITECSA participates in the EUROVENT Certification program. Check certified products on the web.
7
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
SAFETY PRECAUTIONS
DANGER
• In case of folding electrical panels, before folding them up in order to access to the interior of the machine, it is MANDATORY to disconnect the power supply hose from the electrical voltage, IT MUST ALWAYS BE FREE OF VOLTAGE for this operation.
• Do not touch or adjust the safety elements inside of any unit of the system. Use only original spare parts in repairs and install them in the same position where old parts were placed.
• The installation and maintenance of the air conditioning equipment could be dangerous because the system is
under pressure, some of its elements have high temperatures and include electrical components.
• Do not install the unit in the explosive atmosphere.
ATTENTION!
• Only qualified and trained service staff (technical service) must make the installation, commissioning and carry out
maintenance works. Unqualified staff can only make basic tasks such as cleaning and replacement of filters, etc.
• Prevent access to children so they cannot play with the appliances.
• In every visit, all precautions must be taken into account: those recommended in the installation, operation and
maintenance instructions, as well as the ones indicated in labels of the unit. Do not forget to strictly follow any other safety precautions. .
• DO NOT introduce objects into the air inlets or outlets that can be drawn into the fan, people, etc.
• Use safety glasses, work gloves and any other safety accessory necessary.
• For brazing operations use a quenching cloth and take precautions to have at close distance a fire extinguisher.
• This product contains fluorinated greenhouse gases, its leakage can cause displacement of air and cause insufficient
oxygen to breath.
• All safety recommendations must be followed.
Before starting installation, service or maintenance, turn off the main power switch in order to avoid electrical shock that may cause personal damages.
WARNING!
In case if the existance of water tanks with ELECTRIC HEATERS.
Before starting the equipment, make sure that the water tank is completely full and that the installation is
perfectly drained of air.
WARNING!
8
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
TECHNICAL SPECIFICATIONS
MODEL
1001
1502
1602
2003
2303
POWER SUPPLY
Voltage
V / f / Hz
400 / III / 50
HEAT EXCHANGER COIL
Type
Aluminium fins and copper tubing
Number of cooling circuits
1 1 2 2 2 3
3
Refrigerant
(1)
R-410 (50% HFC32 + 50% HFC125)
GWP
(2)
2088
Installed Expansion Kit
(3)
EXV-8.0 E1
EXV-10.0 E1
2 x EXV-8.0
E1
EXV-8.0 E1 + EXV-10.0 E1
2 x EXV-10.0
E1
3x EXV-8.0
E1
3 x EXV-10.0 E1
Cooling capacity
kW
20
26
40
46
50
60
73
Heat capacity
kW
23
28
45
50
52
65
81
Volume
l
3,48
4,63
3,23
3,46
4,62
4,28
3,15
4,03
Volume min
l
2,92
3,89
2,89
2,92
3,89
3,89
2,92
3,89
Volume max
l
3,89
4,76
3,89
3,89
4,76
4,76
3,89
4,76
FAN
Type
Centrifugal, double suction
Model
12/9 G2L
12/9 G2L
12/12 G2L
12/12 G2L
12/12 G2L
15/11G2L
15/11G2L
Rated air flow
m3/h
6200
6300
9000
9000
11200
12000
13000
Available static pressure
Pa
150
150
200
200
200
200
200
Motor power
KW
1,1
1,1
2,2
2,2
3,0
3,0
4,0
Speed
r.p.m.
789
809
914
930
996
740
765
ELECTRICAL DATA (for a fan)
Rated motor power
kW
1,1
1,1
2,2
2,2
3,0
3,0
3,0
Maximum current (at 400V)
A
2,4
2,4
4,6
4,6
6,2
6,2
6,2
Total absorved power
kW
0,6
0,7
1,3
1,4
2,1
1,9
2,2
Total sound power (Lw)
dBA
81
81,5
84,5
84,5
88
83,5
85
DIMENSIONS & WEIGHT
Length
mm
1700
1700
2000
2000
2000
2600
2600
Width
mm
870
870
939
939
939
980
980
Height
mm
650
650
747
747
747
752
752
Weight
Kg
211
211
272
272
272
333
333
1. Mixture of greenhouse gases for which the machine has been designed. The load will depend on the external unit / units with which it is connected.
2. GWP: Global Warming Potential (GWP) of kg of greenhouse gas relative to 1 kg of CO2, calculated in terms of 100-year warming potential.
3. This Expansion Kit, as well as all other technical features, is optimized for HITACHI VRF units. The other Manufacturers, may require the installation of its own Expansion kits, as well as other volumes of Coils, Air Speeds, etc. Consult with HITECSA
9
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
TECHNICAL SPECIFICATIONS
OPTIONAL EC MOTOR
MODEL
1001
1502
1602
2003
2303
Type
RADIAL with EC motor (Type Plug-Fan)
Number / Size
- / mm
2 / 400
2 / 400
2 / 450
2 / 450
2 / 450
2 / 450
2 / 450
Coil width
mm
65
87
87
108
65
87
108
ELECTRICAL DATA (for a fan)
Power supply
V / ~ / Hz
400V / 3 Phases / 50Hz
Rated motor power (1 Fan)
kW
2,4
2,4
2,0
2,0
2,0
2,0
3,6
Maximum current (1 fan at 400V)
A
3,7
3,7
3,2
3,2
3,2
3,2
5,6
RATED OPERATING CONDITIONS
Nominal air flow
m3/h
6200
6300
9000
9000
11200
12000
13000
Available static pressure
Pa
75
75
75
75
100
100
100
Total absorved power
kW
0,40
0,42
0,68
0,69
1,22
1,20
1,52
Speed
rpm
1063
1088
1074
1078
1327
1354
1435
Potencia sonora Total (Lw)
dBA
72
72
76
76
81
83
86
VALORES LÍMITES DE FUNCIONAMIENTO
Maximum available pressure
Pa
1150
1150
850
850
710
700
1075
Maximum air flow
m3/h
16000
15800
17350
17300
17250
17900
22340
Maximum speed
r.p.m.
2400
2400
1880
1880
1880
1880
2260
Maximum sound power
dBA
92
92
86
86
86
87
93
Sound power at 400Pa
dBA
77
77
81
81
83
84
87
10
01.18 207691 Rev101
ECV-SP
AUTONOMOUS UNITS FOR OUTDOOR UNITS
AIR-AIR
TRANSPORT & RECEPTION
INSPECTION AT RECEPTION
It is advisable to examine the equipment carefully at the time of its reception.  Check that the equipment has not been damaged during transport and has been supplied complete with all parts
specified in the order and/or with the optional specified in the order. If this is not the case contact the transport company immediately. (First 48h)
Verify the correct voltage of the nameplate and make sure it is in accordance with local power supply.  In case of any flaw or anomaly detected, please contact HITECSA.
RIGGING
Before moving the unit, make sure that all panels are well fixed.  Raise and set down the equipment carefully.  Do not tilt the unit more than 15 degrees during transportation. (Fig. 1) (Fig. 2)  Always transport the unit in its original packaging to the place of installation.  All units come with a particular rigging diagram of that model, similar to the one shown below. Be sure to hoist
the machine through the points indicated in the diagram.
Make sure that the unit is balanced, stable and without any deformations when it is lifted.
STORAGE
If the equipment is going to be stored before the installation, please follow the instructions below in order to avoid damages, corrosion or deterioration:
Move it carefully. Do not place the machine in places exposed to ambient temperature above 50ºC and preferably keep the unit away
from direct sunlight.
Avoid placing the unit with plastic wrapping protection under the sun, as the pressure of the circuits could assume
values that could lead to the intervention of the safety valves. In addition, when cooling, water condensation occurs inside the machine and the plastic wrap.
Avoid placing other objects on top of the unit (unless it is done within the limits of the overlap planes indicated on the
packaging, etc. Follow these indications).
Avoid prolonged storage, before installation, water inlet, dust and objects in general due to invasion or biological,
meteorological and/or human inclemencies.
Minimum storage temperature: -10ºC Maximum relative humidity: 90%.
Fig. 1
Fig. 2