CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
1
Installation, operation and maintenance instructions
CCHA / ECHA – Cooling Only
CCHBA / ECHBA – Heat Pump
SPLIT HORIZONTAL UNITS AIR-AIR
Page 2
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
2
CONTENTS
INTRODUCTION
................................................................................
3
SAFETY PRECAUTIONS
................................................................................
4
RECEPTION
................................................................................
5
LOCATION INSTALLATION
................................................................................
8
START UP
................................................................................
10
TECHNICAL DATA
................................................................................
14
DIMENSIONS
................................................................................
16
REFRIGERANT CHARGE
................................................................................
22
REGULATION
................................................................................
27
MAINTENANCE
................................................................................
23
Page 3
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
3
INTRODUCTION
The contents of this manual are designed to assure the correct installation, adjustment and maintenance of the unit, therefore:
Read the instructions with due care and attention.
The appliance must be installed, tested and serviced by properly qualified staff licensed in
accordance with the established legislation.
The manufacturer declines all liability and warranty coverage is automatically waived, if electrical and/or mechanical modifications to the unit. Tampering and unauthorized repairs or modifications to the unit will automatically void the warranty.
Observe the safety regulations in force at the time of installation.
Make sure that the characteristics of the mains network conform to the data on the serial
number plate placed on the unit.
Keep this manual and the wiring diagram with care and make sure that they are available for consultation by the operator whenever necessary.
Packing materials (plastic wrappings, expanded polystyrene, etc) are potentially hazardous and must be kept out of reach of children. Recycle packing materials in accordance with local legislation.
The units must be used only for the purpose for which they are designed. The manufacturer bears no responsibility in the case of applications other than the specified use.
Disconnect the unit in the event of breakdowns or malfunctions.
If repairs are necessary, use only HITECSA approved service centres and always insist on
original spare parts. The use of non-original parts and/or unauthorized service centres may result in unsafe operation of the unit.
REGULATIONS AND CERTIFICATIONS
ISO 9001:2008 certification: HITECSA AIRE ACONDICIONADO S.L.U., trying always to find the
customer satisfaction, has obtained the ISO 9001:2008 Quality System referred to its production activity. This will result in a continuous determination to improve quality and reliability of all our products. Commercial activities, design, raw materials, production and after-sales service, are the means to reach our goal.
CE marking: our machines have got the CE mark, in conformity with the essential requirements of the applicable EC directives and their last modifications as well as with the national legislation of each country.
Page 4
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
4
SAFETY PRECAUTIONS
Installation and maintenance of air conditioning equipment can be dangerous because the system is under pressure, because some of its elements have high temperatures and include electrical components.
Only qualified and trained service staff should install, commission and carry out maintenance works. Unqualified staff should only carry out basic tasks such as cleaning and replacement of filters, etc.
In every visit, all precautions should be taken into account: those recommended in the Installation, operation and maintenance instructions, as well as the ones indicated in labels of the unit. Do not forget to strictly follow any other safety codes.
Use safety glasses, work gloves and any other safety accessory necessary.
For brazing operations use a quenching cloth and have at close distance a fire extinguisher.
WARNING!
Before starting installation, service or maintenance, turn off the main power switch in order to
avoid electrical shock that may cause personal damages.
When repairing the unit, use only original spare parts and install them properly in the same position where old parts were placed.
These units are designed to work with 100% recirculated air. The installation with 100% outdoor air is prohibited. See application limits.
Do not install the unit in explosive atmosphere.
Page 5
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
5
RECEPTION
INSPECTION UPON RECEIPT
Units are delivered with special protective packing; therefore when it arrives, please inspect it carefully to check that no damage has occurred during transport and that the unit has been supplied complete with all parts specified in the order. If any damage is found, immediately file a claim with the transport company.
Verify the correct voltage of the nameplate and make sure it’s in accordance with local power supply.
In case of any flaw or anomaly detected, please contact HITECSA
RIGGING
Before moving the unit, make sure that all panels are well fixed.
Raise and set down the equipment carefully.
Do not tilt the unit more than 15 degrees during transportation.
When lifting the unit, make sure that it’s balanced and stable; bear in mind that the heaviest part is where the compressor is installed.
STORAGE
If the equipment is going to be stored please follow the instructions below in order to avoid damages, corrosion or deterioration:
Keep the unit away from direct sunlight, rain, sand, wind or temperatures above 50ºC
Storage temperature: maximum 50ºC, minimum -10ºC
Maximum humidity: 90%
Page 6
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
6
INSTALLATION LOCATION
Check if the base is able to support the weight of unit during operation.
Reserve a minimum service area according to Fig. 2.
Choose a place free of dust or any other foreign material that could clog or damage the
condenser coil. The location should also be a place that cannot be flooded.
Consult and respect all regulations concerning installation of air conditioning systems.
Check if sound waves do not disturb anyone and put anti-vibration plots if necessary.
SERVICE AREA (mm)
Page 7
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
7
WEIGHT DISTRIBUTION (Kg)
UNIT SETTLEMENT
Make sure that the unit is correctly levelled.
The bed frame should be strong and solid enough to support the weight of the machine.
Verify that the indoor drain is working properly.
Page 8
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
8
BEFORE START UP
Check the following points:
o Wires are well tightened. o Panels are firmly secured with screws. o There are no oil or refrigerant leaks. o The unit is correctly levelled. o There is enough space for service and maintenance. o Drainage is not blocked. o Crankcase heater has been working at least 24 hours prior to the start-up. o Air filters are clean and correctly mounted. o Grilles, air diffusers, air ducts and flexible connections are in good condition. o Electrical power source is in accordance with what is said in the nameplate. o Fans rotate in the right direction.
.
START UP
Start up should be performed by qualified technical people.
Use a start up check list: record inlet and outlet temperatures and pressures, outdoor air
temperature, volts and amps of each compressor and each fan motor, suction and discharge pressure of each compressor.
Use a similar check list for service and maintenance works.
Remember that after 4 hours of operation, it is necessary to clean the filters.
Monitor at least 3 cooling cycle operations.
Page 9
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
9
LEGEND
1. Main power 400/3/50 + neutral or 230/1
2. Earth
3. Time delay fuses or circuit breaker (MCB) curve D
4. Main power switch
5. Indoor fan motor supply 400/3** or 230.1*
6. Electric heating wiring (option)
7. Electric heating supply (option) de ∆ ∆ 400.3 or ∆ 230.1
8. Remote control
OPERATING LIMITS
OUTDOOR UNIT
INDOOR UNIT
Units can operate
at a maximum altitude of
1.500 meters.
For other conditions, please consult.
Page 10
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
10
WARNING!
Before starting installation, service or maintenance, turn off the main power switch in order to
avoid electrical shock that may cause personal damages.
Main power supply of the unit should agree with the data shown on the nameplate. HITECSA will not be held responsible for damages resulted from non observance of the above.
Always use the wiring diagram sent with the unit to make electrical connections.
Make sure that the crankcase heater has been working at least 24 hours prior to the start up of
the unit.
Current supply should be within 10% of Volts and Amperes indicated on the unit nameplate.
Do not operate the unit at different current from that shown on the unit nameplate.
The installer should put line protection elements in compliance with current legislation.
The interconnecting wires should be protected with a tube or put inside a groove channel.
ELECTRICAL DATA
Alimentación V (50Hz) 230.I 230.I 400.III 400.III 400.III 400.III Potencia total absorbida (1)
kW
2,8 3,3 4,2 5,3 5,6
7,0
Corriente total absorbida (1)
A
15 20 12 15 15
15
Potencia total absorbida (2)
kW
3,5 4,1 5,3 6,9 7,1
9,23
Corriente total absorbida (2)
A
16 19 13 17 17
17
Potencia total absorbida (3)
kW
2,6 3,2 3,7 4,8 4,9
6,2
Corriente total absorbida (3)
A
13 19 12 15 15
13
Potencia total absorbida (4)
kW
3,4 4,3 4,8 5,8 6,5
8,5
Corriente total absorbida (4)
A
15 19 13 16 16
15
Corriente de arranque
A
63 96 43 63 63
66
Magnetotérmicos curva D *
A
20 20 15 15 20
20
Sección min. cable (227 CEI 53)
mm
2
2,5 4,0 2,5 2,5 2,5
2,5
Alimentación
V (50Hz)
400.3
400.3
400.3
400.3
400.3
400.3
Potencia total absorbida (1)
kW
7,6 8,8 10,7 10,3 13,4
15,7
Corriente total absorbida (1)
A
17 19 20 20 25
32
Potencia total absorbida (2)
kW
10,9 12,0 13,2 13,3 17,0
20,31
Corriente total absorbida (2)
A
19 21 22 22 29
34
Potencia total absorbida (3)
kW
6,8 7,7 10,0 10,1 12,7
15,2
Corriente total absorbida (3)
A
14 17 19 19 23
32
Potencia total absorbida (4)
kW
9,4 10,2 12,4 12,0 16,4
19,46
Corriente total absorbida (4)
A
18 19 21 21 27
33
Corriente de arranque
A
67 96 96 96 96
158
Magnetotérmicos curva D *
A
25 25 25 25 30
40
Sección min. cable (227 CEI 53)
mm
2
4,0 4,0 4,0 4,0 6,0
10
801 1001 1201
CCHBA / ECHBA STD
CCHA / ECHA STD
701 721 751
371 401
CCHBA / ECHBA STD
501
CCHA / ECHA STD
201 251 351
NOTES:
1.COOLING: Outdoor air temperature 35ºC. Indoor air temperature (WB) 19ºC.
2. COOLING (MAX.) : Outdoor air temperature 46ºC. Indoor air temperature (WB) 21ºC.
3.HEATING: Outdoor air temperature (WB) 6ºC. Indoor air temperature 20ºC.
4. HEATING (MAX.) : Outdoor wet temperature 18ºC. Indoor air temperature 26ºC. * Recommendation to the installer
Page 11
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
11
DRAINAGE
Indoor drainage (of condensate water) has a 3/4” MPT connection.
Condensate drain line diameter should be equal or larger than the unit connection depending
on pipe length and general building configuration.
Drainage line should have a minimum inclination of 2% for proper water evacuation.
When drainage line is exposed to temperatures below 0ºC, it is necessary to provide thermal
insulation or electrical heating wire to avoid water freezing and tube damages
It is advisable to install a trap with proper dimensions.
AIR DUCTS
- Air duct dimensions will be determined according to the airflow and available static pressure.
- Ducts must be designed by qualified technical people.
- Use ducts made of non-inflammable materials in order to avoid any emission of gas in case of
fire. It is advisable to use metal plate duct with insulation.
- Use flexible ducts to connect air ducts into the unit and thus avoid vibration and noise transmission.
Page 12
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
12
ADJUSTMENT OF FAN TRANSMISSION
- Adjust transmission so that indoor fan-motor reaches its nominal value..
-
If consumption is lower than the nominal value, the airflow is insufficient.
To change fan speed:
1. Remove the belt and slide the motor over the channel.
2. Loosen setscrews and turn the mobile flap around, depending on your needs.
3. Tight setscrews.
4. Put the belt back in the pulley’s channel.
5. Tight the belt using a tension adjuster screw.
LEGEND:
1.- Motor.
2.- Motor pulley.
3.- Belt.
4.- Fan pulley.
5.- Tensor adjustment screw.
6.- Setscrew.
7.- Mobile flap
8.- Fix flap.
7
6
8
3
1
5
4
2
Polea Pulley abi ertas
Fij o Vari able Correa
kW A
CCHBA 751 X 1,5 3,6 150 E25 1A 75/100 E 24 1A A-45 0
CCHBA 801 X 1,5 3,6 150 E25 1A 100/125 E 24 1A A-45 2
CCHBA 1001 X 2,2 4,7 150 E25 1A 100/125 E 28 1A A-46 1
CCHBA 1201 X 4,0 9,2 160 E30 2A 100/125 E 28 2A A-46 2
ECHBA 501 X 0,550 1,59 150 E20 1A 100/125 E19 1A A-42 0
ECHBA 701 X 0,735 2,0 150 E25 1A 75/100 E19 1A A-43 1
ECHBA 721 X 0,735 2,0 150 E25 1A 75/100 E19 1A A-43 1
ECHBA 751 X 0,735 2,0 150 E25 1A 75/100 E19 1A A-43 1
ECHBA 801 X 0,735 2,0 150 E25 1A 75/100 E19 1A A-43 0
ECHBA 1001 X 1,5 3,0 160 E25 1A 100/125 E24 1A A-45 2
ECHBA 1201 X 2,2 4,8 160 E25 2A 100/125 E28 2A A-46 2
MODELO
Exterior
Nominal
Interior
Page 13
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
13
To line up motor and fan pulleys:
1. Loosen setscrews from the fan pulley.
2. Slide the fan pulley down the axe and line up with the motor, using a ruler to make sure
that it’s in parallel with the belt.
3. Tight the fan pulley using a tension adjuster crew.
COMPRESSOR LUBRICANT
- Compressors with R410a refrigerant use synthetic polyester oil, each manufacturer using a specific oil for his product.
- The system must not remain open to the atmosphere more than 15 minutes.
- Due to its hygroscopic qualities, you must be very careful during manipulation: when synthetic
oils mix up with mineral oil, they deteriorate causing obstructions and even the breakdown of the compressor. Do not mix them under any circumstance.
WRONG ALIGNMENT
90
WRONG
WRONG
90
RIGHT POSITION OF THE RULER
90
Page 14
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
14
TECHNICAL DATA
POTENCIAS
Potencia frigorífica (1) kW 5,6 7,4 9,7 11,6 12,4 14,1 Potencia calorífica (2) kW 6,1 8,2 9,8 12,0 13,8 16,4
COMPRESOR
Tipo Rotativo Rotativo Rotativo Scroll Scroll Scroll Voltaje V 230-1 230-1 400-3 400-3 400-3 400-3 Carga de refrigerante R410A Kg 2,2 2,7 3,8 4,0 4,1 5,0
INTERCAMBIADOR INTERIOR
Tipo Área frontal m2 0,20 0,25 0,25 0,31 0,31 0,31 Paso aletas mm 2,1 2,1 1,8 2,1 2,1 2,1 Diametro tubos " 3/8 3/8 3/8 3/8 3/8 3/8
INTERCAMBIADOR EXTERIOR
Tipo Área frontal m2 0,22 0,292 0,36 0,4 0,4 0,4 Paso aletas mm 1,8 1,8 1,8 1,8 1,8 1,8 Diametro tubos " 3/8 3/8 3/8 3/8 3/8 3/8
VENTILADOR INTERIOR
Tipo Modelo 9/7 DD 9/9 DD 10/10 DD 10/10 DD 10/10 DD 10/10 SS Potencia motor kW 0,120 0,250 0,250 0,373 0,373 0,550 Voltaje V 230-1 230-1 230-1 230-1 230-1 400-3 Corriente absorbida nominal A 1,6 1,5 1,9 2,6 2,7 1,6
VENTILADOR EXTERIOR
Tipo Modelo 9/9 DD 10/10 DD 10/10 DD 12/9 DD 12/9 DD 12/9 DD Potencia motor kW 0,37 0,37 0,44 0,55 0,55 1,10 Voltaje V 230-1 230-1 230-1 230-1 230-1 400-3 Corriente absorbida nominal A 4,0 4,0 4,3 4,8 4,7 3,0
501
Batería de aletas de aluminio y tubos de cobre
Batería de aletas de aluminio y tubos de cobre
Centrífugo de doble aspiración
Centrífugo de doble aspiración
CCHA / ECHA
201 371251 351 401
CCHBA / ECHBA
(1)
COOLING
:
Outdoor air temperature
: 35 °C.
Indoor air temperature (WB)
: 19 °C.
(2)
HEATING
:
Outdoor air temperature (WB)
.: 6 °C.
Indoor air temperature
: 20 °C.
Page 15
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
15
TECHNICAL DATA
POTENCIAS
Potencia frigorífica (1) kW 17,2 18,5 20,8 21,9 28,4 33,5 Potencia calorífica (2) kW 18,9 20,4 21,9 24,6 29,8 37,2
COMPRESOR
Tipo Voltaje V 400-3 400-3 400-3 400-3 400-3 400-3 Carga de refrigerante R410A Kg 5,7 5,7 5,9 6,7 9,0 9,5
INTERCAMBIADOR INTERIOR
Tipo Área frontal m2 0,47 0,47 0,47 0,54 0,65 0,77 Paso aletas mm 1,8 1,8 1,8 1,8 1,8 1,8 Diametro tubos " 3/8 3/8 3/8 3/8 3/8 3/8
INTERCAMBIADOR EXTERIOR
Tipo Área frontal m2 0,605 0,605 0,605 0,605 0,9 1,19 Paso aletas mm 1,8 1,8 1,8 1,8 1,8 1,8 Diametro tubos " 3/8 3/8 3/8 3/8 3/8 3/8
VENTILADOR INTERIOR
Tipo Modelo 12/9 SS 12/9 SS 12/9 SS 12/9 SS 12/12 SS 15/15 SS Potencia motor kW 0,735 0,735 0,735 0,735 1,500 2,200 Voltaje V 400-3 400-3 400-3 400-3 400-3 400-3 Corriente absorbida nominal A 2,0 2,0 2,1 2,3 3,0 4,8
VENTILADOR EXTERIOR
Tipo Modelo 12/12 DD 12/12 DD 12/12 SS 12/12 SS 12/12 SS 15/15 SS Potencia motor kW 1,10 1,10 1,50 1,50 2,20 4,00 Voltaje V 400-3 400-3 400-3 400-3 400-3 400-3 Corriente absorbida nominal A 3,5 3,5 3,4 3,6 4,7 9,2
1201
Batería de aletas de aluminio y tubos de cobre
Batería de aletas de aluminio y tubos de cobre
Scroll
Centrífugo de doble aspiración
Centrífugo de doble aspiración
CCHA / ECHA
701 801721 751 1001
CCHBA / ECHBA
(1)
COOLING
:
Outdoor air temperature
: 35 °C.
Indoor air temperature (WB)
: 19 °C.
(2)
HEATING
:
Outdoor air temperature (WB)
.: 6 °C.
Indoor
air temperature
: 20 °C.
Page 16
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
16
DIMENSIONS
CCHA – CCHBA 351
ECHA – ECHBA 351
Page 17
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
17
CCHA – CCHBA 371 – 401 – 501
ECHA – ECHBA 371 – 401 – 501
Page 18
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
18
CCHA – CCHBA 701 – 721 – 751 - 801
ECHA – ECHBA 701 – 721 – 751 - 801
Page 19
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
19
REFRIGERANT LINES
REFRIGERANT CIRCUIT
Split systems demand a correct disposition of refrigerant piping and a correct connection between both indoor and outdoor units. Line selection should be done according to the following criteria:
- Pressure drop of the line
- Circulation speed of the refrigerant
- Refrigerant mass
DISCHARGE LINE
In heat pump operation, the gas line works as discharge line.
WARNING!!!
When working with the machines in operation, discharge line temperature is very HIGH and
could result in burns.
TRAZADO DE LÍNEAS
1. When indoor unit is at a lower level than outdoor unit: It is not essential to install traps in the vertical line. However, it could be convenient to install some every 6 to 9 meters in order to help oil return.
A –
INDOOR UNIT
B –
OUTDOOR UNIT
GAS LINE
LIQUID LINE
B
A
Page 20
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
20
2. When indoor unit is at the same level as outdoor unit: rise the suction line to a higher level than the exchanger in order to avoid refrigerant return into the compressor.
3. When indoor unit is at a higher level than outdoor unit.
LÍNEA DE GAS
LÍNEA DE LÍQUIDO
A B
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
LÍNEA DE GAS
LÍNEA DE LÍQUIDO
LÍNEA DE GAS
LÍNEA DE LÍQUIDO LÍNEA DE LÍQUIDO
A B
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
A B
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
B
A
LÍNEA DE GAS
LÍNEA DE LÍQUIDO
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
BAB
A
LÍNEA DE GAS
LÍNEA DE LÍQUIDO
LÍNEA DE GAS
LÍNEA DE LÍQUIDO LÍNEA DE LÍQUIDO
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
A – UNIDAD INTERIOR
B – UNIDAD EXTERIOR
Page 21
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
21
NOTES :
- Refrigerant lines should be as short and straight as possible. Use recommended diameters
to reduce quantity of refrigerant in the system.
- Fasten the tubes to fixed elements by means of braces to avoid vibration.
- Carry out welding works in dry nitrogen atmosphere inside the line to be welded -USE A
BOTTLE WITH PRESSURE REGULATOR- to avoid the appearance of oxide and to expel rest of polluting material or humidity. Use rods with a minimum 15% of silver alloy.
- Insulate suction line in order to avoid condensation. Liquid line will be insulated only when
exposed to high temperatures (solar radiation, etc.)
- Horizontal segment of suction line: 4% pitch towards the compressor.
- In addition to refrigerant, sometimes it’s necessary to add oil. For more than 25 meters,
add 30 grams.
- When height difference is more than 30 meters, it may be necessary to install an oil
separator on discharge line.
- If liquid line is descendant and there is a considerable height difference, you have to
compensate the excess pressure before the expansion.
- If liquid line is ascendant and there is a considerable height difference, the formation of gas
refrigerant before the expansion must be avoided.
- If you should not find the chosen pipe diameter, you can use the immediately lower
diameter. The system will function normally only with a slight reduction of performance.
Page 22
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
22
REFRIGERANT CHARGE
WARNING!!!
It is forbidden by law to expel refrigerant into the atmosphere; therefore, it is necessary to
recover all the refrigerant and to avoid leaks.
-
Units CCHA-CCHBA y ECHA-ECHBA are supplied with nitrogen charge. Before proceeding to any welding work, it’s necessary to remove this charge out of the interconnection lines. Once you have finished, make the vacuum and charge with the right amount of refrigerant.
WARNING!!!
Never use oxygen to carry out leak tests. Oxygen reacts violently when in contact with oil and
could cause an explosion resulting in damage, personal injuries or even death.
Should it be necessary to add or recover refrigerant, do it always in LIQUID phase, never in gas or vapour phase since this would cause wrong mixing conditions.
Due to its high pressure and quick evaporation, refrigerant R410A cannot be kept in liquid phase inside charge cylinder because bubbles would form, making reading difficult.
WARNING!!!
If it’s necessary to make welding operations, you must fill the circuit with dry nitrogen.
Combustion of R410a refrigerant generates toxic gases.
Repair immediately any refrigerant leak.
Never overcharge the system.
Never use compressor as a vacuum pump.
If symptoms of refrigerant loss appear during operation, it’s necessary to carry out a leak test.
Leak detectors usually employed with CFC and HCFC cannot be used with R410a, due to chlorine in its composition. A leak detector for R134a may be used but the sensibility will be lower (when sensibility is 1 for R134a, it falls to 0,6 for R410a).
To find small leaks, you will need a detector for HCF. Sensibility for R410A is approx. 23 grams per year.
If a gas leak is found, it will be necessary to remove and completely recover the refrigerant charge. Pressurize the system with dry nitrogen. If no leakage is detected, then do the vacuum and charge again with refrigerant.
Page 23
CCHA/ECHA – CCHBA/ECHBA Installation, operation and maintenance instructions
23
MAINTENANCE
WARNING!!!
Before performing any service or maintenance operation, turn off the main power switch of the
system to avoid any personal injuries. Block the power switch so that nobody other than a
qualified technician can switch on electrical power.
It is advisable to do maintenance works every 1.000 operating hours as well as at the
beginning of each cooling season.
Coils: at least once a year, clean condenser coils with water and detergent, then dry with
air at a pressure of 600 kPa. Never clean with wire brush.
Fans and motors: adjust transmission belt at least twice during the first month of operation
and then check every 1.000 hours. Fan and motors do not need additional lubrication.
Drainage system: verify condition and good operation of the drainage tray. Make sure that
holes at the base of the unit are not blocked so that evacuation can be properly done.
Refrigeration circuit: check for oil refrigerant leaks, noises or system’s vibrations. Take
measurements of temperatures and pressures of components and record them on the maintenance form.
Electrical circuit: make sure that all electrical connections -wires, contactors, terminals- are properly tight. Record the measurements (volts and amperes) of each compressor and fan motor. Verify the starting current. Check the good operation of all relays, pressostats and phase sequence relay of Scroll compressor.
Air filters: clean filters after the first 4 operating hours and then every 3 months (or even
before). Wash filters in water with detergent, rinse thoroughly and let dry.