PACKAGED AIR-AIR ─ SPLIT HORIZONTAL INVERTER UNITS
Models: 301
HEAT PUMP
Installation, Operation and Maintenance Manual
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
Cooling Capacities: from 1.3 kW to 8.3 kW
Heating Capacities: from 1.2 kW to 8.1 kW
Page 2
Thank you for trusting the Hitecsa Products. Our company has been offering the market an extended range of specialized units for
air conditioning and cooling installations for over 35 years. Our approach is based on efficiency, adaptability, usability and practical
solutions. This has been the hallmark of our product catalogue.
The versatility of our factory allows us to contribute solutions, almost tailored to each project’s specifications, in search of a solution
to every problem that arises in design and implementation of air conditioning installations.
From all of us at Hiplus Aire Acondicionado, once again, thank you very much.
APPENDIX: SAFETY DATA R410A .................................................................................... 22
3
Page 4
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
This manual and the instruction documents of refrigeration lines, wiring diagrams and any other attached
documents, have been written to allow a correct installation, set up and maintenance of the unit.
Therefore it is essential to read the instructions with due attention. Verify all the necessary information for
the correct installation of the system is included in the manuals supplied with this unit and / or the rest of
the indoor units, accessories, etc. Otherwise, the manufacturer declines any responsibility for any
damage to persons or things, as a result of improper use of the unit and/or failure to observe these
instructions.
Check that electrical network features are in accordance to data shown in the data nameplate of the unit.
The packaging material (plastic bags, insulating materials, nails, etc.) is a potential source of danger and
should be kept out of the reach of children and properly recycled according to local safety regulations.
This product should not be mixed with household waste at the end of its life. Due to the refrigerant, oil
and other components contained in this product, it must be dismantled by professional installers in
accordance with current regulations.
Carry out periodic inspections to detect possible damaged or broken pieces. If they are not repaired it
could result in damage to people or stuff. Before executing any maintenance operation, cut off the unit
power supply.
All operations must be carried out in accordance with local safety regulations.
INTRODUCTION
Purpose of the Manual
Preservation Manual
This manual and the electric diagram of the unit must be retained and remain available to the operator for any further
consultation.
Updating the Data
The continuous improvement in design and performance to which we are committed gives us the right to modify the
specifications of our products without prior notice.
Electrical Network
Local Safety Regulations
Observe and analyze all possible causes of accidents that may arise in the place or places of installation of the units,
check means and tools to use, etc. It is not possible to anticipate each and every one of the potential circumstances of
danger in this manual. Respect the local security standards during installation.
Principles of Security on Installation
The unit is designed and built in a way that does not pose a risk to the health and safety of people. Appropriate project
solutions have been adopted to eliminate the possible causes of risk in the installation.
Packaging and Replacement of Equipment
Use
The unit will be used only for the reason has been conceived. Any other use does not imply any kind of compromise or
link for the manufacturer.
Incorrect Operation
In case of breakdowns or operation faults, turn off unit.
Periodic Inspections and Maintenance
4
Page 5
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
Reparations should be always realized for trained personal authorized by the manufacturer using original
spares. Failure to comply with these warnings could affect the safety features of the unit.
INTRODUCTION
Repairs
Modifications
All manufacturer responsibility is declined when the warranty has been expired in case of electrical and/or mechanical
modifications. Alterations in general not expressly allowed and not respecting what is instructed here, they cause the
warranty expiration.
Refrigerant
This product is hermetically sealed and contains R-410A which is a HFC fluorinated greenhouse gas.
REGULATIONS AND CERTIFICATIONS
ISO 9001:2015 CERTIFICATION: HILPUS AIRE ACONDICIONADO S.L., trying always to find the customer satisfaction,
has obtained the ISO 9001:2015 Quality System referred to its production activity. This will results in a continuous
determination to improve quality and reliability of all our products; commercial activities, design, raw materials, production
and after-sales service, are the means to reach our goal.
CE MARKING: Our machines have got the CE mark, in conformity with the essential requirements of the applicable EC
directives and their last modifications as well as with the national legislation of each country.
5
Page 6
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
Before starting installation, service or maintenance, turn off the main power switch in
order to avoid electrical shock that may cause personal damages.
SAFETY PRECAUTIONS
Installation and maintenance of air conditioning equipment can be dangerous because the system is under pressure,
because some of its elements have high temperatures and include electrical components.
Only qualified and trained service staff should install, commission and carry out maintenance works. Unqualified staff
should only carry out basic tasks such as cleaning and replacement of filters, etc.
In every visit, all precautions should be taken into account: those recommended in the Installation, operation and
maintenance instructions, as well as the ones indicated in labels of the unit. Do not forget to strictly follow any other
safety codes.
Use safety glasses, work gloves and any other safety accessory necessary.
For brazing operations use a quenching cloth and have at close distance a fire extinguisher.
When repairing the unit, use only original spare parts and install them properly in the same position where old parts
were placed.
The equipment is designed to work with 100% recirculated air. For installations with external air supply, consult our
commercial department.
Do not install the unit in explosive atmosphere.
6
Page 7
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
RECEPTION
INSPECTION
Units are delivered with special protective packing; therefore when it arrives, please inspect it carefully to check that
no damage has occurred during transport and that the unit has been supplied complete with all parts specified in the
order. If any damage is found, immediately file a claim with the transport company. (first 48h)
Verify the correct voltage of the nameplate and make sure it’s in accordance with local power supply.
In case of any flaw or anomaly detected, please contact HITECSA.
RIGGING
Before moving the unit, make sure that all panels are well fixed.
Raise and set down the equipment carefully.
Do not tilt the unit more than 15 degrees during transportation (Fig. 2).
When lifting the unit, make sure that it’s balanced and stable; bear in mind that the heaviest part is where the
compressor is installed.
STORAGE
If the equipment is going to be stored please follow the instructions below in order to avoid damages, corrosion or
deterioration:
Keep the unit away from direct sunlight, rain, sand, wind or temperatures above 50ºC.
Storage temperature: maximum 50ºC, minimum -10ºC.
Maximum humidity: 90%.
7
Page 8
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
INSTALLATION LOCATION
Check if the base is able to support the weight of unit during operation.
Reserve a minimum service area.
Choose a place free of dust or any other foreign material that could clog or damage the condenser coil. The location
should also be a place that cannot be flooded.
Consult and respect all regulations concerning installation of air conditioning systems.
Install anti-vibration supports to avoid noise transmission.
SERVICE AREA (mm)
CCHIBA 301
CSTIBA 301
8
Page 9
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
CSTIBA
1 2 3 4 TOTAL
301
7 8 8 8 31
CCHIBA
1 2 3 4 TOTAL
301
32
32
28
58
150
CSTIBA 301
CCHIBA 301
WEIGHT DISTRIBUTION (kg)
UNIT SETTLEMENT
Make sure that the unit is correctly levelled.
The bed frame should be strong and solid enough to support the weight of the machine.
Verify that the water drain of the indoor is working properly.
9
Page 10
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
BEFORE START-UP
EVAPORATOR
CONDENSER
6. Switch
Check the following points:
Electrical connections are well tightened.
Panels are firmly secured with screws.
There are no oil or refrigerant leaks.
The unit is correctly leveled.
There is enough space for service and maintenance.
Drainage is not blocked.
If outdoor temperature is under 25ºC, verify the crankcase heater of the compressor.
Air filters are cleaned and correctly mounted.
Grilles, air diffusers, air ducts and flexible connections are in good condition.
Electrical power source is in accordance with what is said in the nameplate.
Fans rotate in the right direction.
START-UP
Start-up should be performed by qualified technical people.
Use a start-up check list: record inlet and outlet temperatures of the indoor coil, volts and amps of each compressor
and fan motor, suction and discharge pressure of each compressor.
Remember that after the first 4 hours of operation, it is necessary to clean the filters.
Monitor at least 3 cooling cycle operations.
Due to the unit has frequency converters for compressor and fans, it’s essential that the differential supply be at
minimum 300 mA to prevent supply cuts caused by the differential switch.
10
1. Power Supply 230/I/50 + T
2. Circuit Breaker
3. Th-Tune Termostat
4. Electrical Panel
5. Comunication Cables
(Shielded and Twisted)
Page 11
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
OUTDOOR AIR
INDOOR AIR
DRY
WET
DRY
WET
COOLING
ºC
ºC
ºC
ºC
Standard
35ºC - 27ºC
19ºC
Minimum
-10ºC
-
20ºC
15ºC
Maximum
50ºC - 32ºC
23ºC
HEATING
ºC
ºC
ºC
ºC
Standard
7ºC
6ºC
20ºC
-
Minimum
-12ºC
-13ºC
15ºC
-
Maximum
24ºC
18ºC
26ºC
-
OPERATION LIMITS
The units can run at a maximum altitude of 1500 m above mean see level with a loss in performance below 3%.
For other conditions, please consult Hitecsa.
These units have been designed to work with 100% of indoor air returned. It is forbidden to design an installation with a
100 % outdoor air returned. See the working limits.
Before starting installation, service or maintenance, turn off the main power switch in
order to avoid electrical shock that may cause personal damages.
Main power supply of the unit should same as the data shown on the nameplate. HITECSA will not be held responsible
for damages resulted from non observance of the above.
Always use the wiring diagram sent with the unit to make electrical connections
Check that the crankcase heater has been working at least 24 hours prior to the start-up of the unit.
Power supply should be within 10% of Volts indicated on the unit nameplate.
Do not operate the unit at different voltage from the one shown on the unit nameplate.
The installer should put line protection elements in compliance with current legislation.
The interconnecting wires should be protected with an electrical duct or put inside a groove channel.
11
Page 12
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
DRAINAGE
Indoor drainage (of condensate water) has a 3/4” gas
connection.
Condensate drainage pipe diameter should be equal or
larger than the unit connection depending on line
length and general building configuration.
Drainage line should have a minimum inclination of 2%
for proper water evacuation.
When drainage line is exposed to temperatures below
0ºC, it is necessary to provide thermal insulation or
electrical heating wire to avoid water freezing and tube
damages.
It is advisable to install a trap with proper dimensions.
AIR DUCTS
Air duct dimensions will be determined according to the airflow and available static pressure.
Ducts must be designed by qualified technical people.
Use ducts made of non-inflammable materials in order to avoid any emission of gas in case of fire. It is advisable to
use metal sheet duct with insulation.
Use flexible ducts to connect air ducts on the unit and thus avoid vibration and noise transmission.
COMPRESSOR LUBRICANT
Compressors with R410a refrigerant uses synthetic lubricant with Ester base, each manufacturer uses specific oil for his
product. The system must not remain open to the atmosphere more than 15 minutes.
Due to oil qualities affect directly the correct work of compressor, you must be very careful during manipulation: Do not mix
the oil with other substances.
12
Page 13
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
CCHIBA
301
CAPACITIES
Rated Cooling Capacity (1)
KW
7.4
Cooling Capacity (20 – 100 – 120 Hz)
KW
1.2 – 7.4 – 8.1
Rated Heating Capacity (2)
KW
7.5
Heating Capacity (20 – 100 – 120 Hz)
KW
1.3 – 7.5 – 8.3
Coeficient EER
>8
SEER
4.6
Class
B
SCOP (Warm Zone)
4.1
Class
A+
Sound Power
dBA
70
REFRIGERANT
Type
R-410A
Global Warming Potential (GWP) (3)
2088
Number of Refrigerant Circuits
1
Frigorific Connection Liquid Line
“
3/8
Frigorific Connection Gas Line
“
1/2
Charge (Include 0 m of Lines) (4)
Kg
2.7
COMPRESSOR
Type
BRUSHLESS DC MOTOR
Number
2
Oil type
Ester VG74
Oil Volume
L
0.65
INDOOR HEAT EXCHANGER
Type
Aluminum Fins and Copper Pipes
Frontal Surface
m2
0.372
Fins Size
mm
1.8
Piping Diameter
"
5/16
ELECTRICAL SPECIFCATIONS
Power Supply
V / phases /
Hz
220-240 / I / 50
Electric Connections
mm²
2 x 2.5 + T
Interconnection Between Units
Twisted Pair + Shielded
OUTDOOR FAN
Type
Centrifugal with Double Suction
Model
10/10 DD
Voltage
V
230/1/50
Motor Power
KW
0.55
Transmission
Integrated in Motor
Rated Airflow
m3/h
2600
Maximum Airflow
m3/h
3000
Available Static Pressure
Pa
50
Maximum Speed Fan
R.P.M.
1014
DIMENSIONS AND WEIGHT
Length
mm
1445
Width
mm
825
Height
mm
504
Weight
Kg
150
TECHNICAL DATA
(1) Cooling Rated Conditions: Internal temperature DB: 27ºC, Internal temperatura WB: 19ºC
(2) Heating Rated Conditions: Internal temperature DB: 20ºC
(3) GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2, calculated
in terms of 100-year warming potential.
(4) Just the units which has serial “FLARE” (not from option) are charged with refrigerant, the rest come
pre-charged with dry nitrogen to prevent the emtry of moisture.
13
Page 14
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
CSTIBA
301
CAPACITIES
Rated Cooling Capacity (1)
kW
7.4
Cooling Capacity (20 – 100 – 120
Hz)
kW
1.2 – 7.4 – 8.1
Rated Heating Capacity (2)
kW
7.5
Heating Capacity (20 – 100 – 120 Hz)
kW
1.3 – 7.5 – 8.3
Coeficient EER
>8
SEER
4.6
Class
B
SCOP (Warm Zone)
4.1
Class
A+
Sound Power at Low Speed
dBA
34
Sound Power at Medium Speed
dBA
40
Sound Power at High Speed
dBA
50
REFRIGERANT
Type
R-410A
Global Warming Potential (GWP) (3)
2088
Frigorific Connection Liquid Line
“
3/8
Frigorific Connection Gas Line
“
1/2
Charge (4)
kg
-
DRAINAGE
Condensate Pump
YES
Available Pressure
mm. W.G
400
INDOOR HEAT EXCHANGER
Type
Aluminum Fins and Copper Pipes
Frontal Surface
m2
0.360
Fins Size
mm
2.1
Piping Diameter
mm
7.2
ELECTRICAL SPECIFCATIONS
Power Supply
V / phases /
Hz
220-240 / I / 50
Electric Connections
mm²
2 x 1.5 + T
Interconnection with Termostat
Twisted Pair + Shielded
Interconnection Between Units
Twisted Pair + Shielded
INDOOR FAN
Diameter
mm
380
Voltage
V
220-240 / I / 50
Motor Power
kW
0.13
Transmission
AC Integrated Motor 3 Speeds
Rated Airflow
m3/h
840 / 1000 / 1200
DIMENSIONS AND WEIGHT
Length
mm
830
Width
mm
830
Height
mm
300
Weight
kg
31
(1) Cooling Rated Conditions: Internal temperature DB: 27ºC, Internal temperatura WB: 19ºC
(2) Heating Rated Conditions: Internal temperature DB: 20ºC
(3) GWP: Global warming potential (climatic) of 1 kg of greenhouse gas relative to 1 kg of CO2,
calculated in terms of 100-year warming potential.
(4) Only the outdoor units which has serial “FLARE” valve (not from option) are charged with
refrigerant, the rest come Pre-Charged with dry nitrogen.
14
Page 15
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
CONSTRUCTION DETAILS
DIMENSIONS
CSTIBA 301
1. Drain
2. Cooling Connections
3. Electrical Panel
15
Page 16
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
CONSTRUCTION DETAILS
CCHIBA 301
16
4. Compressor
5. Outdoor Heat Exchanger
6. Electrical Panel
7. Outdoor Turbine
8. Outdoor Drain Diameter 3/4" Male
9. Cooling Connections
10. Electrical Connections Inputs
11. Main Switch
Page 17
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
When working with the machines in operation, discharge line temperature is
very HIGH and could hurt people.
REFRIGERANT LINES
For more information on the dimensioning of the refrigeration lines, request document with reference 207682 Rev100.
COOLING CIRCUIT
Split systems demand a correct disposition of refrigerant piping and a correct connection between both indoor and outdoor
units.
Pressure drop of the line
Circulation speed of the refrigerant
Refrigerant mass
DISCHARGE LINES
In heat pump operation, the low pressure line works as high pressure line.
LINES POSITION
1. When indoor unit is at a lower level than outdoor unit:
It is not essential to install traps in the vertical line. However, it could be convenient to install some every 6 to 9 meters
in order to help oil return.
17
Page 18
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
R410A
Liquid line
Ø
3/8”
1/2”
5/8”
3/4”
7/8”
1 1/8”
1 3/8”
Gas quantity
gr/m
52
100
166
244
341
538
867
2. When indoor unit is at the same level as outdoor unit:
Rise the suction line to a higher level than the exchanger in order to avoid liquid refrigerant back to the compressor.
3. When indoor unit is at a higher level than outdoor unit.
NOTES:
Refrigerant lines should be as short and straight as possible.
Use recommended diameters to reduce quantity of refrigerant in the system.
Fasten the tubes to fixe elements by means of braces to avoid vibration.
Carry out welding works in dry nitrogen atmosphere inside the pipe to be welded -USE A BOTTLE WITH PRESSURE
REGULATOR- to avoid the appearance of oxide and to expel rest of polluting material or humidity. Use rods with a
minimum 15% of silver alloy.
Insulate suction line in order to avoid condensation. Liquid line will be insulated only when exposed to high
temperatures (solar radiation, etc.).
Horizontal segment of suction line: 4% pitch towards the compressor.
18
Page 19
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
It is forbidden by law to expel refrigerant into the atmosphere; therefore, it is
necessary to recover all the refrigerant and to avoid leaks.
caution previously the realization of unions.
In addition to refrigerant, sometimes it’s necessary to add oil. For more than 25 meters, add 30 grams.
If liquid line is descendant and there is a considerable height difference, you have to compensate the excess pressure
before the expansion.
If liquid line is ascendant and there is a considerable height difference, the formation of gas refrigerant before the
expansion must be avoided.
If you do not find the right pipe diameter, you can use the immediately lower diameter. The system will function
normally only with a slight capacity reduction.
Units without valves come loaded with nitrogen pressure leak test. Drain with
Units CSTIBA/CCHIBA are supplied with nitrogen charge at a pressure between 5 and 6 bar. Before proceeding
to any welding work, it’s necessary to remove this charge out of the circuit. Once you have finished, only qualified
and trained service staff can make the vacuum and charge with the right amount of refrigerant.
19
Page 20
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
Never use oxygen to carry out leak tests. Oxygen reacts violently when in contact
death.
REFRIGERANT CHARGE
with oil and could cause an explosion resulting in damage, personal injuries or even
Should it be necessary to add or recover refrigerant, do it always in LIQUID phase, never in gas or vapour phase
since this would cause wrong mixing conditions.
Due to its high pressure and quick evaporation, refrigerant R410A cannot be kept in liquid phase inside charge
cylinder because bubbles would form, making reading difficult. Use always a scale to charge the unit with refrigerant.
If it’s necessary to make welding operations, you must fill the circuit with dry
nitrogen. Combustion of R410A refrigerant generates toxic gases.
Repair immediately any refrigerant leak.
Never overcharge the system.
Never use compressor as a vacuum pump.
If symptoms of refrigerant loss appear during operation, it’s necessary to carry out a leak test. Leak detectors usually
employed with CFC and HCFC cannot be used with R410a, due to chlorine in its composition. A leak detector for
R134A can be used but the sensitibity will be lower (when sensitibity is 1 for R134A, it falls to 0,6 for R410A).
To find small leaks, you will need a detector for HCF. Sensitibity for R410A is approx. 23 grams per year.
If a gas leak is found, it will be necessary to remove and completely recover the refrigerant charge. Pressurize the
system with dry nitrogen. If no leakage is detected, then do the vacuum and charge again with refrigerant.
20
Page 21
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
than a qualified technician can switch on electrical power.
MAINTENANCE
Before performing any service or maintenance operation, turn off the main power
switch of the system to avoid any personal injuries. Locked it so that nobody other
It is advisable to do maintenance works every 1.000 operating hours as well as at the beginning of each cooling season.
• Coils: At least once a year, clean condenser coils with water and detergent, then dry with air at a low pressure. Never
clean with wire brush.
• Fans and motors: Adjust transmission belt at least twice during the first month of operation and then check every 1.000
hours. Fan and motors do not need additional lubrication.
• Drainage system: Verify condition and good operation of the drainage tray and siphon.
• Refrigeration circuit: Check for oil refrigerant leaks, noises or system’s vibrations. Take measurements of temperatures
and pressures of components and record them on the maintenance form.
• Electrical circuit: Make sure that all electrical connections -wires, contactors, and terminals- are properly tight. Record
the values (volts and amperes) of each compressor and fan motor. Verify the starting current. Check the good operation
of all relays, pressostats and phase sequence relay of Scroll compressor.
• Air filters: Clean filters after the first 4 operating hours and then every 3 months (or even before). Wash filters with water
and detergent, rinse thoroughly and let dry.
21
Page 22
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
Refrigerant data
Safety data: R410A
Toxicity
Low
Contact with Skin
R410A vapours can irritate the skin and eyes. In liquid form, it can freeze
skin on contact. If contact with skin occurs, flush the exposed area with
lukewarm water until all of the chemical is removed. If there is evidence of
frostbite, bathe in lukewarm water.
Contact with Eyes
If contact with eyes occurs, immediately flush with large amounts of
lukewarm water for at least 15 minutes, lifting eyelids occasionally to
facilitate irrigation. Seek medical attention as soon as possible.
Ingestion
Very unlikely - should something happen, it will cause frost burns. Do not
induce vomiting. Only if the patient is conscious, wash out mouth with water
and give some 250 ml of water to drink. Then, obtain medical attention.
Inhalation
Inhalation of the R410A vapour may cause irritation. Vapour inhalation at
high concentrations may result in asphyxiation or the heart may become
sensitized, causing cardiac arrhythmia. When concentration of R410A reach
levels which reduce oxygen to 14-16% by displacement, symptoms of
asphyxiation will occur. An individual exposed to high concentrations of
R410A must be given medical attention immediately. Adequate ventilation
must be provided at all times.
Recommendations
Semiotics or support therapy is recommended. Cardiac sensitisation has
been observed that, in the presence of circulating catecholamines such as
adrenalin, may cause cardiac arrhythmia and accordingly, in case of
exposure to high concentrations, cardiac arrest.
Prolonged Exposure
R410A: a study on the effects of exposure to 50,000 ppm during the whole
life of rats has identified the development of benign testicle tumour.
This situation should therefore be negligible for personnel exposed to
concentrations equal to or lower than professional levels.
R410A: is stable under normal operating conditions.
Conditions to Avoid
Do not use in the presence of high temperatures, flames, burning surfaces
and excess humidity.
Hazardous Reactions
Contact with certain red-hot metals may result in exothermic or explosive
reactions and yield toxic and/or corrosive decomposition products. Specific
materials to avoid include freshly abraded aluminium surfaces and active
metals such as sodium, potassium, calcium, powdered aluminium,
magnesium and zinc.
Hazardous Decomposition
Products
R410A: Halogen acids produced by thermal decomposition and hydrolysis.
APPENDIX: SAFETY DATA R410A
22
Page 23
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLIT HORIZONTAL INVERTER UNITS
PACKAGED AIR-AIR
General Precautions
Do not inhale concentrated vapours. Their concentration in the atmosphere
should not exceed the minimum preset values and should be maintained
below the professional threshold. Being weightier than the air, the vapour
concentrates on the bottom, in narrow areas. T here fore, the exhaust
system must work at low level.
Respiratory System Protection
If you are in doubt about the concentration in the atmosphere, it is
recommended to wear a respirator approved by an accident prevention
Authority, of the independent or oxygen type.
Storage
Cylinders must be stored in a cool, dry and properly ventilated storage area
away from heat, flames, corrosive chemicals, flumes, explosives and be
otherwise protected from damage. Keep a temperature below 52°C.
Protective Clothing
Wear overalls, protective gloves and goggles or a mask.
Accidental Release Measures
IIt is important to wear protective clothing and a respirator. Stop the source
of the leak, if you can do this without danger. Negligible leaks can be left
evaporating under the sun, providing that the room is well ventilated.
Considerable leaks: ventilate the room. Reduce the leak with sand, earth or
other absorbing substances. Make sure that the liquid does is not
channelled into gutters, sewers or pits where the vapours are likely to create
a stuffy atmosphere.
Disposal
The best method is recovery and recycling. If this method is not practicable,
dispose according to an approved procedure, which shall ensure the
absorption and neutralization of acids and toxic agents.
Fire Fighting Information
R410A: Not flammable in the atmosphere.
Cylinders
The cylinders, if exposed to fire, shall be cooled by water jets; otherwise, if
heated, they may explode.
Protective Fire Fighting
Equipment
In case of fire, wear an independent respirator and protective clothing.
23
Page 24
IOM_CCHIBA-CSTIBA_301_207925_170706_EN
CCHIBA/CSTIBA
SPLITHORIZONTALINVERTER UNITSPACKAGED AIR-AIR
We reserve the right to add modifications without prior notice
24